ML18054B398

From kanterella
Revision as of 11:39, 3 February 2020 by StriderTol (talk | contribs) (Created page by program invented by StriderTol)
(diff) ← Older revision | Latest revision (diff) | Newer revision → (diff)
Jump to navigation Jump to search
Responds to NRC Bulletin 89-002, Stress Corrosion Cracking of High-Hardness Type 410 Stainless Steel Internal Preloaded Bolting. No Anchor Darling Model S350W Swing Check Valves Used at Facility.Actions Considered Complete
ML18054B398
Person / Time
Site: Palisades Entergy icon.png
Issue date: 01/17/1990
From: Berry K
CONSUMERS ENERGY CO. (FORMERLY CONSUMERS POWER CO.)
To:
NRC OFFICE OF INFORMATION RESOURCES MANAGEMENT (IRM)
References
IEB-89-002, IEB-89-2, NUDOCS 9001260078
Download: ML18054B398 (2)


Text

  • consumers Power Kenneth W Berry Director l'OWERINli Nuclear licensing MICHlliAN'S l'ROliRESS General Offices: 1945 West ParnalL Road, Jackson. Ml 49201 * (517) 788-1636 January 17, 1990 Nuc_lear Regulatory Commission Document Control Desk Washington, DC 20555 DOCKET 50-255 - LICENSE DPR PALISADES PLANT - RESPONSE TO NRC BULLETIN 89 STRESS CDRROSION CRACKING OF HIGH-HARDNESS TYPE 410 STAINLESS STEEL INTERNAL PRELOADED BOLTING NRC Bulletin 89-02, Stress Corrosion Cracking of High-Hardness Type 410 Stainless Steel Internal Preloaded Bolting in Anchor Darling Model S350W Swing Check Valves or Valves of Similar Design, dated July 19, 1989, required Consumers Power to determine if Anchor Darling Model S350W swing check valves or check valves of similar design are used *at Palisades. If check valves of the types of concern are used, an inspection and testing program is to be initiated.

Palisades has completed the requested review. No Anchor Darling Model S350W swing check valves are used at Palisades. Palisades does use swing check valves of similar design; however, none of the similar valves use ASTM A 193 Grade B6 type 410 stainless steel for internally preloaded bolting applica-tions. Palisades does have a Check Valve Preventive Maintenance Program which requires an inspection of internal bolting when applicable. Palisades actions in response to this Bulletin are considered complete.

Kenneth W Berry Director, Nuclear Licensing CC Administrator, Region III, USNRC NRC Resident Inspector - Palisades 9001260078 900117 PDR ADOCK 05000255 Q PDC OC0190-0001-NL03

\

CONSUMERS POWER COMPANY Palisades Plant Docket 50-255 - License DPR-20 RESPONSE TO NRC BULLETIN 89-02 At the request of the Commission and pursuant to the Atomic Energy Act of 1954 and the Energy Reorganization Act of 1974, as amended, and the Commission's Rules and Regulations thereunder, Consumers Power Company submits our response to NRC Bulletin 89-02 dated July 19, 1989, entitled, "Stress Corrosion Cracking of High-Hardness Type 410 Stainless Steel Internal Preloaded Bolting in Anchor Darling Model S350W Swing Check Valves or Valves of Similar Design." Consumers Power Company's response is dated January 17, 1990.

CONSUMERS POWER COMPANY To the best of my knowledge, information and belief, the contents of this submittal are truthful and complete.

Sworn and subscribed to before me this 17th day of January, 1990.

~ . c ./' .

,~e) .[; ~;_~J Elaine E Buehrer, Notary Public Jackson County, Michigan My cormnission expires October 11, 1993 OC0190-0001-NL03