Line 16: Line 16:
| event date = 03/11/2004 14:30 CST
| event date = 03/11/2004 14:30 CST
| last update date = 03/11/2004
| last update date = 03/11/2004
| title = Voluntary Report Involving Potential Tsc Unavailability During A Dba Loca
| title = Voluntary Report Involving Potential Tsc Unavailability During a Dba Loca
| event text = Monticello Nuclear Generating plant is making a voluntary report with regard to the Technical Support Center (TSC) not meeting design criteria Subsection 8.2-1.f of Supplement 1 to NUREG-0737. This specifies that the TSC will be provided with radiological protection necessary to assure that the radiation exposure to any person working in the TSC would not exceed 5 REM whole body (or its equivalent part of the body) for the duration of the accident.  
| event text = Monticello Nuclear Generating plant is making a voluntary report with regard to the Technical Support Center (TSC) not meeting design criteria Subsection 8.2-1.f of Supplement 1 to NUREG-0737. This specifies that the TSC will be provided with radiological protection necessary to assure that the radiation exposure to any person working in the TSC would not exceed 5 REM whole body (or its equivalent part of the body) for the duration of the accident.  
During review of the calculations associated with an on-going Alternative Source Term project, plant staff identified the potential for a radiation shine path to exist from the reactor building to the TSC during a DBA [Design Basis Accident] - Loss of Coolant Accident [LOCA], that could result in radiation levels reaching a point dictating evacuation of the TSC under existing emergency plan procedures.
During review of the calculations associated with an on-going Alternative Source Term project, plant staff identified the potential for a radiation shine path to exist from the reactor building to the TSC during a DBA [Design Basis Accident] - Loss of Coolant Accident [LOCA], that could result in radiation levels reaching a point dictating evacuation of the TSC under existing emergency plan procedures.

Latest revision as of 21:24, 1 March 2018

ENS 40585 +/-
Where
Monticello Xcel Energy icon.png
Minnesota (NRC Region 3)
Reporting
Other Unspec Reqmnt
Time - Person (Reporting Time:+0.87 h0.0363 days <br />0.00518 weeks <br />0.00119 months <br />)
Opened: Dale Johnson
21:22 Mar 11, 2004
NRC Officer: Steve Sandin
Last Updated: Mar 11, 2004
40585 - NRC Website
Loading map...