c ,
e OPERATING DATA REPORT '
- - DOCKET NO. 50-269 ,
DATE 10-15-84 C051PLETED BY J.A. Reavis-TELEPHONE 704-373-7567 L OPERATING STATUS .
Oconee 1- Notes t 1. Unit Name:
'2. Reporting Period: September 1,1984-September 30,19E 4 Year-to-date and cumulative 2568 capacity factors are calcu-3.1.icensed Thermal Power (MWt): .-lated using a weighted-
- 4. Nameplate Rating (Gross alWe): 934-886 average for maximunt
- 5. Design Electrical Rating (Net MWe): dependable capacity.
- 6. Maximum Dependable Capacity (Gross MWe): 899
- 7. Maximum Dependable Capacity (Net MWe): 860
~ 8. If Changes Occur in Capacity Ratings (Items Number 3 Through 7) Since Last Report. Give Reasons:
None
- 9. Pow:er Level To Which Restricted. If Any (Net MWe): n-
- 10. Reasons For Restrictions.If Any:
This Month Yr. to.Date Cumulative
!!. Hours in Reporting Period 720.0 6 575.0 98 280.0
- 12. Number Of Hours Reactor Was Critical 720.0 6 550.L 71 090.7
- 13. Reactor Reserve Shutdown Hours -- ---
- 14. Hours Generator On.Line 720.0 6 542.1 '67'931.4
- 15. Unit Reserve Shutdown Hours --- --- ---
- 16. Gross Thermal Energy Generated (51WH) 1 853 273- 16 773 666 163 071 698
. 17. Gross Electrical Energy Generated (MWH) 635 81o s' asa inn 56 722 530
- 18. Net Electrical Energy Generated (MWH) 606 279 5 596 927 53 762 478
- 19. Unit Service Factor 100.0 99.5 69.1
- 20. Unit Availability Factor 100.0 99.5 69.2
- 21. Unit Capacity Factor (Using MDC Net) 97.9 99.0 63.3-
- 22. Unit Capacity Factor (Using DER Net) 95.0 '96.1 61.7
- 23. Unit Forced Outage Rate 0.0 0.5 16.1
- 24. Shutdowns Scheduled Over Next 6 Months (Type. Date.and Duration of Each):
[ Refueling - October 5, 1984 - 7 Weeks
... 25. If Shut Down At End Of Report Period. Estimated Date of Startup:
.6. Units in Test Status t Prior to Commercial Operation): Forecast Achieved i
- INITIAL CRITICALITY INITIA L ELECTRICITY COMMERCIAL OPERATION i
I h
R PDR
[
TC 284 Yi .
. . - ~ _ - .w -- - , ~ + . ,---y+-=--.-e.smne y
+3~ ,
~
~
y '. . . ,
.<- . AVERAGE-DAILY UNIT! POWER LEVEL
-DOCKET NO. '50-269
/> '
Oconee 1
^
UNIT-DATE -10/15/84
. , - 'C0KPLETED BY J. A. Reavis 3 '
TELEPHONE- 704-373-7567-s MONTH September, 1984L
- DAY..
AVERAG D LY OWER LEVEL DAY ; AVERAGE DAILY POWER LEVEL
- (MWe-Ne t) .
'1
-845 842 17' 12- 845- 842 18' 3' 844 842 39-4 843 20; 842 5 844 842 21 6 844 22 840' 7 845 842 23 8 826 24 843' 9 843 842 25 10 842- 26- 841 11 842 27 842 12 842 28 843 13 842 843 29 14 841 844 30 15 841 ---
31
- 16 842 L
i INSTRUCTIONS On this format, In the reporting month. list the average daily unit power level in MWe-Net for each day Compute to the nearest whole megawatt.
l O
,.Ie
_ - , - - ,,.y..,...~.r,,- +w.<. . . -w.-, ,.,.,..,.,,,+,..,m.- . - - - - . . , - . . , . - - - , - - - - - - - - . , - - - - , ,
k UNIT SHUTDOWNS AND POWER REDUCTIONS DOCKET NO. 50-269 UNIT NAME oconee i DATE' 10/15/84 REPORT MONTH SEPTEMBER, 1984 COMPLETED BY J.' A. Reavis_'
. . . -TELEPHONE 704-373-7567.
"s_
O c 'a enj License y Cause'& Corrective--
S7 "co v5g a e je, No. Date ~. %h a3, Event Action to
,&n,
+R o- he a tER xmo a"
- g=
= Report # mO oO Prevent Recurrence 15-p 84-09-08 S --
B --
CC VALVEX Turbano control.& stop valve novement.
PT's-16-p 84-09-22 F --
A --
HH PUMPXX Heater Drain Pump oil' System Repairs-1 2 3 4 Reason: Method:
A-Equipment Failure (Explain)' Edlibit G - Instructions SS duled 1-Manual for Preparation of Data B-Maintenance or Test 2-Manual Scram Entry Sheets for Licensee C-Refueling 3-Automatic Scram Event Report (LER)
D-Regulatory Restriction 4-Other (Explain)
E-Operator Training 4 License Examination File (NUREG-0161)
F-Administrative S G-Operational Error (Explain) Exhibit I - Same Source
- II-Other (Explain) 9/77)
a - Mr- +4 re+ 4 M L.
. 1 : 2-s,
+-
t DOCKET NO:- 269-UNIT: oconee 1 DATE: 10/15/84
' NARRATIVE SUbHARY '
- Month: September'1984 ' ,
'. The unit operated at 100% except for a Turbine Control:PT. The unit also
- repaired an oil leak on one of its Heater Drain Tank Pumps.
t 4
% 9 I
t t
I, i-
~
L f '[
p.
1
. MONTHLY REFUELING INFORMATION REQUEST Y,'
r
. El.'; Facility name: Oconee Unit-1 ,
- 2. : Scheduled next refueling shutdown: October 1984 ,
'- 3' . Scheduled restart following refueling: November 1984 ,
- 4. Will refueling or resumption of operation thereafter require a technical specification change or other license amendment? Yes .
If yes, what will these be? Technical Specification Revision If no, has reload design and core configuration been reviewed by Safety Review Committee regarding unreviewed safety questions? N/A .
- 5. Scheduled date(s) for submitting proposed licensing action and supporting
, information: N/A ,
- 6. Important licensing considerations (new or different design or supplier, unreviewed design or performance analysis methods, significant changes in design or new operating procedures).
1, j
l I
1 i
, 7. Number of fuel assemblies (a) in the core: 177 .
t
, (b) in the spent fuel pool: 1032* .
i
. 8. Present licensed fuel pool capacity: 1312 ,
i Size of requested or planned increase: .
- 9. Projected date of last refueling which can be accommodated by present licensed capacity: August 1991 .
f DUKE POWER COMPANY Date: October 15, 1984 ,
l Name of
Contact:
J. A. Reavis Phone: 704-373-7567
- Represents the combined total for Units 1 and 2.
T:
OPERATING DATA REPORT DOCKET NO. 50-270 I
DATE 10-15-84 C051PLETED BY J.A. Reavis OPERATING STATUS
- 1. Unit Name: Oconee 2 Notes
'2. Reporting Period: September 1, 1984-September 30, 198L Year-to-date and cumulative
- 3. Licensed Thermal Power 151Wt): 2569 capacity factors are calcu-
- 4. Nameplate Rating (Gross SIWE): 934 lated using a weighted
- 5. Design Electrical Rating ('Net 31We): 886- average for maximum
. 6. Siaximum Dependable Capacity (Gross 51We): 899 dependable capacity.
- 7. Slaximum Dependable Capacity (Net SIWE): 860
- 8. If Changes Occur in Capacity Ratings (Items Number 3 Through 7) Since Last Report. Give Reasons:
None i
- 9. Power Level To Which Restricted.If Any (Net 31We): None
! 10. Reasons For Restrictions. !f Any:
This 51onth Yr. to Date' Cumulative
.11. Hours in Reporting Period 720.0 6 575.0 88 200.0
- 12. Number Of Hours Reactor Was Critical 720.0 6 575.0 63 888.5
- 13. Reactor Reserve Shutdown Hours --- ---
- 14. Hours Generator On Line 720.0 6 579.0 '69 71s.2
- 15. Unit Resene Shutdown Hours ' --- --- ---
- 16. Gross Thermal Energy Generated (51WH) 1 790 166 16 773 663 149 264 330
- 17. Gross Electrical Energy Generated (SIWH) 601 320 5 758 650 50 863 506
- 18. Net Electrical Energy Generated (51WH) 573 566 5 517 761 4R 179 110
- 19. Unit Service Factor 100.0 100.0 71.1
- 20. Unit Availability Factor 100.0 100.0 71.1
- 21. Unit Capacity Factor (Using SIDC Net) 92.6 07.6 61.5
- 22. Unit Capacity Factor (Using DER Net) 89.9 94.7 61.9
- 23. Unit Forced Outage Rate 0.0 0.0 15.0
- 24. Shutdowns Scheduled Over Nest 6 51onths (Type.Date,and Duration of Each1
t Refueling - February 24, 1985 - 9 Weeks I
! i
- 25. If Shut Down At End Of Report Period. Estimated Dxe of Startup:
- 26. Units in Test Status tPrior to Commercial Operation): Forecast 1 Achiesed
{ INITIAL CRITICALITY INITIA L ELECTRICITY CONistERCIAL OPERAT10N l
i (9/77)
Y AVERAGE DAILY UNIT POWER LEVEL DOCKET NO. _ 50-270 UNIT Ocnnee 2 DATE 10/15/84 COMPLETED BY J.A. Reavis TELEPHONE __704-373-7567 MONTH September, 1984 DAY AVERAGE DAILY POWER LEVEL DAY AVERAGE DAILY POWER LEVEL (MWe-Net)
(MWe-Ne t) 1 556 823 17 2 678 18 823 3 801 823 19 4 825 20 823 5 503 21 823 6 768 22 823 7 825 824 23 8 825 24 823 9 824 823 25 10 824 26 823 11 824 27 824 12 824 28 824 13 823 823 29 14 823 825 30 15 822 ---
31 16 823 INSTRUCTIONS On this format, list the average daily unit power level in MWe-Net for each day in the reporting month. Compute to the nearest whole megawatt.
+.
UNIT SHUTDOWNS AND POWER REDUCTIONS DOCKET NO. 50-270 UNIT NAME oconee 2 DATE 10/15/84 REPORT MONTH September 1984 COMPLETED BY J. A. Reavis TELEPHONE - 704-373-7567 "s_
o e t en$ License y Cause & Corrective-S7 "c u ." # a e No. Date ~. %h he g jgc Event 5e y, g Action to H
R o~ a a:
tER xmo gE g=
Report # mu oO Prevent Recurrence 13-p 84-09-01 F -
A --
CH PUMPXX Main Feedwater Pump Repairs 14-p 84-09-01 S -
F --
ZZ ZZZZZZ Economic Dispatch Reduction 15-p 84-09-05 F --
A --
IHI PIPEXX Repair Heater Bleed Line u- _ ,
1 2 -
3 4 Reason: Method:
A-Equipnent Failure (Explain) Exhibit G - Instructions S Sc uled 1-Manual for Preparation of Data B-Maintenance or Test 2-Manual Scram Entry Sheets for Licensee C-Refueling 3-Autanatic Scram Event Report (LER) .
D-Regulatory Restriction 4-Other (Explain)
E-Operator Training 4 License Examination File' (NUREG-0161)
F-Administrative 5 G-Operational Error (Explain) Exhibit I'- Same Source li-Other (Explain)
- )/771
r , :- - ,
dOCKETNO: 270 UNIT: oconee 2
'DATE: 10/15/84 NARRATIVE
SUMMARY
- Month
- September, 1984 l .
' This unit ran at 100% except for a reduction to 51% power on September 1, for l feedwater pump repairs followed by Economic Dispatch at 86% and a reduction to
- j. 25% power on September 5, to repair a Heater Bleed line, t
L i
o
... ' MONTHLY REFUELING'INFORMATION REQUEST
- 1. Facil'ity name:' Oconee Unit.2 ,
3 ~2. Scheduled next refueling shutdown:
~
February, 1985 , [
p
- 3. . Scheduled restart.following refueling: April.1985 ,
4$.Willrefuelingorresumptionofoperationthereafterrequireatechnical specification change or other license amendment? Yes- .
If,yes, what will these be? Technical Specification Revision If no, has reload design and core configuration been reviewed by. Safety.
Review Committee regarding unreviewed safety questiona? N/A ,
5.
Scheduled information:date(s)/Afor N submitting proposed licensing action and supporting
- 6. Important licensing considerations (new or different design or supplier, unreviewed design or performance analysis methods, significant changes in design or new operating procedures).
l
- 7. Number of fuel assemblies (a) in the core: 177 ,
(b) in the spent fuel pools 1032* .
l l 8. .Present licensed fuel pool capacity: 1312 ,
[ Size of requested or planned increase .
- 9. Projected date of last refueling which can be accommodated by present licensed capacity: August 1991 ,
DUKE POWER COMPANY Date: October 15, 1984 ,
Name of
Contact:
J. A. Reavis Phones 704-373-7567
- Represents the combined total for Units 1 and 2.
1.
. _ - , ._ _...__ _ ._ _ _ _ .. _ _ ._ _. -.--,.--.-- -_ - - - ~
i f
OPERATING DATA REPORT
. DOCKET NO. 50-287 DATE m-15 CO31PLETED BY J.A- Reavis TELEPilONE 704-373-7567 OPERATING STATUS oconee 3 Notes
- 1. Unit Name:
- 2. Reporting Period: September 1,1984-September 30, 1982 Year-to-date and cumulative
- 3. Licensed Thermal Power p!Wt): 2568 capacity factors are calcu-
- 4. Nameplate Rating (Gross .\ lWe): 934 lated using a weighted 886 a m age for ma & um S. Design Electrical Rating (Net SIWE):
899 dependable capacity.
- 6. Staximum Dependable Capacity (Gross SIWE):
- 7. Maximum Dependable Capacity (Net 31We): 860
- 8. If Changes Occur in Capacity Ratings (Items Number 3 Through 7) Since Last Report. Give Reasons:
None
- 9. Power Level To which Restricted if Any (Net 51We):
- 10. Reasons For Restrictions.lf Any:
This .\lonth Yr..to Date Cumulative
- 11. Hours in Reporting Period 720.0 6 575.0 85 847.0
- 12. Number Of Houn Reactor Was Critical 720.0 4 625.6 61 336.5
~~ -~ ~~
- 13. Reactor Resene Shutdown Hours
- 14. Hours Generator On.Line 720.0 4 587.4 60 170.0
~~ ~~ ~~
- 15. Unit Reserve Shutdown Hours -
- 16. Gross Thermal Energy Generated (alWH) 1 848 705 11 485 108 M 6 977 672
- 17. Gross Electrical Energy Generated plWH) 631 820 3 956 390 50 770 984
- 18. Net Electrical Energy Generated ($1WH) 604 146 3 775 477 48 342 595
- 19. Unit Service Factor 100.0 69.8 70.1
- 20. Unit Availability Factor 100.0 69.8 70.1
- 21. Unit Capacity Factor (Using 31DC Net) 97.6 66.8 65.3
- 22. Unit Capacity Factor (Using DER Net) 94.7 64.8 63.6
- 23. Unit Forced Outage Rate 0.0 1.8 14.'4
- 24. Shutdowns Scheduled Oser Nest 6 Sionths(Type. Ihte.and Duration of Each1:
None
- 25. If Shut Down At End Of Report Period. Estimated Date of Startup:
- 26. Units in Test Status irrior io Commercial Operation): Forecast Achiesed INITI \L CRITICALITY INITIAL ELECTRICITY C0\l\lERCI AL OPER ATION (0/77 )
1
- _ _ . .- . _ .-.-_. . ~
, m-7.
- .7 i
- -.
- 2. AVERAGE: DAILY UNIT P'0WER' LEVEL' DOCKET NO. 50-287
' UNIT Oconee 3 DATE ' 10/15/84
' COMPLETED BY- J.A. Reavis TELEPHONE 704-373-7567 HONTH September, 1984 DAY AVERAGE DAILY POWER LEVEL DAY AV'ERAGE DAILY' POWER LEVEL (MWe-Ne t)
(MWe-Ne t) 1 842 840 17 2 843 18 839 3 842 839 19 4 840 20 839 5 840 21 840 6 841 22 840 7 841 23 840 8 840 24 839 9 840 25 839 10 838 26 839 11 839 27 839 12 840 28 840 13 839 29 841 14 838 30 841 15 817 ---
31 16 839 INSTRUCTIONS On this format, 11st the average daily unit power level in MWe-Net for each day in-the reporting month. Compute to the nearest whole megawatt.
O
m UNIT SHUTDOWNS AND POWER REDUCTIONS DOCKET NO. 50-287-UNIT NAME- oconee 3 DATE 10/15/84 REPORT PONTH September 1984 - COMPLETED BY J. A. Reavis-TELEPHONE. 704-373-7567 "s.
o e o o,$ License y Cause & Corrective No. Date ~
32 "e o3E m o o
o.
%h s- o g
.o gc Event ,Be, h Action to o s 3: . .o N 56 E $5S Report # &O bb Prevent Recurrence 13-p 84-09-15 S --
B --
CC VALVEX Control & Stop Valve Movement PT's I
1 2 3 4 Reason: Method: Exhibit G - Instructions
[ 1ed A-Equipment Failure (Explain)
B-Maintenance or Test 1-Manual .for Preparation of Data 2-Manual Scram Entry Sheets for Licensee C-Refueling 3-Automatic Scram Event Report-(LER)
D-Regulatory Restriction 4-Other (Explain)
E-Operator Training 4 License Examination File (NUREG-0161)
F-Ahinistrative 5
, G-Operational Error (Explain) Exhibit I - Same Source II-Other (Explain) nrrn
)
~
+
J
- LOCKET NO: 50-287
. UNIT: Oconee 3 . .
DATE:_10/15/84
- NARRATIVE
SUMMARY
l Month: September 1984 The ~ unit operated at 100%' except for a reduction to 85% for turbine control PT on September 15.
i l
l l
l i
I' L._
-~ . -. .-
a
, MONTHLY REFUELING INFORMATION REQUEST
- 1. Facility.name: Oconee. Unit 3 ,
- 2. Scheduled.next refueling shutdown: September,1985 .
-3. Scheduled restart following refueling: November 1985 .
- 4. !W111 refueling or resumption of operation thereafter require a technical specification change or other license amendment? Yes ,
If yes, What will these be? Technical Specification Revision Elf no, has reload design and core configuration been reviewed by Safety Review Committee regarding unreviewed safety questions? N/A .
5.
Scheduled information:date(s)/Afor N submitting proposed licensing action and supporting ,
- 6. Important licensing considerations (new or different design or supplier, unreviewed design or performance analysis methods, significant changes in design or new operating procedures).
- 7. Number of fuel assemblies (a) in the core: 177 , l (b) in the spent fual pool: 158 , ,
l
- 8. Present licensed fuel pool capacity: 825 ,
l Size of requested or planned increase: .
- 9. Projected date of last refueling which can be accommodated by present licensed capacity: August 1991 ,
DUKE POWER COMPANY Date: October 15, 1984 ,
Name of
Contact:
J. A. Reavis Phone: 704-373-7567 I
I
u'^
+ 4'
- '" " OCONEE NUCLEAR' STATION Monthly Operating Status Report-l'. ' Personnel ~ Exposure
'For the' month of August, n' individual (s) exceeded.10 percent of-their allowable annual radiation dose limit.
2.. The' total station liquid release for August has been compared with the Technical Specifications maximum annual dose commitment.and ,
was less than 10 percent of this limit.
'The total station gaseous release for August has been compared ,
with the Technical Specifications maximum annual dose commitment and was less than 10 percent of this limit.
I s
0 4
L-_
s DumE POWER GOMPANY P.O. BOX 33189 CHARLOTTE. M.C. 28949 trALn. m m October 15, 1984 """
vws ,ames===v -
.wo. ,- (704)373-453:
s Director Office of Inspection and Enforcement-U. S. Nuclear Regulatory Commission Washington,'D. C.)-20555 Attention: Document Control Desk Re: Oconee Nuclear Station Docket Nos. 50-269, -270, -287 s ,
s
Dear Sir:
i Picase find attached information concerning the performance and operating status of the Oconee Nuclear Station for the month of September, 1984.
Very truly yours.
Hal B. Tucker JAR:scs Attachments '
cc: Regional Administrator 1 American Nuclear Insurers U. S. Nuclear Regulatory Commission c/o Dottie Sherman, ANI Library Region 11 The Exchange, Suite 245 101 Marietta Street, FW,' Suite 2900 270 Farmington Avenue Atlanta, Georgia 30323 ' Farmington, Connecticut 06032 Mr. Phil Ross Ms. Helen Nicolaras, Project Manager U. S. Nuclear Regulatory Commission Office of Nuclear Reactor Regulation HNBB-5715 U. S. Nucicar Regulatory Commission Washington, D. C. 20555 Washington, D. C. 20555 Senior Resident Inspector INPO Records Center Oconee Nuclear Station Suite 1500 1100 Circle 75 Parkway
, Atlanta, Georgia 30339 Ms. Judy Dovers Nucicar Assurance Corporation
' 5720 Peachtree Parkway Norcross, Georgia 30092 p$
Y is
_.____m