Pages that link to "05000275/LER-1982-003, Forwards LER 82-003/03L-0"
Jump to navigation
Jump to search
The following pages link to 05000275/LER-1982-003, Forwards LER 82-003/03L-0:
Displayed 24 items.
- ML20042A772 (redirect page) (← links)
- 05000275/LER-1982-007, Forwards LER 82-007/03L-0 (← links)
- 05000275/LER-1982-005, Forwards LER 82-005/03X-1 (← links)
- 05000275/LER-1982-009, Forwards LER 82-009/01T-0 (← links)
- 05000275/LER-1982-008, Forwards LER 82-008/03L-0 (← links)
- 05000275/LER-1982-012, Forwards LER 82-012/01T-0 (← links)
- ML20198H709 (← links)
- 05000275/LER-1982-012-01, /01T-0:on 821206,radiation Survey of Spent Fuel Pool Not Performed in Accordance W/Tech Spec 3.3.3.1.Caused by Personnel Error.Technician Counseled (← links)
- 05000275/LER-1982-011-03, /03L-0:on 821024,steam Generator Blowdown Effluent Line Flow Rate Measurement Device FR-53 Found Inoperable Prior to Fuel Load.Caused by Worn Motor Gear Assembly. Design Change Will Correct Erroneous Readings (← links)
- 05000275/LER-1982-010-01, /01T-0:on 821102,liquid Radwaste Sys Tank Discharge Initiated W/O Liquid Radwaste Effluent Monitor RE-18 Operable.Caused by Instrument Being Tagged Improperly. Procedure Revised (← links)
- 05000275/LER-1982-009-01, /01T-0:on 821007,testing on Auxiliary Saltwater Sys Revealed Sys Susceptible to Water Hammer Effects During Anticipated Operational Transients.Caused by Water Column Separation & Recombination at Piping Slope Change (← links)
- 05000275/LER-1982-008-03, /03L-0:on 820603,control Room Plant Vent Radiation Alarm on Plant Vent Iodine Monitor RE24 Sounded.Caused by Spurious Low Background Radiation Indication.Monitor Had Not Been Reset Properly (← links)
- 05000275/LER-1982-007-03, /03L-0:on 820526,prior to Fuel Load,Control Room Received Alarm on Plant Vent Iodine Sampler (RE-24).Caused by Failure of Sample Pump Due to End of Vane Life.Pump Cleaned,Vanes Replaced & Oil Changed (← links)
- 05000275/LER-1982-006-03, /03L-0:on 820423,steam Generator Blowdown Tank Vent Sys Gross Activity Monitor Would Not Respond to Calibr Check Sources within Specified Range.Caused by Photomultiplier Tube end-of-life & Electronic Interference (← links)
- 05000275/LER-1982-006, Forwards LER 82-006/03L-0 (← links)
- 05000275/LER-1982-003, Forwards LER 82-003/03X-1 (redirect page) (← links)
- ML20052A380 (redirect page) (← links)
- 05000275/LER-1982-003 (redirect page) (← links)
- 05000275/LER-1982-002-03, /03L-0:on 820222,air Sample Pumps for Plant Vent Radiation Monitors (RM 14A & B) Found Tripped.Caused by Clogging of Rad Monitor Filter Paper W/Debris from Const Activities (← links)
- 05000275/LER-1982-002, Forwards LER 82-002/03L-0 (← links)
- 05000275/LER-1982-004-03, /03L-0:on 820223 & 26,oily Water Separator Effluent Line Flow Rate Measurement Device (FR-251) Inoperable.Caused by Faulty Electronic Component on First Occasion & by Breakdown of Oscillator on Second (← links)
- 05000275/LER-1982-004, Forwards LER 82-004/03L-0 (← links)
- 05000275/LER-1982-003-03, /03L-0:on 820212,prior to Fuel Load,Operators Received Vital Instrument Ac Panel Under Voltage Alarm in Control Room.Caused by Tripped Feeder Breaker to PY-15. Event Under Investigation (← links)
- 05000275/LER-1982-001-03, /03L-0:on 820129,during Audit Prior to Fuel Load, Communication Phone Mounted on Front Section of Hot Shutdown Panel Was Discovered Excluded from Seismic Analysis.Caused by Coordination Failure.Panel Will Be Reanalyzed (← links)
- 05000275/LER-1982-001, Forwards LER 82-001/03L-0 (← links)