ENS 50015: Difference between revisions

From kanterella
Jump to navigation Jump to search
(Created page by program invented by Mark Hawes)
 
(Created page by program invented by StriderTol)
 
Line 16: Line 16:
| event date = 04/09/2014 CDT
| event date = 04/09/2014 CDT
| last update date = 05/09/2014
| last update date = 05/09/2014
| title = Part 21 - Potential Defect In General Electric Type Cr120Ad Control Relays
| title = Part 21 - Potential Defect in General Electric Type Cr120Ad Control Relays
| event text = The following information was received via fax:
| event text = The following information was received via fax:
This letter is being issued by QualTech NP, Huntsville, AL, to provide an initial notification to the Nuclear Regulatory Commission and Nebraska Public Power District [NPPD] Cooper Nuclear Station concerning a potential defect in General Electric Type CR120AD control relays. A failure analysis revealed that the most likely initiator of the failure was a flaw or defect in the start wrap of the magnet wire. The flaw created an arc that involved windings directly beneath the start wrap which resulted in an open circuit on the coil windings. This failure is classified as infant mortality, which is similar to the failure mode identified in the 10 CFR part 21 30 day report (accession number  9706190261) dated June 12, 1997 submitted by GPU Nuclear.
This letter is being issued by QualTech NP, Huntsville, AL, to provide an initial notification to the Nuclear Regulatory Commission and Nebraska Public Power District [NPPD] Cooper Nuclear Station concerning a potential defect in General Electric Type CR120AD control relays. A failure analysis revealed that the most likely initiator of the failure was a flaw or defect in the start wrap of the magnet wire. The flaw created an arc that involved windings directly beneath the start wrap which resulted in an open circuit on the coil windings. This failure is classified as infant mortality, which is similar to the failure mode identified in the 10 CFR part 21 30 day report (accession number  9706190261) dated June 12, 1997 submitted by GPU Nuclear.

Latest revision as of 21:50, 1 March 2018

ENS 50015 +/-
Where
Qualtech Np
Huntsville, Alabama (NRC Region 1)
Organization: Qualtech Np
Reporting
10 CFR 21.21(d)(3)(i), Failure to Comply or Defect
Time - Person (Reporting Time:+10.35 h0.431 days <br />0.0616 weeks <br />0.0142 months <br />)
Opened: Matthew Thelen
15:21 Apr 9, 2014
NRC Officer: Steve Sandin
Last Updated: May 9, 2014
50015 - NRC Website