05000266/LER-1997-022, Forwards LER 97-022-00 Re Electrical Short Circuits During CR Fire That Could Affect Safe Shutdown Capability.App R Rebaselining Project Team Discovered Design Condition During Review of NRC Information Notice in 92-018

From kanterella
Jump to navigation Jump to search
Forwards LER 97-022-00 Re Electrical Short Circuits During CR Fire That Could Affect Safe Shutdown Capability.App R Rebaselining Project Team Discovered Design Condition During Review of NRC Information Notice in 92-018
ML20140D759
Person / Time
Site: Point Beach NextEra Energy icon.png
Issue date: 06/05/1997
From: Dante Johnson
WISCONSIN ELECTRIC POWER CO.
To:
NRC OFFICE OF INFORMATION RESOURCES MANAGEMENT (IRM)
Shared Package
ML20140D766 List:
References
IEIN-92-018, IEIN-92-18, NPL-97-0326, NPL-97-326, NUDOCS 9706110086
Download: ML20140D759 (1)


LER-2097-022, Forwards LER 97-022-00 Re Electrical Short Circuits During CR Fire That Could Affect Safe Shutdown Capability.App R Rebaselining Project Team Discovered Design Condition During Review of NRC Information Notice in 92-018
Event date:
Report date:
2662097022R00 - NRC Website

text

. _ . _ _ _ _ _ _ . _ _ . _ _ _. _ ____. _ . . - - _ . _ _

Wisconsin

. Electnc POVER COMPANY l

231 W Michigon. PO Box 2046. Milwaukee. WI 53201 2046 (414)221-2345 NPL 97-0326 June 5,1997 Document Control Desk i U.S. NUCLEAR REGULATORY COMMISSION Mail Station PI-137 Washington, D. C. 20555 Gentlemen:

l l

l DOCKET 50-266 AND 50-301 l LICENSEE EVENT REPORT 97-022-00 ELECTRICAL 5llORT CIRCUITS DURING A CONTROL ROOM FIRE l COULD AFFECT SAFE S11UTDOWN CAPABILITY j POINT BEACII NUCI EAR PLANT. UNITS 1 AND 2 Enclosed is Licensee Event Report 97-022-00 for Point Beach Nuclear Plant, Units 1 and 2. This report is provided in accordance with 10 CFR 50.73(a)(2)(v)(A),"Any event or condition that alone could have prevented the l fulfillment of the safety function of structures or systems that are needed to shut down the reactor and maintain it in l a safe shutdown condition." This report describes the potential for a postulated control room fire to cause hot I

electrical shorts in motor-operated valve control circuits that could disable the valve and hinder the capability of achieving safe shutdown. Our Appendix R Rebaselining Project team discovered this design condition during review of NRC Information Notice IN 92-18," Potential for Loss of Remote Shutdown Capability During Control Room Fire" If you require additional information, please contact us.

Sincerely, l te>vra $ wS O Douglas F. Johnson Manager ,

Regulatory Services and Licensing l

GDA/kmc l Enclosure I 3