05000219/FIN-2015001-02
From kanterella
Jump to navigation
Jump to search
Finding | |
---|---|
Title | Inadequate Post Maintenance Testing for Emergency Service Water Pump Breaker |
Description | The inspectors identified an NCV of 10 CFR 50, Appendix B, Criterion V, Instructions, Procedures, and Drawings for Exelons failure to develop an adequate post maintenance test to determine operability of the A emergency service water pump breaker. Specifically, the corrective maintenance work performed on April 16, 2013, did not correct the cause of the failure and Exelon did not perform an adequate post maintenance test to verify conditions had been corrected. As a result, the emergency service water system was returned to service even though it did not meet all the requirements for operability. The issue was not identified and resolved until a subsequent surveillance test on April 17, 2013, which identified a failed breaker. Exelon entered this issue into their corrective action program (IR 2471069). Planned corrective actions include revising work order activities to specify the correct post maintenance test. This performance deficiency is more than minor because it is associated with the Equipment Performance attribute of the Mitigating Systems cornerstone, and adversely affected its objective to ensure the availability and reliability of the systems that respond to initiating events. Specifically, the inadequate post maintenance test for A emergency service water pump breaker on April 16, 2013, led to the A emergency service water pump failing to perform its function during the subsequent surveillance testing on April 17, 2013. The inspectors assessed this finding in accordance with the IMC 0609, Appendix A, The Significance Determination Process (SDP) for Findings At-Power. The inspectors concluded that this finding did not represent an actual loss of function of the emergency service water system for greater than its technical specification allowed outage time (15 days). Therefore, the inspectors determined that this finding is of very low safety significance (Green). The inspectors determined that this finding had a cross-cutting aspect in the area of Human Performance, Work Management, in that Exelons work planning and executing of work activities did not include documented instructions for performing an adequate post maintenance test. |
Site: | Oyster Creek |
---|---|
Report | IR 05000219/2015001 Section 4OA2 |
Date counted | Mar 31, 2015 (2015Q1) |
Type: | NCV: Green |
cornerstone | Mitigating Systems |
Identified by: | NRC identified |
Inspection Procedure: | IP 71152 |
Inspectors (proximate) | S Kennedy T O'Hara A Patel B Bollinger E Andrews E Burket J Kulp J Patel M Orr N Floyd P Kaufman |
Violation of: | 10 CFR 50 Appendix B Criterion V Technical Specification Technical Specification - Procedures |
CCA | H.5, Work Management |
INPO aspect | WP.1 |
' | |