ML19269C728

From kanterella
Revision as of 19:08, 1 February 2020 by StriderTol (talk | contribs) (Created page by program invented by StriderTol)
(diff) ← Older revision | Latest revision (diff) | Newer revision → (diff)
Jump to navigation Jump to search
LER 79-008/03L-0 on 790109:during Surveillance Testing, Containment Recirculation Fan 1-1 Failed to Run.Cause Attributed to Buildup of non-conductive Film on Auxiliary Controller Contacts
ML19269C728
Person / Time
Site: Davis Besse Cleveland Electric icon.png
Issue date: 02/05/1979
From: Naylor R
TOLEDO EDISON CO.
To:
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION III)
Shared Package
ML19269C723 List:
References
LER-79-008-03L, LER-79-8-3L, NUDOCS 7902120131
Download: ML19269C728 (2)


Text

. . . .. .

(7 77)

LICENSEE EVENT REPORT l l l l (PLEASE PRINT CR TYPE ALL REQUIRED lidFORMATION) g .CcraROLstOCK:

7 o 1 8 9 l 0 l LICENSEE H l D CODE l B l S l 1 15l@l 0 l 0 l- LICENSE 14 l 0 l 0NUMBERl N l P l F l- l250 l263 lhl4 1l1l1l1l@l57 C Al T 58lg LICENSE TY PE JO CON'T l0l1l Eny L l@ 0 l 5 l 0 l- 10 l 3 l 4 l 6 l@l 0 1 l 0 l 9 l 7 l 9 lhl0 l2 l0 l5 7 9 l@

7 5 (30 61 DOCKET NUMGER 63 63 EVENT DATE 74 75 REPORT DATE 80 EVENT DESCRIPTION AND PROBAOLE CONSEQUENCES h fo l 2 ] [ On 1/9/79, during surveillance testing Containment Recirculation Fan 1-1 failed to runl o a l Attempts to reset the breaker and start the fan failed. This placed the unit in the j l o l 4 l l Action Statement of Technical Specification 3.6.4.2. This required the one inoperable l o c, Containment Recirculation System to be restored to an operable condition within 30 ]

IolcII days. There was no danger to the health and safety of the public or unit personnel. l o 7 [The standby Containment Recirculation Fan 1-2 was operational. (NP-33-79-08) g 0 8 l  !

7 8 9 80 SYSTE M CAUSE CAUSE COYP. VALVE CODE CODE SUaCODE COMPONENT COCE SUSCOCE SUSCODE o 9 lSlElh [ h d h lC K T l B l R l K lh l B lh [_Z_j h 7 8 9 to 31 12 13 18 19 20

,_ SEQUENTIAL OCCURRENCE REPORT REVISION LER RO EVENT YEAR REPORT NO. CODE TYPE N O.

@ g,La; I 719l l-l l 0 l NI 8l l/l l013l lL l l-l l01

_ 21 22 23 24 26 27 28 29 J'J 31 32 TAKE AC O O PLANT ET HOURS S 8 ITk F R! 9 S PPLIE MANUFACTURER lx l@l xi@

33 34 Lz_j@

35 l36zi@ 10 10 l0 e1 l Yl@

43 l l@ l43 Al@ l Wl ll 2 l 0l@

3/ 40 42 44 47 CAUSE DESCRIPTION AND CORRECTIVE ACTIONS h i o lThe connections, contacts and components for the controller were insnected. Although l l lij lno exact cause has been determined, the cause has been attributed to the buildup of a I i, ;7] lnon-conductive film on the auxiliary controller contacts. The contacts were cleaned. I i ,13 [ l The fan was satisfactorily tested and declared operable. The unit was removed from pi l4 ; lthe Action Statement of Technical Specification 3.6.4.2. I 7 8 9 80 ST S  % POWER oTHER STATUS ISCOV RY DISCOVERY DESCRiPT!QN i s l E j@ l 0 9l9l@l NA l l B l@l Surveillance Test ST 5065.06 l ACTIVITY CO TENT RELEASEO OF RELE ASE AMOUNT OF ACTIV!TY LOCATION oF RELE ASE i o l Z l @ lZ l@l NA l l NA l 7 8 9 10 11 44 45 80 PERSONNE L EXPOSURES f NU"HER TYPE DESCRIPTION lil711010 0 l@W@l NA

,ERSONNE t imuhS i NUVRE R DESCR6PTION@

i 7

a 8 9 101010 l@l NA 11 12 80 l

LOSS OF OR D AY AGE TO F ACallTY TYPE D E SC n1P T ION hil9l E NA J n 9 10 is0 g,<t > t t i Wil% *

' . l o l LN MJ1JNA l ll llllllll lll~

8 1 -

71 79-010  %,'r m emi7mtn Rick Navlor p..; a tao '::o_snno r. . ,. y _