ML20004E159
| ML20004E159 | |
| Person / Time | |
|---|---|
| Site: | Monticello |
| Issue date: | 06/02/1981 |
| From: | Myrabo A NORTHERN STATES POWER CO. |
| To: | |
| Shared Package | |
| ML20004E151 | List: |
| References | |
| NUDOCS 8106110270 | |
| Download: ML20004E159 (4) | |
Text
.
1 'AC -i 1381 NARRATIVE
SUMMARY
OF OPERATING EXPERIENCE DOC ET NO. 50-263____ _
DATE 6- 2-Gi_.... _
COMPLETED BY A. L. t:y r a t) o TELEPH0tE 612/295-5151 M O N T H _ _. _ _ _ __ M a y _ _ _ _ _ _ _ _ ._ _ __ _
5- 1-Si to Continuation of i?8i refueling outage (EOC-8).
5-10-81 5-i1-01 Reactor critical for BOC-9 physics testing.
5-12-81 Reactor eriticaL for BOC-9. Generatar on-tine.
5-13-81 Generator off-tine for turbine overspeed testing.
5-i3-Si Reactor scram on MSIV closure.
5-14-81 to Generator on-line. Power operation.
5-31--61 Note: Power operation defined as essentiaLiy 1 0 0 ?. oi rated power except for weekend Load drops for spec 1fied surveillance testing, 810611o S 7 0
4 JUN 4 199; OPERATING DATA REPORT DOCi(ET NO. 50-263__ ___
DATE 6- 2-81 ___
COMPLETED BY A. L. Myrabo TELEPHONE 612/295-5151 OPERATING STATUS _. .___.._______________._______
INotes i
- 1. Unit Name ________________________MonticeLto l l
- 2. Reporting period: ___________________MAY I 1
- 3. Licensed Thermal Power (MWt) ____________1670 l l
- 4. Nameplate Rating (Gross MWe) _____________569 i i
- 5. Design Electrical Rating (Net MWe)' _____545.4 I i
- 6. Maximum Dependable Capacity (Gross hWe): __564 I I
- 7. Maximum Dependabte Capacity (Net MWe) ____536 l______..__________._.._____.l
- 8. If Changes Occur in Capacity Ratings (Items Nunece r 3 Through 7) Since Last Report, Give Reasons: __N/A_____________________,____________________-___
- 9. Power Level To Which Restricted, If Any (Net hWe): ..__N/A____________..______
- 10. Reasons For Restrictions, If Any: __N/A_____________________________ _____'__
This Month Yr.-to-Date Cumu la t i ve
- 11. Hours In Reporting Period _____744 _____3623 ___. 86952
- 12. Number Of Hours Reactor Was Critical ___468.8 ___2972.4 __ 71491.4
- 13. Reactor Reserve Shutdown Hours _____0.0 ______0.0 ___.._940.7
- 14. Hours Generator On-Line ___444.1 ___2927.5 __ 69774.6
- 15. Unit Reserve Shutdown Hours _____0.0 ______O.0 _______0.0
- 16. Gross Thermal Energy Generated (MWH) _ 697478 . 4418819 _114Q42339
- 17. Gross Electrical Energy Generated (MWH) __235565 __1499425 __36094616
- 18. Net Electrical Energy Generated (MWH) __225055 __i438355 __34524358
- 19. Unit Service Factor __ 59.7% ___. 80.8% ____ 80.2%
- 20. Unit Availability Factor -_ 59.7% ___ 80.8% _..__ 80.2%
- 21. Unit Capacity Factor (Using MDC Net) __ 56.4% ___ 74.1% ____ 74.1%
- 22. Unit Capacity Factor (Using DER Net) __ 55.5% .__ 72.8% ____ 72.8%
- 23. Unit Forced Outage Rate __ 3.1% ___ 2.9% ____ 6.4%
- 24. Shutdowns Scheduled Over Next 12 Months (Type, Date, and Duration of Each)
__0ctober 12, 1981 - Maintenance Outage - 42 days ___________________..___
- 25. If Shut Down At End Of Report Period, Estimated Date Of Startup:__N/A_____ _
- 26. Units In Test Status (Prior to Commercial Operation) N/A Forecast Achieved INITIAL CRITICALITY INITIAL ELECTRICITY ________ ________
COMMERCIAL OPERATION _ _ _ _ _ _ _ _ _ _ _ . . _ _ _
_ P00R ORIGINAL
O AVERAGE DAILY UNIT POWER LEVEL DOCKET NO. 50-263__ ___
UNIT MonticeLlo__
DATE 6- 2-81____
COMPLETED BY A. L. Myrabo TELEPHONE 612/295-5151 MONTH ______MAY _______
DAY AVERAGE DAILY POWER LEVEL DAY AVERAGE DAILY POWER LEVEL (MWe-Net) (MWe-Net) i __________ -2____________ 17 __________545___.______ .._
9
- __________ -4____________ 18 ._____ _-.542 _ __..______
3 __________ -3____________ 19 __________540___ ________
4 __________ -4____________ 20 __________544____________
5 __________ -2____________ 21 ______..___540_____________
6 __________ -4____________ 22 __________540__________,._
7 __________ -4____________ 23 ______..___542____________
0 __________ -3____________ 24 __________475_______.____
9 __________ -4____________ 25 __________541____________
i s
t
. 10 __________ -4____________ 26 __________542___..________
)
11 __________ -6____________ 27 __________540____________ ,
12 __________ 4____________ 28 __________542 ________ __
13 __________101____________ 29 __________542____________
I 14 __________961__________-_
- 30 ---_-_---_ 543___-_-_-.-_-
t 1
- 15 __________444____________ 31 __..____.___535__.._______._
l 16 __________532____________
1 l
! INSTRUCTIONS l
l l
On this format, list the average dail/ unit power level in MWe-Net for each P00R ORIGINAL
~.,
UNIT SilU1 DOWNS \ND POWER REbuCTIONS DOCKET NO. 50-263 UNIT NASIE hionticello DATE 6-7-R1 R EPORT .\lON ill bl3V CO%1PLETED BY A. L. htvrabo IELEPalONE 612/261-5808
-, {? 3 j YE Licensee 5-t,, ['1, Cause & Correcene No. Dare i 3g 4 2s5 Esent gg Aoion to H
AE $ jij Report : mO j~
E- 3 Psesent Recurrence 6
9 5-01-8; S 284.4 C 2 N/A ZZ ZZZZZZ Continuation of 1981 refueling outage (EOC-8).
10 5 - 1. 81 S 1.2 B 1 N/A IIA RIRBIN Generator off-line for turbine overspeed test.
11 5-13-81 F 14.2 G 3 N/A CC bECIUN Mistaken use of reactor pressure controls resulted in reactor ' scram on MSIV closure.
/
l 2 3 4 F: Forced Reason : hiethod: Edubis G -Instructions S: Scheduled A Equipinent Failure (E.splain) 1 klanual for Preparation of Data B41aintenance of Test 2-hlanual Scrain. Entr> Sheets for Licensee .
C Refueling 3 Automatic Scram. Esent Repost (LER) File int' REG-l) Regulatory Restriction 4 Other (Explain) 01611 E-Operator Training & license Exannnation F-Administ rati.e 5 G-Operational Error ( E xplain) Ex!nbit 1 Same Source 19/77) 11 Other (E xplain)
_ _ _ _ _ _ - _ _ _ _ _ - _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _