The following pages link to 05000306/LER-1982-009, Forwards LER 82-009/03L-0:
Displayed 48 items.
- ML20054F182 (← links)
- 05000306/LER-1982-009 (redirect page) (← links)
- ML20053E960 (redirect page) (← links)
- 05000306/LER-1982-027, Forwards LER 82-027/03L-0 (← links)
- 05000282/LER-1982-016, Forwards LER 82-016/03L-0 (← links)
- 05000282/LER-1982-015, Forwards LER 82-015/01T-0 (← links)
- 05000306/LER-1982-014, Forwards LER 82-014/03L-0 (← links)
- 05000306/LER-1982-013, Forwards LER 82-013/03L-0 (← links)
- 05000306/LER-1982-010, Forwards LER 82-010/01T-0 (← links)
- 05000306/LER-1982-012, Forwards LER 82-012/03L-0 (← links)
- 05000282/LER-1982-020, Forwards LER 82-020/03L-0 (← links)
- ML20069K308 (← links)
- 05000282/LER-1982-018, Forwards LER 82-018/03L-0 (← links)
- 05000282/LER-1982-019, Forwards LER 82-019/03L-0 (← links)
- 05000282/LER-1982-011, Forwards LER 82-011/03L-0 (← links)
- 05000282/LER-1982-021, Forwards Revised LER 82-021/03X-1 (← links)
- 05000282/LER-1982-011-03, /03L-0:on 820622,motor-driven Auxiliary Feedwater Pump 12 Failed to Start During Surveillance Test.Caused by Installing self-cleaning Oil Filter Backwards,Allowing Build Up of Sludge.Filter Reversed (← links)
- 05000282/LER-1982-022-03, /03L-0:on 821112,during Power Operation,Control Power Lost to Diesel Cooling Water Pump 22,rendering Pump Inoperable.Caused by Loose Fuse Clip.Clip Repaired & Pump Tested Satisfactorily (← links)
- 05000282/LER-1982-020-03, /03L-0:on 821026,during Surveillance Test, Auxiliary Bldg Special Vent Sys Pac Filter 121 Exhibited DOP Removal Efficiency of 98.6%,less than Tech Specs Requirement.Caused by Loose Filters.Filters Tightened (← links)
- 05000282/LER-1982-018-03, /03L-0:on 820915,discovered That Two Ventilation Flow Tests Not Performed as Scheduled.Caused by Personnel Error.Tests Rescheduled (← links)
- 05000282/LER-1982-019-03, /03L-0:on 820917,diesel Cooling Water Pump 22 Did Not Start on Demand During Testing.Start Attempt 7 Minutes Later Successful.Cause Unknown.In 5 Days of Testing,Failure Could Not Be Reproduced (← links)
- 05000306/LER-1982-017-03, /03L-0:on 820908,two Undervoltage Relays Found to Trip Outside Tolerance Band of 90 Plus or Minus 2% of Nominal Voltage.Cause Not Stated.Relays Recalibr (← links)
- 05000306/LER-1982-027-03, /03L-0:on 821208,containment Vacuum Breaker Isolation Valve Inoperable for Approx 8 H When Air Supply Line Disconnected from Tubing Fitting.No Defects in Mfg or Installation of Fitting Detected.Fitting Repaired (← links)
- 05000282/LER-1982-016-03, /03L-0:on 820906,spike Occurred in RCS Activity Up to 1.38 Uci/G Dose Equivalent I-131.Caused by Reactor Trip & Subsequent Washout of Fission Product from Existing Fuel Defects.Region 9 Fuel Will Be Removed (← links)
- 05000282/LER-1982-015-01, /01T-0:on 820827,while Performing Operability Test on D2 Diesel Generator,Procedure Step Missed Resulting in Auto/Manual Switch for D2 Supply to Bus 16 Being Left Open. Caused by Personnel Error (← links)
- 05000306/LER-1982-014-03, /03L-0:on 820725,during Startup Operations, Flux Difference of Two ex-core Channels Deviated from Target Band for Greater than 15 Minutes.Caused by Personnel Error. Personnel Will Review Rept (← links)
- 05000306/LER-1982-013-03, /03L-0:on 820719,pressurizer Steam Space Sample Isolation valve,CV-31303,would Not Close on Demand.Cause Unknown.Valve Inaccessible During Operation.Repairs Will Be Made During Shutdown.Manual Valve in Penetration Closed (← links)
- 05000306/LER-1982-010-01, /01T-0:on 820618,during Local Leakage Rate Testing at Refueling,One Containment Purge Supply Valve Leaked in Excess at Tech Specs.Cause Not Stated.Blind Flanges Will Be Installed on Containment Purge Penetrations (← links)
- 05000306/LER-1982-012-03, /03L-0:on 820702,radiation Monitor Sample Return Isolation Valve Gave Dual (Open/Closed) Indication.Cause Not Determined.Valves Will Be Cycled Periodically (← links)
- 05000306/LER-1982-009-03, /03L-0:on 820505,during Surveillance Testing of SI Pump 22,test Isolation Valve Found Closed.Caused by Improper Restoration of Sys After Maint.Design Change Initiated (← links)
- 05000282/LER-1982-005-03, /03L-0:on 820322,review of Chemistry Logs Showed That Boric Acid Tank 11 Had Not Been Sampled.Caused by Communication Breakdown.Tank Sampled & Involved Personnel Will Review Rept (← links)
- 05000282/LER-1982-005, Forwards LER 82-005/03L-0 (← links)
- 05000282/LER-1982-006-01, /01T-0:on 820423,during Surveillance Test Sp 1104, Measured Reactor Coolant Boron Concentration Higher than Originally Predicted Value.Caused by Miscalculation of Predicted Worth.Analysis Performed to Monitor Disagreement (← links)
- 05000282/LER-1982-006, Forwards LER 82-006/01T-0 (← links)
- 05000306/LER-1982-004-03, /03L-0:on 820226,maint Workman Accidentally Bumped Overspeed Trip Mechanism on Auxiliary Feedwater Pump, Tripping Valve & Making Pump Inoperable.Caused by Personnel Error.Valve Operator Reset (← links)
- 05000306/LER-1982-004, Forwards LER 82-004/03L-0 (← links)
- 05000306/LER-1982-002-03, /03L-0:on 820125,one Overpower Delta T Summing Unit Found Out of Spec High.Caused by Instrument Drift. Device Recalibr (← links)
- 05000306/LER-1982-002, Forwards LER 82-002/03L-0 (← links)
- 05000282/LER-1982-001-03, /03L-0:on 820125,one Overpower Delta T Summing Unit Found Out of Spec.Caused by Foxboro Model 66RC-OL Summing Unit Instrument Drift.Device Recalibr.Evaluation Underway (← links)
- 05000282/LER-1982-001, Forwards LER 82-001/03L-0 (← links)
- 05000282/LER-1982-003-03, /03L-0:on 820209,during Annual Visual Insp,One Steam Exclusion Control Damper Found Inoperable.Caused by Failure of Drive Gear in Pacific Air Products Damper Model R-35-FS.Gear Replaced (← links)
- 05000282/LER-1982-003, Forwards LER 82-003/03L-0 (← links)
- 05000282/LER-1982-029-01, /01T-0:on 821228,tiny through-wall Crack Found in heat-affected Zone of Weld on Safety Injection Supply Line from Boric Acid Storage Tanks.Cause Unknown. Fracture Mechanics Analysis Underway (← links)
- 05000282/LER-1982-029, Forwards LER 82-029/01T-0 (← links)
- 05000306/LER-1982-025, Signed LER 82-025/03L-0:on 821130,during Power Reduction,One Steam Flow Channel Differed from Redundant Channels. Transmitter Showed Out of Calibr.Cause Unknown.Transmitter Recalibr.Bistables Placed in Trip During Recalibr (← links)
- 05000306/LER-1982-025-03, /03L-0:on 821130,one Steam Flow Channel Differed from Redundant Channels During Power Reduction Due to out- of-calibr Transmitter.Cause Not Known.Transmitter Recalibr & Returned to Svc.Transmitter to Be Replaced If Drift Rec (← links)
- 05000306/LER-1982-024-03, /03L-0:on 821123,diesel Generator D1 Inoperable for Approx 4 Minutes After Lockout of Engine Shutdown Circuit Occurred.Probably Caused by Sticky Action of Speed Switch.Further Exam of Circuitry Will Be Performed (← links)
- 05000306/LER-1982-024, Forwards LER 82-024/03L-0 (← links)