ML20023B554: Difference between revisions

From kanterella
Jump to navigation Jump to search
(StriderTol Bot insert)
 
(StriderTol Bot change)
 
Line 17: Line 17:


=Text=
=Text=
{{#Wiki_filter:}}
{{#Wiki_filter:..                                                          .
NRC FORM 386                                                                                                                                                                                                U. S. NUCLEAR CE!ULATORY 'mana**manen
* 77',          ',.                                                                                                                                                                                        Attachment to AECM-83/0261 LICENSEE EVEDT REPORT Page 1 of 2 CONTROL BLOCK: l                                  l    l  l        l      l      h                                          IPLEAgE pensT OR TYPE ALL REOUIRED INFORMATIO8N lo li_I 7      8 9 l e4 LICENSEE S i alCODE        s i d i14l@l15 o l ol -1 olLICENst                            o l olNuadel            o M ol- 1 ol o3i @IS41Lactam                                          ,          1111Tvyt    11@l al      I t - S7CATSB@
l CON'T o i 7        e          0 0 @aoI ol 51 o1                      si                    olo ooCasi            l 411161@l esummen                    as                    a ol 3sveier                        l 2191  emiu sl 31@lol  74    15      4121oATEel e l8e31@
mePanT EVENT DESCRIPTION AND PROSABLE CONSE0ptseCES h o 2 [On March 29. 1983. while in Cold Shutdown. a Load Sheddino and                                                                                                                                                                                          I o 3 l Sequencing (LSS) panel failure alarm actuated.                                                                                                                                                    The Division I LSS                                  1 o 4          l system, the Division I Diesel Generator, LPCI A and LPCS were                                                                                                                                                                                1 o s l subsequently declared inoperable.                                                                                                      The Division II Diesel Generator was 1 o s lavailable.                                          LPCI C was the only operable ECCS system, therefore, an                                                                                                                                            1 o 7 [LCO was entered pursuant to T.S.3.5.2.                                                                                                                                      This event is reported                                                    j o 8 l pursuant to T.S.6.9.1.13.b.                                                                                                                                                                                                                          1 7      8 9                                                                                                                                                                                                                                                  8D oOE              SveCOBE                                    COMPONENT CODE                                                      S      DE o 9
            .                          l ElB l@nW@ @@ l i3IlN I SlT l R[U Q lF@
                                      .                      is                                  in                                                                                              i.
Pl            Z@
EVENT vf AR                                                            O                                                                                  DE                T p'
LER RO                                                                                                                                                                                                                  neO
                  @ ,agg le1 31                                              L--J                  l o l6 I o f                                    M                                        i ol31    _                          M            po
                                    ,, 21                        22          23                  24                26                              27                                      28      2                          3 K N        C                                      LA T      ME                                Hours 22                                                S8 i                      FOmed US.                            lutAN        pe,a lA 33_.
J@LZJ@  34 LZ 35 _ J@
L2JO 38 I
37 I              I                I 40 I                t'._J@
41 LN jg          {Ajg_          lX en l 9l9 l 9)g 42              43                                47 CAUSE DESCRIPTION ANDCORRECTIVE ACTIONS h
[ go-] lThe cause was f ound to be f ailure of the 15V DC power supply used to                                                                                                                                                                                j i i          [ power the solid state electronics for system logic and timing functions.j
      , ,          gThe LSS cabinet is supplied by Automation Industries, Vitro Laboratoriesj
      , 3        l Division.                            The power supply is manufactured by CEA, part no. CEA3B150Y                                                                                                                                              j i 4        glo3FLP3.                        The power supply was replaced on April 9, 1983.                                                                                                                                                                l 7      8 9                                                                                                                                                                                                                                                  #
l                sTAN              % Poguem                                      oTHER STATUS                                              o fW                                                              DesclW GIW 9000mIPTeeII l I i I s I L' J@ l' l' l' l@l "                                                                                    I                l.a J@l ' ''''' ''"'*"
l l            AC TIVI TV C TENT LoCATeenermELtAsE@
i 6        (_j RetpSE@D                    or RyEAsEQlE                      Amount                    or ACTiv>Tv.@                                    @                                        I                                                              l 7      9 9                    10                  ft                                                      44                                        4                                                                                                      E PERSONNEL EMPosunE5
      , ,        i e ~g''i . gT"'"'"
j                j PERSONNF L INJ                IES 3
      , y        l 0 '[I*'gl jgl                                                                                                                                                                                                                                l r      ee                      n            i2                                                                          8305050178 830428                                                                                                                  "
LOSS OF OR DAMAGE TO FActLITv 43                                                                          PDR ADOCK 05o00416 l    i 9        T }"      y "'"'m                                                                                        S                                                                            PDR                                                    j k
7      8 9              to                                                                                                                                                                                                                                80 PUB L ICITY                                                                                                                                                                                                      98AC UE ONLY CU9 [U@I" 7      ' 1              10 1
M 66 11111'lillill:
80 3 NAME OF PREPARER                                          on h d                                                                                                                PHONE:
                                        . . . , _ . . . . _ _ . _ _ _ . -            _ ___ ..                . _ , , , , . . . _ , , _ . . _ . . - _ _ _ _ _ _ _ _ . , . ~ . . _ _ _ _ . . .                                                          _    ._      _ __
 
      ' '. ' 4*'  -
Attachmsnt to AECM-83/0261 Page 2 of 2 SUPPLEMENTARY INFORMATION TO LER 83-060/03 L-0 Mississippi Power & Light Company.
Grand Gulf Nuclear Station - Unit 1 Docket No. 50-416 Technical Specification involvtd: 3.5.2
                    -Reported Under Technical Specification: 6.9.1.13.b                              ,
Event Narrative:
On March 29, 1983, while in Cold Shutdown, a Division I Load Shedding and Sequencing panel failure alarm actuated. Upon investigation'it was determined that power was available.to the panel, however, some indicating lights were off. A subsequent maintenance investigation found the internal 15V DC power supply failed. The power supply powers solid state circuits for system logic and timing functions. The power supply was replaced and LSS Division I was restored on April 9, 1983.
During the event, an LCO was entered under T.S.3.5.2 due to LPCI C being the only operable ECCS system. Division I (D/G 11, LPCI A, and LPCS) was declared inoperable due to inoperability of LSS Division I. HPCS was inoperable due to maintenance being performed on the HPCS and D/G 13 systems. LPCI B was inoperable due to the SSW B system being down for maintenance. This is submitted as a final report.
I i
_ .      , , .            - - . . _  __.  ,    _ , ~ . . .                            ~__ _--            .m    ., , . ,-    , - _ , - _}}

Latest revision as of 00:37, 21 February 2020

LER 83-060/03L-0:on 830329,during Cold Shutdown,Load Shedding & Div I LSS Sequencing Panel Failure Alarm Actuated.Caused by Failure of 15-volt Dc Power Supply Used to Power Solid State Electronics for Sys Logic
ML20023B554
Person / Time
Site: Grand Gulf Entergy icon.png
Issue date: 04/28/1983
From: Byrd R
MISSISSIPPI POWER & LIGHT CO.
To:
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION II)
Shared Package
ML20023B542 List:
References
LER-83-060-03L, LER-83-60-3L, NUDOCS 8305050178
Download: ML20023B554 (2)


Text

.. .

NRC FORM 386 U. S. NUCLEAR CE!ULATORY 'mana**manen

  • 77', ',. Attachment to AECM-83/0261 LICENSEE EVEDT REPORT Page 1 of 2 CONTROL BLOCK: l l l l l l h IPLEAgE pensT OR TYPE ALL REOUIRED INFORMATIO8N lo li_I 7 8 9 l e4 LICENSEE S i alCODE s i d i14l@l15 o l ol -1 olLICENst o l olNuadel o M ol- 1 ol o3i @IS41Lactam , 1111Tvyt 11@l al I t - S7CATSB@

l CON'T o i 7 e 0 0 @aoI ol 51 o1 si olo ooCasi l 411161@l esummen as a ol 3sveier l 2191 emiu sl 31@lol 74 15 4121oATEel e l8e31@

mePanT EVENT DESCRIPTION AND PROSABLE CONSE0ptseCES h o 2 [On March 29. 1983. while in Cold Shutdown. a Load Sheddino and I o 3 l Sequencing (LSS) panel failure alarm actuated. The Division I LSS 1 o 4 l system, the Division I Diesel Generator, LPCI A and LPCS were 1 o s l subsequently declared inoperable. The Division II Diesel Generator was 1 o s lavailable. LPCI C was the only operable ECCS system, therefore, an 1 o 7 [LCO was entered pursuant to T.S.3.5.2. This event is reported j o 8 l pursuant to T.S.6.9.1.13.b. 1 7 8 9 8D oOE SveCOBE COMPONENT CODE S DE o 9

. l ElB l@nW@ @@ l i3IlN I SlT l R[U Q lF@

. is in i.

Pl Z@

EVENT vf AR O DE T p'

LER RO neO

@ ,agg le1 31 L--J l o l6 I o f M i ol31 _ M po

,, 21 22 23 24 26 27 28 2 3 K N C LA T ME Hours 22 S8 i FOmed US. lutAN pe,a lA 33_.

J@LZJ@ 34 LZ 35 _ J@

L2JO 38 I

37 I I I 40 I t'._J@

41 LN jg {Ajg_ lX en l 9l9 l 9)g 42 43 47 CAUSE DESCRIPTION ANDCORRECTIVE ACTIONS h

[ go-] lThe cause was f ound to be f ailure of the 15V DC power supply used to j i i [ power the solid state electronics for system logic and timing functions.j

, , gThe LSS cabinet is supplied by Automation Industries, Vitro Laboratoriesj

, 3 l Division. The power supply is manufactured by CEA, part no. CEA3B150Y j i 4 glo3FLP3. The power supply was replaced on April 9, 1983. l 7 8 9 #

l sTAN  % Poguem oTHER STATUS o fW DesclW GIW 9000mIPTeeII l I i I s I L' J@ l' l' l' l@l " I l.a J@l ' "'*"

l l AC TIVI TV C TENT LoCATeenermELtAsE@

i 6 (_j RetpSE@D or RyEAsEQlE Amount or ACTiv>Tv.@ @ I l 7 9 9 10 ft 44 4 E PERSONNEL EMPosunE5

, , i e ~gi . gT"'"'"

j j PERSONNF L INJ IES 3

, y l 0 '[I*'gl jgl l r ee n i2 8305050178 830428 "

LOSS OF OR DAMAGE TO FActLITv 43 PDR ADOCK 05o00416 l i 9 T }" y "'"'m S PDR j k

7 8 9 to 80 PUB L ICITY 98AC UE ONLY CU9 [U@I" 7 ' 1 10 1

M 66 11111'lillill:

80 3 NAME OF PREPARER on h d PHONE:

. . . , _ . . . . _ _ . _ _ _ . - _ ___ .. . _ , , , , . . . _ , , _ . . _ . . - _ _ _ _ _ _ _ _ . , . ~ . . _ _ _ _ . . . _ ._ _ __

' '. ' 4*' -

Attachmsnt to AECM-83/0261 Page 2 of 2 SUPPLEMENTARY INFORMATION TO LER 83-060/03 L-0 Mississippi Power & Light Company.

Grand Gulf Nuclear Station - Unit 1 Docket No. 50-416 Technical Specification involvtd: 3.5.2

-Reported Under Technical Specification: 6.9.1.13.b ,

Event Narrative:

On March 29, 1983, while in Cold Shutdown, a Division I Load Shedding and Sequencing panel failure alarm actuated. Upon investigation'it was determined that power was available.to the panel, however, some indicating lights were off. A subsequent maintenance investigation found the internal 15V DC power supply failed. The power supply powers solid state circuits for system logic and timing functions. The power supply was replaced and LSS Division I was restored on April 9, 1983.

During the event, an LCO was entered under T.S.3.5.2 due to LPCI C being the only operable ECCS system. Division I (D/G 11, LPCI A, and LPCS) was declared inoperable due to inoperability of LSS Division I. HPCS was inoperable due to maintenance being performed on the HPCS and D/G 13 systems. LPCI B was inoperable due to the SSW B system being down for maintenance. This is submitted as a final report.

I i

_ . , , . - - . . _ __. , _ , ~ . . . ~__ _-- .m ., , . ,- , - _ , - _