Finding | |
---|---|
Title | LICENSEE-IDENTIFIED Violation |
Description | Title 10 CFR 50.47(b)(4) requires, in part, that a standard classification and emergency action level scheme is in use by the licensee. Contrary to the above, on October 13, 2010, the licensee identified they had not maintained in effect a standard classification and emergency action level scheme. Specifically, the licensee identified seven examples of failures to implement emergency action level AA1-1 for airborne and liquid effluent releases in 2009 and 2010. In each example, the 200-times discharge permit specific alarm setpoint value could not be read on the associated process radiation monitor because the value was above the monitors operating range. This finding was more than minor because it impacted the Emergency Preparedness Cornerstone objective attribute of emergency response organization performance and was evaluated as having very low safety significance (Green) because it was a failure to comply with NRC requirements, was associated with a risk-significant planning standard, and was not a functional failure or degraded function of the planning standard. This condition was documented in Condition Reports CR-WF3-2010-6184 and CR-WF3-2010-6387. |
Site: | Waterford |
---|---|
Report | IR 05000382/2010005 Section 4OA7 |
Date counted | Dec 31, 2010 (2010Q4) |
Type: | NCV: Green |
cornerstone | Emergency Prep |
Identified by: | Licensee-identified |
Inspection Procedure: | |
Inspectors (proximate) | L Ricketson P Elkmann M Davis D Jones T Burns J Clark D Overland R Latta C Steely N Greene P Prescott |
INPO aspect | |
' | |
Finding - Waterford - IR 05000382/2010005 | ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
Finding List (Waterford) @ 2010Q4