| event date = 10/06/2003 22:15 CDT
| event date = 10/06/2003 22:15 CDT
| last update date = 10/07/2003
| last update date = 10/07/2003
| title = Hpci System Inoperability Due To Failed Suppression Pool Level Switch At Dresden Unit 2
| title = Hpci System Inoperability Due to Failed Suppression Pool Level Switch at Dresden Unit 2
| event text = The Unit 2 HPCI system has been declared INOPERABLE due to the failure of a pressure suppression pool high-level switch during surveillance and being unable to maintain the HPCI pump suction lined up to the pressure suppression pool in standby lineup.
| event text = The Unit 2 HPCI system has been declared INOPERABLE due to the failure of a pressure suppression pool high-level switch during surveillance and being unable to maintain the HPCI pump suction lined up to the pressure suppression pool in standby lineup.
Per technical specification 3.3.5.1. required action D.2.2. with the high level switch INOPERABLE the HPCI system must have the pump suction aligned to the suppression pool with in 24 hours or declare the HPCI system INOPERABLE when the required action completion time can not be met. The function of the suppression pool high-level switch causes the HPCI pump suction to automatically realign to the suppression pool when the suppression pool reaches the high level set point during an accident.
Per technical specification 3.3.5.1. required action D.2.2. with the high level switch INOPERABLE the HPCI system must have the pump suction aligned to the suppression pool with in 24 hours or declare the HPCI system INOPERABLE when the required action completion time can not be met. The function of the suppression pool high-level switch causes the HPCI pump suction to automatically realign to the suppression pool when the suppression pool reaches the high level set point during an accident.

Latest revision as of 21:25, 1 March 2018

ENS 40227 +/-
Where
Dresden Constellation icon.png
Illinois (NRC Region 3)
Reporting
10 CFR 50.72(b)(3)(v)(D), Loss of Safety Function - Mitigate the Consequences of an Accident
Time - Person (Reporting Time:+3.08 h0.128 days <br />0.0183 weeks <br />0.00422 months <br />)
Opened: Glen Morrow
06:20 Oct 7, 2003
NRC Officer: Rich Laura