Pages that link to "05000409/LER-1978-010, Forwards LER 78-010/03L-0"
Jump to navigation
Jump to search
The following pages link to 05000409/LER-1978-010, Forwards LER 78-010/03L-0:
Displayed 12 items.
- ML20147A938 (redirect page) (← links)
- 05000409/LER-1978-013-03, /03L-0 on 781202:periodic Leakage Rate Test for Personnel Did Not Meet Type B Test Criteria as Specified by Tech Specs.Test Strongbacks Were Not Completely Tightened Thereby Causing Seal to Stretch Upon Initial Pressurizatio (← links)
- 05000409/LER-1978-013, Forwards LER 78-013/03L-0 (← links)
- 05000409/LER-1978-010-03, /03L-0 on 780811:During Change of Engine Sump Lube Oil on 1A Diesel Generator,Lube Oil Was Diluted with Diesel Fuel oil.1B Diesel Generator & Other AC Sources Provided Required Elec Pwr.(Encl to 7809270110) (← links)
- 05000409/LER-1978-010 (redirect page) (← links)
- 05000409/LER-1978-008-03, /03L-0 on 780620:zone 13 Fire & Smoke Detection Sys Placed on Bypass Following False Alarms.Caused by Malfunctioned Detector Head Which Had Been Overlooked by Personnel Implementing Tech Specs (← links)
- 05000409/LER-1978-008, Forwards LER 78-008/03L-1 (← links)
- 05000409/LER-1978-012-01, /01T-0 on 781126:Leakage Rate Test for Emergency Airlock Did Not Meet Type B Test Criteria Req by Tech Specs. Leakage Rate Was 1.037 Scfh in Excess of Limit.Leakage Was Due to Scratches on Valve Seats.Valve Was Replaced (← links)
- 05000409/LER-1978-012, Forwards LER 78-012/01T-0 (← links)
- 05000409/LER-1978-011, Forwards LER 78-011/01T-0 (← links)
- 05000409/LER-1978-014-03, /03L-0 on 781215:during Routine Surveillance Test on 1B Emergency Diesel Generator,Unit Tripped on Indicated Overspeed.Problem Duplicated 781218 & Unit Declared Inoperable.Due to Erroneously Set Switch Setpoint (← links)
- 05000409/LER-1978-014, Forwards LER 78-014/03L-0 (← links)