05000324/FIN-2015002-04
From kanterella
Jump to navigation
Jump to search
Finding | |
---|---|
Title | 2C Residual Heat Removal Service Water (RHRSW) Pump Oil Leak |
Description | The inspectors opened a URI to review the licensees evaluation of the motor oil leak on the 2C RHRSW pump and determine if there is a performance deficiency. On April 8, 2015, the licensee identified an oil leak on the motor for the 2C RHRSW pump in excess of the amount that would be acceptable for the pump to meet the 30-day mission time, and the pump was declared inoperable. The licensees immediate corrective actions were to apply sealant to the mechanical joints of the bearing housings. The licensee entered this issue in the CAP as NCR 742643. This issue is being tracked as a URI: URI 05000324/2015002-04, 2C Residual Heat Removal Service Water Pump Oil Leak. |
Site: | Brunswick |
---|---|
Report | IR 05000324/2015002 Section 1R19 |
Date counted | Jun 30, 2015 (2015Q2) |
Type: | URI: |
cornerstone | Mitigating Systems |
Identified by: | NRC identified |
Inspection Procedure: | IP 71111.19 |
Inspectors (proximate) | D Jones G Hopper M Bates M Catts M Schwieg M Singletary W Loog Hopperm Catts M Orr M Riches M Schwieg |
INPO aspect | |
' | |
Finding - Brunswick - IR 05000324/2015002 | ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
Finding List (Brunswick) @ 2015Q2
Self-Identified List (Brunswick)
| ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||