05000335/FIN-2014004-02
From kanterella
Jump to navigation
Jump to search
Finding | |
---|---|
Title | Failure to Establish a Reasonable Maintenance Effectiveness Demonstration for the ECCS Floor Drain Valve System |
Description | An NRC-identified non-cited violation (NCV) of 10 CFR 50.65(a)(2), Requirements for Monitoring the Effectiveness of Maintenance at Nuclear Power Plants, resulted from the licensees failure to establish a technically justifiable and reasonable maintenance effectiveness demonstration for the emergency core cooling system (ECCS) floor drain valve system. Corrective actions included a revision to the maintenance rule (MR) system function and the reliability performance criteria, the completion of a 3-year extent of condition review to identify all missed functional failures, entering the valve actuators into the licensees air-operated valve program, and monitoring the performance of the Unit 1 ECCS floor drain valve system as required by 10 CFR 50.65(a)(1). This issue was entered into the licensees corrective action program as action request 1936612. The performance deficiency was more than minor because it involved degraded system performance which, if left uncorrected, could become a more significant safety concern. The inspectors evaluated the significance of the finding under the mitigating systems cornerstone using Table 2 of Attachment 4 (dated June 19, 2012) and Exhibit 2 of Appendix A (dated June 19, 2012) to Inspection Manual Chapter 0609, Significance Determination Process, (dated June 2, 2011). The inspectors determined the finding was of very low safety significance (i.e., Green) because the exhibit criteria did not screen the finding to a detailed risk assessment. The inspectors concluded the finding was associated with the cross-cutting aspect of trending (P.4) in the problem identification and resolution area because the licensee had failed to utilize the corrective action program to associate and identify an adverse trend related to repeated system failures in the aggregate to identify common cause and programmatic issues. |
Site: | Saint Lucie |
---|---|
Report | IR 05000335/2014004 Section 1R12 |
Date counted | Sep 30, 2014 (2014Q3) |
Type: | NCV: Green |
cornerstone | Mitigating Systems |
Identified by: | NRC identified |
Inspection Procedure: | IP 71111.12 |
Inspectors (proximate) | D Dumbacher J Reyes J Rivera Ortiz M Coursey T Hoeg T Morrissey |
Violation of: | 10 CFR 50.65(a)(1) 10 CFR 50.65(a)(2) 10 CFR 50.65 |
CCA | P.4, Trending |
INPO aspect | PI.4 |
' | |
Finding - Saint Lucie - IR 05000335/2014004 | ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
Finding List (Saint Lucie) @ 2014Q3
Self-Identified List (Saint Lucie)
| ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||