Corrected Proposed Tech Spec Page 3.6-8 Re Reactor Coolant Leakage
ML20070W130
Person / Time
Site: Hatch Southern Nuclear icon.png
Issue date: 02/11/1983
From:
GEORGIA POWER CO.
To:
Shared Package
ML20070W127 List:
References
TAC-49156, NUDOCS 8302180290
Download: ML20070W130 (2)


Text

LIMIIING CONDIIIONS F0H OPEHAfION buRVdILLANCE rtEQuinti4ENfa G. _ Reactor Coolant Leakace

2. Leakace Detection Systems (Cont'd)
a. (Continued) in the reactor vessel and reactor coolant temperature is above 2120F Further, the '

primary containment atmosphere particulate radioactlyity monitoring system shall be among these t'.-d operable j"O systems, or samples shall be octained and analyzed at least once each 4 hours4.62963e-5 days <br />0.00111 hours <br />6.613757e-6 weeks <br />1.522e-6 months <br />.

D.

From and after the date that any two of the four systems identified in Table 3.2-10, note c are made or found to be inoperaale but with the primary con,tainment atmosphere particulate radioactivity / -- 8/' W y

  • monitoring system i.. w llo, reactor power operation may continue for the succeeding 30 days provided the primary containment atmosphere particulate radioactivity monitoring system reading is checked and recorded at least once each 4 hours4.62963e-5 days <br />0.00111 hours <br />6.613757e-6 weeks <br />1.522e-6 months <br />.
c. From and after the date that any two of the four systms, including the primary containment atmosphere particulate radioactivity monitoring syst s , identified in Table 3.2-10, note c are made or found to be inoperable, reactor power operation may continue for the succeeding 30 days provided samples of the containment atmosphere are obtained and analyzed at least once each 4 hours4.62963e-5 days <br />0.00111 hours <br />6.613757e-6 weeks <br />1.522e-6 months <br />.

pa82;gg2pagggg; P

Amendment No.

3. 6- 8

LIMITING CONDITIONS FOR OPERATION SURVEILLANCE REQUIREENTS G. Reactor Coolant Leakage

2. Leakage Detection Systems (Cont'd)
a. (Continued) fn the reactor vessel and reactor coolant temperature is above 2120F. Further, the primary containment atmosphere particulate radioactivity monitoring system shall be among these two operable cystems, or samples shall be obtained and analyzed at least once each 4 hours4.62963e-5 days <br />0.00111 hours <br />6.613757e-6 weeks <br />1.522e-6 months <br />.
b. From and after the date that any two of the four systems identified in Table 3.2-10, note c are made or found to be inoperable, but with the primary containment atmosphere particulate radioactivity monitoring system operable, l reactor power operation may continue for the succeeding 30 days provided the primary containment atmosphere particulate radioactivity monitoring systen reading is checked and recorded at least once each 4 hours4.62963e-5 days <br />0.00111 hours <br />6.613757e-6 weeks <br />1.522e-6 months <br />.
c. From and after the date that any two of the four systems, including the primary containment atmosphere particulate radioactivity monitoring system, identified in Table 3.2-10, note c are made or found to be inoperable, reactor power operation may continue for the succeeding 30 days provided samples of the containment atmosphere are obtained and analyzed at least once each 4 hours4.62963e-5 days <br />0.00111 hours <br />6.613757e-6 weeks <br />1.522e-6 months <br />. ,

1 l

l l

Amendment No. 3.6-8 l l