Finding | |
---|---|
Title | Failure to Review the Impact of Site Staffing Changes to the Fire Protection Program |
Description | The team identified that in July 2002, AmerGen failed to review a change to personnel resources that would increase the time necessary to complete an NRC approved hot shutdown repair after a fire in the A 480V switchgear room. Specifically, AmerGen eliminated the need for onsite electrical or instrument and controls technician staffing at all times. This finding was determined to be of very low safety significance (Green) and a NCV of Oyster Creek Nuclear Generating Station Facility Operating License condition 2.C.(3) Fire Protection. AmerGens immediate corrective actions for this issue included assessing current call-in processes to verify the hot shutdown repair would be completed by qualified personnel within the safe shutdown analysis time requirement. The team determined that this finding was more than minor because it was associated with the external factors attribute (fire) of the mitigating systems cornerstone objective to ensure the availability, reliability, and capability of systems that respond to initiating events to prevent undesirable consequences (i.e. core damage). Specifically, AmerGen did not analyze the reduction in personnel readiness for an adverse impact on implementing a hot shutdown repair to Bus USS 1B2 within the safe shutdown analysis time requirement. This finding was also similar to more than minor example 3.i in NRC Inspection Manual Chapter (IMC) 0612, Power Reactor Inspection Reports, Appendix E, Examples of Minor Issues. The team assessed this finding in accordance with NRC IMC 0609, Appendix F, Fire Protection Significance Determination Process. This finding screened to very low safety significance (Green) in phase 1 of the SDP because it was assigned a low degradation rating. A low degradation rating was assigned because actual emergency response organization call-in and drive-in data demonstrated that the hot shutdown repair would most likely be completed within the safe shutdown analysis time requirement. (Section 1R05.01 |
Site: | Oyster Creek |
---|---|
Report | IR 05000219/2008008 Section 1R05 |
Date counted | Jun 30, 2008 (2008Q2) |
Type: | NCV: Green |
cornerstone | Mitigating Systems |
Identified by: | NRC identified |
Inspection Procedure: | IP 71111.05 |
Inspectors (proximate) | J Tifft J Rogge M Patel J Daniel Or |
INPO aspect | |
' | |
Finding - Oyster Creek - IR 05000219/2008008 | |||||||||||||||||||||||||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
Finding List (Oyster Creek) @ 2008Q2
| |||||||||||||||||||||||||||||||||||||