05000331/FIN-2014005-04
From kanterella
Jump to navigation
Jump to search
Finding | |
---|---|
Title | Failure to Accomplish Procedure for Leaking Pipe Snubber |
Description | A finding of very low safety significance and an associated non-cited violation of Title 10 of the Code of Federal Regulations, Part 50, Appendix B, Criterion V, Instructions, Procedures, and Drawings, was identified by the inspectors for the licensees failure to accomplish procedure EN-AA-203-1001, Operability Determinations/Functionality Assessments. Specifically, on May 8, 2014, the licensee failed to properly evaluate functionality of a leaking pipe snubber associated with the A core spray subsystem, the resultant operability impact on the Technical Specification affected systems, and the extent of condition. The licensee entered the inspectors concerns into the Corrective Action Program as condition report 02003867 and 02010686. Corrective actions included coaching/training of licensed operators during requalification training and management review committee members, and changes to applicable snubber program procedures. The performance deficiency was determined to be more than minor because it impacted the Mitigating System cornerstone attribute of equipment performance, and adversely affected the cornerstone objective of ensuring the availability, reliability, and capability of systems that respond to initiating events to prevent undesirable consequences. Because the finding did not involve the total loss of any safety function, the finding screened as very low safety significance (Green). This finding was associated with the cross-cutting aspect of consistent process in the area of Human Performance, because the licensees inconsistent application of the systematic operability/functionality determination process to evaluate the leaking snubber led to prolonged exposure of the extent of cause that affected several safety-related systems. [H.13] |
Site: | Duane Arnold |
---|---|
Report | IR 05000331/2014005 Section 1R15 |
Date counted | Dec 31, 2014 (2014Q4) |
Type: | NCV: Green |
cornerstone | Mitigating Systems |
Identified by: | NRC identified |
Inspection Procedure: | IP 71111.15 |
Inspectors (proximate) | A Boland A Dahbur C Phillips G O'Dwyer J Beavers J Gilliam J Heath J Jacobson J Steffes L Haeg M Jeffers M Jimenez M Phalen N Feliz-Adorno R Murray R Ng S Smith T Bilik V Meyers |
Violation of: | 10 CFR 50 Appendix B Criterion V Technical Specification Technical Specification - Procedures |
CCA | H.13, Consistent Process |
INPO aspect | DM.1 |
' | |