Title | Adequate Voltage not Assured for EDG Air Start Solenoid Valve |
Description | The inspectors identified a finding of very low safety significance and associated NCV of 10 CFR Part 50, Appendix B, Criterion III, Design Control, for the failure to assure and verify adequate voltage was available at the air start solenoid associated with Unit 2 and Unit 2/3 emergency diesel generators. Specifically, the licensee failed to assure the minimum available voltage at the air start solenoid met the minimum rated voltage value for the solenoid. The licensee entered this finding into their Corrective Action Program and provided test results and calculations to reasonably conclude the currently installed air start solenoid valves would energize at the minimum calculated available voltage. The performance deficiency was determined to be more than minor because it was associated with the Mitigating Systems cornerstone attribute of design control and affected the cornerstone objective of ensuring capability and reliability of systems that respond to initiating events to prevent undesirable consequences. The finding screened as very low safety significance (Green) because the finding was a design deficiency that did not result in a loss of operability or functionality. The inspectors did not identify a cross-cutting aspect associated with this finding because the finding was not representative of current performance. |
Site: | Dresden |
---|---|
Report | IR 05000237/2013007 Section 1R21 |
Date counted | Jun 30, 2013 (2013Q2) |
Type: | NCV: Green |
cornerstone | Mitigating Systems |
Identified by: | NRC identified |
Inspection Procedure: | IP 71111.21 |
Inspectors (proximate) | B Sherbin A Stone J Corujo-Sandin G Morris A Dunlop M Munir B Palagi |
Violation of: | 10 CFR 50 Appendix B Criterion III, Design Control |
INPO aspect | |
' | |
Finding - Dresden - IR 05000237/2013007 | ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
Finding List (Dresden) @ 2013Q2
Self-Identified List (Dresden)
| ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||