ML18033B301: Difference between revisions

From kanterella
Jump to navigation Jump to search
(Created page by program invented by StriderTol)
(Created page by program invented by StriderTol)
 
(One intermediate revision by the same user not shown)
Line 17: Line 17:


=Text=
=Text=
{{#Wiki_filter:Enclosure Revisions To TVA BFN TS 277 Browns Ferry Nuclear Plant Units l, 2, and 3 9005170261 900514 PDR ADOCK 05000259 P PDC UNIT 1 EFFECTIVE PAGE LIST REMOVE INSERT 3.9/4.9-1 3.9/4.9-2 3.9/4.9-3 3.9/4.9-4 3.9/4.9-21 3.9/4.9-22 3.9/4.9-1 3.9/4.9-2*
{{#Wiki_filter:Enclosure Revisions To TVA BFN TS 277 Browns Ferry Nuclear Plant Units l, 2, and 3 9005170261 900514 PDR ADOCK 05000259 P             PDC
3.9/4.9-3*
 
3.9/4.9 4+3.9/4.9-21 3.9/4.9.-22*
UNIT 1 EFFECTIVE PAGE LIST REMOVE                         INSERT 3.9/4.9-1                     3.9/4.9-1 3.9/4.9-2                      3.9/4.9-2*
3.9/4.9-3                      3.9/4.9-3*
3.9/4.9-4                      3.9/4.9 4+
3.9/4.9-21                    3.9/4.9-21 3.9/4.9-22                    3.9/4.9.-22*
*Denotes overleaf or spillover page.
*Denotes overleaf or spillover page.
3.4.AUXILIARY ELEC RICAL SYSTEM LIMITING CONDITIONS FOR OPERATION SURVEILLANCE REQUIREMENTS 3.9 Auxil a ectrica S ste 4.9 Aux a Electrical S stem licab Applies to all the auxiliary electrical power system.e Applies to the periodic testing requirements of the auxiliary electrical system.Ob ective To assure an adequate supply of electrical power for operation of those systems required for safety.~Ob ective Verify the.operability of the auxiliary electrical system.S ecification S ecification A.Auxi ia Electrical E ui ment A.Auxilia Electrical S stem 1.PRIOR TO STARTUP from a COLD CONDITION, the follow-ing must be satisfied:
: 3. 4. AUXILIARYELEC RICAL SYSTEM LIMITING CONDITIONS       FOR OPERATION               SURVEILLANCE REQUIREMENTS 3.9   Auxil   a       ectrica   S   ste             4.9   Aux     a   Electrical   S stem licab Applies to     all the auxiliary                   Applies to the periodic electrical     power system.                         testing requirements of the e
a.Diesel generators A, B, C, and D OPERABLE.b.Requirements 3.9.A.3 through 3.9.A.6 are met.c.At least two of the following offsite power sources are available:
auxiliary electrical       system.
(1)The 500-kV.system is available to the units 1 and 2 shut-down boards through the unit 1 station-service transformer TUSS/1B with no credit taken for the two 500-kV Trinity lines.If the unit 2 station-service transformer is the second choice, a minimum of two 500-kV lines.must be available.
Ob  ective                                            ~Ob ective To assure     an adequate supply of                 Verify the .operability of the electrical power for operation of                     auxiliary electrical system.
'.Diesel Generators a.Each diesel generator shall be manually started and loaded to demonstrate operational readiness in accordance with the frequency specified in Table 4.9.A on a staggered test basis.The test shall continue for at least a one-hour period at 100%or greater of the con-tinuous rating of the diesel generator, and the operation of the diesel fuel oil trans-fer pumps shall be demonstrated.
those systems required for safety.
Also, the diesel generator starting air compressor shall be checked for operation and its ability to recharge air receivers.
S ecification                                       S   ecification A. Auxi ia       Electrical     E ui ment         A. Auxilia     Electrical     S stem
Once per 18 months, each diesel generator will be tested at a load of at least 2800 KW to demonstrate full load carrying capability for'FN Unit 1"3.9/4.9-1 4 AUXILIARY ELECTRICAL S STE LIMITING CONDITIONS FOR OPERATION SURVEILLANCE REQUIREMENTS 3.9.A.uxilia Electrical E ui ment 4.9.A.Auxilia Electrical S ste 3.9.A.l.c.(Cont'd)(2)The 500-kV system is available to the units 1 and 2 shutdown boards through the unit 2 station-service transformer TUSS 2B with no credit taken for the two 500-kV Trinity lines.If the unit 1 station-service transformer is the second choice, a minimum of two 500-kV lines must be available.
: 1. PRIOR TO STARTUP from a                             Diesel Generators COLD CONDITION, the follow-ing must be satisfied:                               a. Each  diesel generator shall be manually
4.9.A.l.a.(Cont'd)an interval of not less than 24 hours.The diesel generator.fast starts (10 seconds)from standby conditions shall be performed once per 184 days in these surveillance tests.All other engine starts for the purpose of this test may be preceeded by an engine idle start.(3)The Trinity 161-kV line is available to the units'and 2 shutdown boards through both common station-service transformers.
: a. Diesel generators A,                                 started and loaded to B, C, and                                           demonstrate operational D OPERABLE.
Additional reporting requirements due to failures are noted in Table 4.9.A.All diesel generator starts shall be logged.Notes for (3): (a)If unit 3 is claiming the Trinity line as an offsite source, see unit'3 technical specifications, Section 3.9.A.l.c.2.(b)If unit 1 is in cold shutdown, only one common station-service transformer is required.b.Once per operating cycle, a test will be conducted simulating a loss of offsite power and similar conditions that would-exist with the presence of an actual safety-injection signal to demonstrate the following:
readiness in accordance
(1)Deenergization o f the emergency buses and load shedding from the emergency buses.(2)The diesel starts from ambient condition on the auto-start signal, energizes the emergency buses with permanently connected loads, energizes the auto-connected emer-gency loads through BFN.Unit 1 3.9/4.9-2
: b. Requirements     3.9.A.3                           with the frequency through 3.9.A.6 are                                 specified in Table 4.9.A met.                                                on a staggered test basis. The   test shall
: c. At least two of the                                  continue for at least a following offsite power                              one-hour period at 100%
sources are available:                              or greater of the con-tinuous rating of the (1) The 500-kV.system                                diesel generator, and is available to the                            the operation of the units 1 and 2 shut-                            diesel fuel oil trans-down boards through                            fer pumps shall be the unit 1 station-                            demonstrated.       Also, service transformer                            the diesel generator TUSS/1B    with no                              starting air compressor credit taken for                              shall be checked for the two 500-kV                                operation and its Trinity lines. If                              ability to recharge the unit 2 station-                            air receivers.
service transformer is the second                                  Once   per 18 months, choice,    a minimum                          each   diesel generator of two 500-kV lines.                          will be tested at a load must be available.                              of at least 2800 KW to demonstrate     full load carrying capability for
                                                                                                        'FN "3.9/4.9-1 Unit  1
 
4   AUXILIARYELECTRICAL      S STE LIMITING CONDITIONS   FOR OPERATION                 SURVEILLANCE REQUIREMENTS 3.9.A. uxilia Electrical       E   ui ment       4.9.A. Auxilia   Electrical   S ste 3.9.A.l.c. (Cont'd)                                 4.9.A.l.a.  (Cont'd)
(2) The 500-kV system is                               an  interval of not less available to the units       1                     than 24 hours.
and 2 shutdown boards through the unit     2                             The  diesel generator .
station-service                                     fast starts (10 seconds) transformer   TUSS 2B   with                     from standby conditions no credit taken for the                             shall  be performed once two 500-kV Trinity lines.                           per 184 days in these If the   unit 1 station-                         surveillance tests. All other engine starts for service transformer is the second choice, a minimum                           the purpose of this test of two 500-kV lines must                           may be preceeded   by an be available.                                      engine idle start.
(3) The Trinity 161-kV line is                         Additional reporting available to the units'                             requirements due to and 2 shutdown boards                               failures are noted in through both    common                            Table 4.9.A.
station-service transformers.                                      All diesel   generator starts shall   be logged.
Notes   for (3):                               b. Once  per operating cycle,  a  test will be (a) If unit 3 is claiming                           conducted simulating a the Trinity line as an                         loss of  offsite power offsite   source, see                         and  similar conditions unit '3 technical                             that would- exist with specifications, Section                       the presence of an 3.9.A.l.c.2.                                   actual safety-injection signal to demonstrate (b) If unit   1 is in cold                       the following:
shutdown, only one common   station-service                       (1) Deenergization   o f the transformer is required.                            emergency buses and load shedding from the emergency buses.
(2) The diesel starts from ambient condition on the auto-start signal, energizes the emergency buses with permanently connected loads, energizes the auto-connected emer-gency loads through BFN                                         3.9/4.9-2
.Unit 1
 
LIMITING CONDITIONS  FOR OPERATION          SURVEILLANCE REQUIREMENTS 3.9.A. Auxilia    E ectrical E ui ment      4.9.A. Auxilia    Electrical  S  stem 3.9.A.l.c. (Cont'd)                          4.9.A.l.b (Cont'd)
(4) The Athens 161-kV line is available to the units 1                  load sequencing, and and 2 shutdown boards                      operates for greater through  a common                          than or equal to five station-service                            minutes while its gener-transformer when unit* 1 is                ator is loaded with the in Cold Shutdown and unit 3                emergency loads.
is not claiming the Athens line as an offsite source.            (3) On diesel generator breaker trip, the loads NOTE FOR  (3) AND (4):                    are shed from the emer-gency buses and the diesel With no cooling tower pumps                output breaker recloses or fans running, a cooling                on the auto-start signal, to~er transformer may be                    the emergency buses are substituted for a common                  energized with permanently station-service transformer.              connected loads, the auto-connected emergency loads are energized through load sequencing, and the diesel operates for gre'ater than or equal to five minutes while its generator is loaded with the emergency loads.
: c. Once a month  the quantity of diesel fuel available shall be logged.
: d. Each diesel generator shall be given an annual inspec-tion in  accordance with instructions based  on the manufacturer's recommendations.
: e. Quarterly the qual'ity of each diesel generator's (A, B, C, and D) seven-day fuel supply shall be checked. The fuel oil quality shall  be within the acceptable  limits specified in Table  1 of ASTM-D975.
BFN                                      3.9/4.9-3 Unit  1


LIMITING CONDITIONS FOR OPERATION SURVEILLANCE REQUIREMENTS 3.9.A.Auxilia E ectrical E ui ment 4.9.A.Auxilia Electrical S stem 3.9.A.l.c.(Cont'd)4.9.A.l.b (Cont'd)(4)The Athens 161-kV line is available to the units 1 and 2 shutdown boards through a common station-service transformer when unit*1 is in Cold Shutdown and unit 3 is not claiming the Athens line as an offsite source.NOTE FOR (3)AND (4): With no cooling tower pumps or fans running, a cooling to~er transformer may be substituted for a common station-service transformer.
4     AUXILIARYELECTRICAL SYSTEM LIMITING CONDITIONS   FOR OPERATION                 SURVEILLANCE REQUIREMENTS 3.9.A. Auxilia     Electrical   E   ui ment       4.9.A. Auxilia     Electrical S stem
load sequencing, and operates for greater than or equal to five minutes while its gener-ator is loaded with the emergency loads.(3)On diesel generator breaker trip, the loads are shed from the emer-gency buses and the diesel output breaker recloses on the auto-start signal, the emergency buses are energized with permanently connected loads, the auto-connected emergency loads are energized through load sequencing, and the diesel operates for gre'ater than or equal to five minutes while its generator is loaded with the emergency loads.c.Once a month the quantity of diesel fuel available shall be logged.d.Each diesel generator shall be given an annual inspec-tion in accordance with instructions based on the manufacturer's recommendations.
: 2. The reactor shall not be                       2~  DC Power System  Unit started up   (made critical)                       Batteries (250-V), Diesel-from the HOT STANDBY CONDITION                      Generator Batteries (125-V) unless all of the following                        and Shutdown Board Batteries conditions are satisfied:                          (250-V)
e.Quarterly the qual'ity of each diesel generator's (A, B, C, and D)seven-day fuel supply shall be checked.The fuel oil quality shall be within the acceptable limits specified in Table 1 of ASTM-D975.
: a. At least one offsite power                     a. Every week the specific source is'" available as                           gravity, voltage and specified in 3.9.A.l.c.                             temperature of the pilot cell and overall battery voltage shall be measured and logged.
BFN Unit 1 3.9/4.9-3 4 AUXILIARY ELECTRICAL SYSTEM LIMITING CONDITIONS FOR OPERATION SURVEILLANCE REQUIREMENTS 3.9.A.Auxilia Electrical E ui ment 4.9.A.Auxilia Electrical S stem 2.The reactor shall not be started up (made critical)from the HOT STANDBY CONDITION unless all of the following conditions are satisfied:
: b. Three units .1 and   2 diesel               b. Every three months the generators shall be                                measurement shall be made OPERABLE.                                          of voltage of each cell to nearest O.l volt, specific gravity of each cell, and temperature of every fifth cell. These measurements shall be
2~DC Power System-Unit Batteries (250-V), Diesel-Generator Batteries (125-V)and Shutdown Board Batteries (250-V)a.At least one offsite power source is'" available as specified in 3.9.A.l.c.
                                                                  ~
a.Every week the specific gravity, voltage and temperature of the pilot cell and overall battery voltage shall be measured and logged.b.Three units.1 and 2 diesel generators shall be OPERABLE.b.Every three months the measurement shall be made of voltage of each cell to nearest O.l volt, specific gravity of each cell, and temperature of every fifth cell.These measurements shall be~logged.c.An additional source of power consisting of one of the following:
logged.
~(1)A second offsite power source available as specified in 3.9.A.l.c.
: c. An additional source of                       c. At least once every 24 power consisting of one                             months, a battery rated of the following:   ~                             discharge (capacity) test shall be performed (1) A second offsite                               and the voltage, time, power source available                         and output current as specified in                               measurements  shall 3.9.A.l.c.                                     be logged.
c.At least once every 24 months, a battery rated discharge (capacity) test shall be performed and the voltage, time, and output current measurements shall be logged.(2)A fourth OPERABLE units 1 and 2 diesel generator.
(2) A fourth OPERABLE units 1 and 2 diesel generator.
d.Requirements 3.9.A.3 through 3.9.A.6 are met.BFN.Unit 1 3.9/4.9-4 AMENDMENT go yg8  
: d. Requirements 3.9.A.3 through 3.9.A.6 are met.
BFN                                           3.9/4.9-4 AMENDMENT go yg8
.Unit  1


4.9 BASES (Cont'd)The monthly test of the diesel generators-is primarily to check for failures and deterioration in the system since last use.The diesels will be loaded to at least 100 percent of its continuous rating (i.e., g 2600 KW)while engine and generator temperatures are stabilized (about one hour).,A minimum 75-percent load will prevent soot formation in the cylinders and injection nozzles.Operation up to an equilibrium temperature ensures that there is no overheating problem.The tests also provide an engine and generator operating history to be compared with subsequent engine-generator test data to identify and to correct any mechanical or electrical deficiency before it can result in a system failure.1 Diesel testing once per 18 months (i.e., at least once per fuel cycle)at a minimum load of 2800 KW for an interval of not less than 24 hours, assures that each diesel generator will be capable of supplying the maximum load during the first 2 hours of a loss of offsite power/loss of coolant accident.This test also demonstrates each diesel generator's long-term load carrying capability.
4.9   BASES   (Cont'd)
The test during refueling outages is more comprehensive, including*procedures that are most effectively conducted at that time.These include automatic actuation and functional capability tests to verify that the generators can"start and be ready to assume load in 10 seconds.The annual inspection will detect any signs of wear long before failure.'BFN tests the 7-day diesel generator fuel oil supplies in accordance with Table 1 of ASTM-D975-89.
The monthly     test of the diesel generators -is primarily to check for failures   and deterioration in the system since last use. The diesels will be loaded to at least 100 percent of its continuous rating (i.e., g 2600 KW) while engine and generator temperatures are stabilized (about one hour). ,A minimum 75-percent load will prevent soot formation in the cylinders and injection nozzles. Operation up to an equilibrium temperature ensures that there is no overheating problem. The tests also provide an engine and generator operating history to be compared with subsequent engine-generator test data to identify and to correct any mechanical or electrical deficiency before it can result in a system failure.                       1 Diesel testing once per 18 months (i.e., at least once per fuel cycle) at a minimum load of 2800 KW for an interval of not less than 24 hours, assures that each diesel generator will be capable of supplying the maximum load during the first 2 hours of a loss of offsite power/loss of coolant accident. This test also demonstrates each diesel generator's long-term load carrying capability.
Each fuel oil supply is tested quarterly.
The   test during refueling outages is more comprehensive, including procedures that are most effectively conducted at that time. These include automatic actuation and functional capability tests to verify that the generators can"start and be ready to assume load in 10 seconds.     The annual inspection will detect any signs of wear long before   failure.
Battery maintenance with regard to the floating charge, equalizing charge, and electrolyte level will be based on the manufacturer's instruction and sound maintenance practices.
      'BFN   tests the 7-day diesel generator fuel oil supplies in accordance with Table 1 of ASTM-D975-89. Each fuel oil supply is tested quarterly.
Xn addition, written records will be maintained of the battery performance.
Battery maintenance with regard to the floating charge, equalizing charge, and electrolyte level will be based on the manufacturer's instruction and sound maintenance practices. Xn addition, written records will be maintained of the battery performance. The plant batteries will deteriorate with time but precipitous failure is unlikely. The type of surveillance called for in this specification is that which has been demonstrated through experience to provide an indication of a cell becoming irregular or unserviceable long before it becomes   a failure.
The plant batteries will deteriorate with time but precipitous failure is unlikely.The type of surveillance called for in this specification is that which has been demonstrated through experience to provide an indication of a cell becoming irregular or unserviceable long before it becomes a failure.The equalizing charge, as recommended by the manufacturer, is vital to maintaining the ampere-hour capacity of the battery and will be applied as recommended.
The   equalizing charge, as recommended by the manufacturer, is vital to maintaining the ampere-hour capacity of the battery and will be applied as recommended.
The testing of the logic systems will verify the ability of the logic systems to bring the auxiliary electrical system to running standby readiness with the presence of an accident signal from any reactor or an undervoltage signal on the 4-kV shutdown boards.The periodic simulation of accident signals in conjunction with diesel generator voltage available signals will confirm the ability of the 480-V load shedding logic system to sequentially shed and restart 480-V loads if an accident signal were present, and diesel generator voltage was the only source of electrical power.BFN ,Unit 1 4.9 BASES (Cont'd)REFERENCES 1.Normal Auxiliary Power System (BFNP FSAR Subsection 8.4)2.Standby AC Power Supply and Distribution (BFNP FSAR Subsection 8.5)3.250-V DC Power Supply and Distribution (BFNP FSAR Subsection 8.6)4.Memorandum from Gene M.Wilhoite to H.J.Green dated December 4, 1981 (LOO 811208 664)and memorandum from C.E.Winn to H.J.Green dated January 10, 1983 (G02 830112 002)~'FN Unit 1 3.9/4.9-22 MIBDMEHT NO.y gg
The   testing of the logic systems will verify the ability of the logic systems to bring the auxiliary electrical system to running standby readiness with the presence of an accident signal from any reactor or     an undervoltage signal on the 4-kV shutdown boards.
The periodic simulation of accident signals in conjunction with diesel generator voltage available signals will confirm the ability of the 480-V load shedding logic system to sequentially shed and restart 480-V loads   if an accident signal were present, and diesel generator voltage was the only source of electrical power.
BFN
,Unit 1


UNIT 2 EFFECTIVE PAGE LIST REMOVE INSERT 3.9/4.9-1 3.9/4.9-2 3.9/4.9-3 3.9/4.9-4 3.9/4.9-21 3.9/4.9-22 3.9/4.9-1 3.9/4.9-2*
4.9  BASES    (Cont'd)
3.9/4.9-3*
REFERENCES
3.9/4.9 4+3.9/4.9-21 3.9/4.9-22*
: 1. Normal  Auxiliary Power System (BFNP FSAR Subsection  8.4)
: 2. Standby  AC Power Supply and  Distribution (BFNP FSAR Subsection 8.5)
: 3. 250-V  DC Power Supply and  Distribution (BFNP FSAR Subsection 8.6)
: 4. Memorandum from Gene M. Wilhoite to H. J. Green dated December 4, 1981 (LOO 811208 664) and memorandum from C. E. Winn to H. J. Green dated January 10, 1983 (G02 830112 002)
                                            ~
                                              'FN MIBDMEHTNO. y gg 3.9/4.9-22 Unit 1
 
UNIT 2 EFFECTIVE PAGE LIST REMOVE                           INSERT 3.9/4.9-1                         3.9/4.9-1 3.9/4.9-2                        3.9/4.9-2*
3.9/4.9-3                        3.9/4.9-3*
3.9/4.9-4                        3.9/4.9 4+
3.9/4.9-21                        3.9/4.9-21 3.9/4.9-22                        3.9/4.9-22*
*Denotes overleaf or spillover page.
*Denotes overleaf or spillover page.
4 AUXIL ARY ELECTRICAL SYS EM LIMITING CONDITIONS FOR OPERATION SURVEILLANCE REQUIREMENTS 3.9 ILIARY ELECTRICAL SYS E 4.9 AUXILIARY ELEC R CAL SYSTEM A 1 cabi it A icab t Applies to all the auxiliary electrical power system.Applies to the periodic testing requirements of the auxiliary electrical system.Ob ective Ob ective To assure an adequate supply of electrical power for operation of those systems required for safety.S ecification A.uxi ia Electrica F.ui ment Verify the operability of the auxiliary electrical system.S ecification A.uxilia Electrical S stem 1.PRIOR TO STARTUP from a COLD CONDITION, the follow-ing must be satisfied:
a.Diesel generators A, B, C, and D OPERABLE.b.Requirements 3.9.A.3 through 3.9.A.6 are met.c.At least two of the following offsite power sources are available:
(1)The 500-kV system is available to the units 1 and 2 shut-down boards through the unit 1 station-service transformer TUSS 1B with no credit taken for the two 500-kV Trinity lines.I f the unit 2 station-service transformer is the second sourc'e, a minimum of two 500-kV lines must be available.
1.Diesel Generators a.Each diesel generator shall be manually.started and loaded to demonstrate operational readiness in accordance with the frequency specified in Table 4.9.A on a staggered test basis.The test shall continue for at least a one-hour period at 100%or greater of the continuous rating of the diesel generator, and the operation of the diesel fuel oil transfer pumps shall be demonstrated.
Also the di'esel generator starting air compressor shall be checked for operation and its ability to recharge air receivers.
Once per 18 months, each diesel generator will be tested at a load of at least 2800 KW to demonstrate full load carrying capability for BFN ,.Unit 2 3.9/4.9-1
/4 AUXILIARY ELECTR CAL SYS EM LIMITING CONDITIONS FOR OPERATION SURVEILLANCE REQUIREMENTS 3.9.A.Auxilia Electr cal E ui ment 4.9.A.Auxilia E ect ica S ste 3.9.A.l.c.(Cont'd)(2)The 500 kV system is available to the units 1 and 2 shutdown boards through the unit 2 station-service transformer TUSS 2B with no credit taken for the two 500-kV Trinity lines..If the unit 1 station-service transformer is the second choice, a minimum of two 500-kV lines must be available.
4.9.A.l.a.(Cont'd)an interval of not less than 24 hours.The diesel generator fast starts (10 seconds)from standby conditions shall be performed once per 184 days in these surveillance tests.All other engine starts for the purpose of this test may be preceeded by an engine idle'start.
(3)The Trinity 161-kV line is available to the units 1 and 2 shutdown boards through both common station-service transformers.
NOTES FOR (3): (a)If unit 3 is claiming the Trinity line as an offsite source, see unit 3 technical specifications, Section 3.9.A.l.c.2.(b)If unit 1 is in-cold shutdown, only one common station-service transformer is required.Additional reporting requirements due to failures are noted in Table 4.9.A..All diesel generator starts shall be logged.b.Once per operating cycle, a test.will be conducted simulating a loss of offsite power and similar conditions that would exist with the presence of an actual safety-injection signal to demonstrate the following:
(1)Deenergization of the emergency buses and load shedding from the emergency buses.(2)The diesel starts from ambient con-dition on the auto-start signal, energizes the emer-gency buses with permanently connec-ted loads, energizes the auto-connected BFN Unit 2 3.9/4.9-2


4 AUXIL ARY ELEC R CAL SYSTEM LIMITING CONDITIONS FOR OPERATION SURVEILLANCE REQUIREMENTS 3.9.A.Auxilia Electrical E ui ment 4.9.A.Auxilia Electrica S stem 3.9.A.l.c.(Cont'd)4.9.A.l.b.(Cont'd)emergency loads through load sequencing, and operates for greater than or equal to five minutes while its generator is loaded with the emergency loads.(4)The Athens 161-kV line is available tothe units 1 and 2 shutdown boards through a common station-service transformer when unit 1 is in Cold Shutdown and unit 3 is not.claiming the Athens line as an offsite source.NOTE FOR (3)AND (4): With no cooling tower pumps or fans running, a cooling tower transformer may be substituted for a common station-service transformer.
4     AUXIL ARY ELECTRICAL SYS      EM LIMITING CONDITIONS       FOR OPERATION             SURVEILLANCE REQUIREMENTS 3.9         ILIARY ELECTRICAL      SYS E           4.9   AUXILIARYELEC        R CAL SYSTEM A   1  cabi  it                                  A   icab      t Applies to   all  the auxiliary                  Applies to the periodic electrical    power system.                       testing requirements of the auxiliary electrical      system.
(3)On diesel generator breaker trip, the loads are shed from the emergency buses and the diesel output breaker recloses on the.auto-start signal, the emergency buses are energized with permanently connected~loads, the auto-connected emergency loads are energized through load sequencing, and the diesel operates for greater than or equal to five minutes while its generator is loaded with the emergency loads.c.Once a month the quantity of diesel fuel available shall be logged.d.Each diesel generator shall be given an annual inspec-tion in accordance with instructions based on the manufacturer's recommendations.
Ob  ective                                        Ob  ective To assure    an adequate supply of                Verify the operability of the electrical    power for operation of             auxiliary electrical system.
e.Quarterly the quality of each diesel generator's (A, B, C, and D)seven-day fuel supply shall be checked.The fuel oil quality shall be within the acceptable limits speci-fied in Table 1 of ASTM-D975.
those systems required for safety.
BFN.:Unit 2 3.9/4.9-3 4.AUXILIARY ELEC AL SYSTE LIMITING CONDITIONS FOR OPERATION SURVEILLANCE REQUIREMENTS 3;9.A.Auxilia Electrical E ui ment 4.9.A.Auxilia Electrical S stem 2.The reactor shall not be started up (made critical)from the HOT STANDBY CONDITION unless all of the following conditions are satisfied:
S  ecification                                    S  ecification A. uxi ia    Electrica    F. ui ment         A. uxilia      Electrical   S stem
2;DC Power System-Unit Batteries (250-V), Diesel-Generator Batteries (125-V)and Shutdown Board Batteries (250-V)a.At least one offsite power source is available as specified in 3.9.A.l.c.
: 1. PRIOR TO STARTUP from a                      1. Diesel Generators COLD CONDITION, the follow-ing must be satisfied:
a.Every week the specific gravity, voltage and temperature of the pilot cell and overall battery voltage shall be measured and logged.b.Three units 1 and 2 diesel generators shall be OPERABLE.b.Every three months the measurement shall be made'f voltage of each cell to nearest 0.1 volt, specific gravity of each~cell, and temperature of every fifth cell.These measurements shall be logged.c.An additional source of power consisting of one of the following:
: a. Each  diesel generator
(1)A second offsite power source available as specified in 3.9.A.l.c.
: a. Diesel generators A,                               shall be manually B, C, and   D OPERABLE.                        . started and loaded to demonstrate operational
c.At least once every 24'months, a battery rated discharge (capacity) test shall be performed and the voltage, time, and output current measurements shall be logged.(2)A fourth OPERABLE units 1 and 2 diesel generator.
: b. Requirements   3.9.A.3                             readiness in accordance through 3.9.A.6 are                               with the frequency met.                                               specified in Table 4.9.A on a staggered
d.Requirements 3.9.A.3 through 3.9.A.6 are met.BFN ,Unit 2 3.9/4.9-4 AMPHORA'5 NP gg$
: c. At least two of the                                 test basis. The test following offsite power                            shall continue for at sources are available:                            least a one-hour period at 100% or greater of (1) The 500-kV system                              the continuous rating is available to the                          of the diesel generator, units 1 and 2 shut-                          and the operation of down boards through                          the diesel fuel oil the unit   1 station-                        transfer pumps shall service transformer                          be demonstrated. Also TUSS 1B  with no                              the di'esel generator credit taken for                              starting air compressor the two 500-kV                                shall be checked for Trinity lines. I f                            operation and its the unit 2 station-                           ability to recharge service transformer                          air receivers.
4.9 BASES (Cont'd)The monthly tests of the diesel generators are primarily to check for failures and deterioration in the system since last use.The diesels will be loaded to at least 100 percent of its continuous rating (i.e., g 2600 KW)while engine and generator temperatures are stabilized (about one hour).A minimum 75-percent load will prevent soot formation in the cylinders and injection nozzles.Operation up to an equilibrium temperature ensures that there is no overheating problem.The tests also provide an engine and generator operating history to be compared with.subsequent engine-generator test data to identify and to correct any mechanical or electrical deficiency before it can result in a system failure.Diesel testing once per 18 months (i.e., at least once per fuel cycle).at a minimum load of 2800 KW for an interval of not less than 24 hours assures that each diesel generator will be capable of supplying the maximum load during the first 2 hours of a loss of offsite power/loss of coolant accident.This test also demonstrates each diesel generator's long-term load carrying capability.
is the second sourc'e, a minimum                            Once  per  18 months, each of two 500-kV lines                          diesel generator will must be available.                           be tested at a load of at least 2800 KW to demonstrate  full load carrying capability for BFN                                           3.9/4.9-1
The test during refueling outages is more comprehensive, including procedures that are most effectively conducted at that time.These include automatic actuation and functional capability tests to verify that the generators can start and be ready to assume load in 10 seconds.The annual inspection will detect any signs of wear long before failure.The.diesel generators are shared by units 1 and 2.Therefore, the capability for the units 1 and 2 diesel generators to accept the emergency loads will be performed during the unit 1 operating cycle using the unit 1 loads.BFN tests the 7-day diesel generator fuel oil supplies=in accordance with Table 1 of ASTM-D975-89.
,. Unit  2
Each fuel oil supply is tested quarterly.
Battery maintenance with regard to the floating charge, equalizing
=charge, and electrolyte level will be based on the manufacturer's instruction and sound maintenance practices.
In addition, written records will be maintained of the battery performance.
The plant batteries will deteriorate with time but precipitous failure is unlikely..
The type of surveillance called for in this specification is that which has been demonstrated through experience to provide an indication of a cell becoming irregular or unserviceable long before it becomes a failure.The equalizing charge, as recommended by the manufacturer, is vital to maintaining the ampere-hour capacity of the battery and will be applied as recommended.
The testing of the logic systems will verify the ability of the logic systems to bring the auxiliary electrical system to running standby readiness with the presence of an accident signal from any reactor or an undervoltage signal on the 4-kV shutdown boards.BFN Unit 2 3.9/4."9-21


4.9 BASES (Cont'd)The'eriodic simulation of accident signals in conjunction with diesel generator voltage available signals will confirm the ability of the 480-V load shedding logic system to sequentially shed and restart 480-V loads if an accident signal were present, and diesel generator voltage were the only source of electrical power.I REFERENCES 1.Normal Auxiliary Power System (BFNP FSAR Subsection 8.4)2.Standby AC Power Supply and Distribution (BFNP FSAR Subsection 8.5)3.250-V DC Power Supply and Distribution (BFNP FSAR Subsection 8.6)4.Memorandum from Gene M.Wilhoite to H.J.Green dated December 4, 1981 (LOO 811208 664)and memorandum from C.E.Winn.to H.J.Green dated January 10, 1983 (G02 830112 002)BFN Unit 2 3 9/4~9-22 AMENDMENT NO.I 4 9 UNIT 3 EFFECTIVE PAGE LIST REMOVE INSERT 3.9/4.9-1 3.9/4.9-2 3.9/4.9-3 3.9/4.9-4 3.9/4.9-20 3.9/4.9-21 3.9/4.9-1 3.9/4.9-2*
  /4    AUXILIARYELECTR CAL SYS        EM LIMITING CONDITIONS  FOR OPERATION                  SURVEILLANCE REQUIREMENTS 3.9.A. Auxilia    Electr cal    E ui  ment        4.9.A. Auxilia      E  ect ica  S ste 3.9.A.l.c. (Cont'd)                                  4.9.A.l.a.  (Cont'd)
3.9/4.9-3*
(2) The 500 kV system is                                  an  interval of not less available to the units      1                        than 24 hours.
3.9/4.9 4*3.9/4.9-20 3.9/4.9-21*
and 2 shutdown boards through the unit    2                              The  diesel generator station-service                                      fast starts (10 seconds) transformer  TUSS 2B  with                        from standby conditions no credit taken for the                              shall  be performed once two 500-kV  Trinity lines.                          per 184 days in these
            .If the unit 1 station-                              surveillance tests. All service transformer is the                          other engine starts for second choice, a minimum                            the purpose of this test of two 500-kV lines must                            may be preceeded      by an be available.                                        engine    idle'start.
(3) The  Trinity 161-kV line is                          Additional reporting available to the units      1                        requirements due to and 2 shutdown boards                                failures are noted in through both    common                              Table 4.9.A.
station-service transformers.                                      . All diesel    generator starts shall      be logged.
NOTES FOR  (3):
: b. Once  per operating (a)  If unit 3  is claiming                        cycle,    a  test. will be the Trinity line as an                          conducted simulating a offsite  source, see                            loss of offsite power unit 3 technical                                and similar conditions specifications, Section                        that would exist with 3.9.A.l.c.2.                                    the presence of an actual safety-injection (b)  If unit  1  is in- cold                        signal to demonstrate the following:
shutdown, only one common  station-service transformer is required.                        (1) Deenergization of the emergency buses and load shedding from the emergency buses.
(2) The diesel starts from ambient con-dition    on the auto-start signal, energizes the emer-gency buses    with permanently connec-ted loads, energizes the auto-connected BFN                                        3.9/4.9-2 Unit  2
 
4    AUXIL ARY ELEC  R  CAL SYSTEM LIMITING CONDITIONS  FOR OPERATION                SURVEILLANCE REQUIREMENTS 3.9.A. Auxilia    Electrical  E  ui  ment        4.9.A. Auxilia      Electrica  S stem 3.9.A.l.c. (Cont'd)                                4.9.A.l.b. (Cont'd) emergency loads through load sequencing, and operates for greater than or equal to five minutes while its generator is loaded with the emergency loads.
(4) The Athens 161-kV line is                    (3)  On diesel generator available to the units 1                          breaker trip, the and 2 shutdown boards                              loads are shed from through a  common                                  the emergency buses station-service                                    and the diesel output transformer    when unit 1 is                      breaker recloses on in Cold Shutdown and unit 3                        the .auto-start signal, is not. claiming the Athens                        the emergency buses line as an offsite source.                          are energized with permanently connected NOTE FOR  (3)  AND  (4):                        ~
loads, the auto-connected emergency With no cooling tower pumps                        loads are energized or fans running, a cooling                          through load tower transformer may be                            sequencing, and the substituted for a common                            diesel operates for station-service transformer.                        greater than or equal to five minutes while its generator is loaded with the emergency loads.
: c. Once a month    the quantity of diesel fuel available shall be logged.
: d. Each diesel generator shall be given an annual inspec-tion in accordance with instructions based on the manufacturer's recommendations.
: e. Quarterly the quality of each diesel generator's (A, B, C, and D) seven-day    fuel supply shall be checked. The fuel oil  quality shall be within the acceptable    limits speci-fied in Table  1  of ASTM-D975.
BFN                                      3.9/4.9-3
.:Unit  2
: 4. AUXILIARYELEC        AL SYSTE LIMITING CONDITIONS    FOR OPERATION                SURVEILLANCE REQUIREMENTS 3;9.A. Auxilia    Electrical  E ui  ment      4.9.A. Auxilia      Electrical  S  stem
: 2. The reactor shall not be                      2;  DC  Power System  Unit started  up (made  critical)                    Batteries (250-V), Diesel-from the HOT STANDBY CONDITION                    Generator Batteries (125-V) unless all of the following                      and Shutdown Board Batteries conditions are satisfied:                        (250-V)
: a. At least one  offsite power                a. Every week the specific source  is available as                            gravity, voltage and specified in 3.9.A.l.c.                            temperature of the pilot cell and overall battery voltage shall be measured  and logged.
: b. Three  units  1 and 2  diesel                b. Every three months the generators shall be                                measurement  shall  be  made'f OPERABLE.                                            voltage of each cell to nearest 0.1 volt, specific gravity of each
                                                                ~
cell, and temperature of every  fifth cell. These measurements  shall  be logged.
: c. An  additional source of                    c. At least once every 24 power  consisting of one                          'months, a battery rated of the following:                                  discharge (capacity) test shall be performed (1)  A second  offsite                            and the voltage, time, power source  available                      and output current as specified  in                            measurements shall 3.9.A.l.c.                                    be logged.
(2)  A fourth OPERABLE units 1 and 2 diesel generator.
: d. Requirements 3.9.A.3 through 3.9.A.6 are met.
BFN                                          3.9/4.9-4              AMPHORA'5 NP  gg$
,Unit  2
 
4.9    BASES  (Cont'd)
The monthly tests of the diesel generators are primarily to check for failures and deterioration in the system since last use. The diesels will  be loaded to at least 100 percent of its continuous rating        (i.e.,  g 2600 KW) while engine and generator temperatures are stabilized (about one hour). A minimum 75-percent load        will prevent soot formation in the cylinders    and  injection  nozzles. Operation  up to an equilibrium temperature ensures that there is no overheating problem. The tests also provide an engine and generator operating history to be compared with .subsequent engine-generator test data to identify and to correct any mechanical or electrical deficiency before        it can result in a system failure.
Diesel testing once per 18 months (i.e., at least once per fuel cycle).
at a minimum load of 2800 KW for an interval of not less than 24 hours assures that each diesel generator will be capable of supplying the maximum load during the first 2 hours of a loss of offsite power/loss of coolant accident. This test also demonstrates each diesel generator's long-term load carrying capability.
The  test during refueling outages is more comprehensive, including procedures that are most effectively conducted at that time. These include automatic actuation and functional capability tests to verify that the generators can start and be ready to assume load in 10  seconds. The annual inspection will detect any signs of wear long before failure. The. diesel generators are shared by units 1 and 2.
Therefore, the capability for the units 1 and 2 diesel generators to accept the emergency loads will be performed during the        unit  1 operating cycle using the unit 1 loads.
BFN tests the 7-day diesel generator fuel oil supplies=in accordance with Table 1 of ASTM-D975-89. Each fuel oil supply is tested quarterly.
Battery maintenance with regard to the floating charge, equalizing        =
charge, and electrolyte level will be based on the manufacturer's instruction and sound maintenance practices. In addition, written records will be maintained of the battery performance. The plant batteries will deteriorate with time but precipitous failure is unlikely.. The type of surveillance called for in this specification is that which has been demonstrated through experience to provide an indication of    a cell  becoming  irregular or unserviceable long before    it becomes  a  failure.
The  equalizing charge, as recommended by the manufacturer, is vital to maintaining the ampere-hour capacity of the battery and will be applied as recommended.
The  testing of the logic systems will verify the ability of the logic systems to bring the auxiliary electrical system to running standby readiness with the presence of an accident signal from any reactor or an undervoltage signal on the 4-kV shutdown boards.
BFN                                        3.9/4."9-21 Unit 2
 
4.9 BASES (Cont'd)
The'eriodic simulation of accident signals in conjunction with diesel generator voltage available signals will confirm the ability of the 480-V load shedding logic system to sequentially shed and restart 480-V loads if an accident signal were present, and diesel generator voltage were the only source of electrical power.
I REFERENCES
: 1. Normal Auxiliary Power System (BFNP FSAR Subsection   8.4)
: 2. Standby AC Power Supply and   Distribution (BFNP FSAR Subsection 8.5)
: 3. 250-V DC Power Supply and Distribution (BFNP FSAR Subsection 8.6)
: 4. Memorandum from Gene M. Wilhoite to H. J. Green dated December 4, 1981 (LOO 811208 664) and memorandum from C. E. Winn. to H. J. Green dated January 10, 1983 (G02 830112 002)
BFN Unit 2 3 9/4 9-22
                                            ~                  AMENDMENTNO.
I4 9
 
UNIT 3 EFFECTIVE PAGE LIST REMOVE                         INSERT 3.9/4.9-1                     3.9/4.9-1 3.9/4.9-2                      3.9/4.9-2*
3.9/4.9-3                      3.9/4.9-3*
3.9/4.9-4                      3.9/4.9 4*
3.9/4.9-20                    3.9/4.9-20 3.9/4.9-21                    3.9/4.9-21*
*Denotes overleaf or spillover page.
*Denotes overleaf or spillover page.
4.AUXILIARY ELECTRICAL S STEM LIMITING CONDITIONS FOR OPERATION SURVEILLANCE REQUIREMENTS 3.9 Auxiliar Electrical S st 4.9 Auxilia E ectr cal S stem A licabi it Applies to all the auxiliary electrical power system.A licabilit Applies to the periodic testing requirements of the auxiliary electrical system.Ob ective~Ob ective To assure an adequate supply of electrical power'or operation of those systems required for safety.Verify the operability of the auxiliary electrical system.S ecification S ecification A.u ilia Electrica.E ui ment A.Aux lia Electrica S stem 1.PRIOR TO STARTUP from a COLD CONDITION, the following must be satisfied:
: 4. AUXILIARYELECTRICAL        S STEM LIMITING CONDITIONS     FOR OPERATION               SURVEILLANCE REQUIREMENTS 3.9   Auxiliar Electrical       S st             4.9   Auxilia       E ectr cal   S stem A licabi it                                         A    licabilit Applies to   all   the auxiliary                   Applies to the periodic electrical   power system.                         testing requirements of the auxiliary electrical       system.
a.Diesel generators 3A,3B, 3C, and 3D OPERABLE.b.Requirements 3.9.A.3 through 3.9.A.6 are met.c.At least two of the following offsite power sources'are available:
Ob ective                                         ~Ob ective To assure   an adequate     supply of             Verify the operability of the electrical power'or operation of                   auxiliary electrical system.
(1)The 500-kV system is available to the unit 3 shutdown boards through the unit 3 station-service transformer TUSS 3B with no credit taken for the two 500-kV Trinity lines.1.Diesel Generators a.Each diesel generator shall be manually~, started and loaded to demonstrate operational readiness in accordance'ith the frequency specified in Table 4.9.A on a staggered test basis.The test shall continue for at least a one-hour period at 100%or greater of the continuous rating of the diesel gener-ator, and the operation of the diesel fuel oil transfer pumps shall be demonstrated.
those systems required for safety.
Also, the diesel generator starting air compressor shall be checked for operation and its ability to recharge air receivers.
S ecification                                     S   ecification A. u ilia     Electrica   .E ui ment         A. Aux lia     Electrica     S             stem
Once per 18 months, each diesel generator will be tested at a load of at least 2800 KW to demonstrate full load carrying capability BFN ,Unit 3 3.9/4.9-1 4 AUX LIARY ELEC CAL SYS E LIMITING CONDITIONS FOR OPERATION SURVEILLANCE REQUIREMENTS 3.9.A.Auxi a Electrical E ui ment 3.9.A.l.c.(Cont'd)(2)The Trinity 161-kV line is available to the unit 3 shutdown boards through a common station-servt.ce or cooling tower.'ransformer.
: 1. PRIOR TO STARTUP from a COLD                   1. Diesel Generators CONDITION, the following must be   satisfied:
NOTE FOR (2): If units 1 and 2 are both in operation and claiming the Trinity line as an offsite source, TUSS 3B must be claimed as the other offsite source for unit 3.4.9.A.Auxilia Electrical S stem 4.9.A.l.a.(Cont'd)for.an interval of not less than 24 hours.The diesel generator fast starts (10 seconds)from standby conditions shall be performed once per 184 days in these surveil-lance tests.All other engine starts for the purpose of this test may be preceeded by an engine idle start.Additional reporting requirements due to failures are noted in Table 4.9.A.(3)The Athens 161-kV line is available to unit 3 shutdown boards through a common station-service or cooling tower transformer.
: a. Each  diesel generator
NOTE FOR (3): If either unit 1 or unit 2 is claiming the Athens line as an offsite source, it may not be claimed as an offsite source for unit 3.'All diesel generator.starts shall be logged.b.Once per operating cycle, a test will be conducted simulating a loss of offsite power and similar conditions that would exist with the presence of an actual safety-injection signal to demonstrate the following:
: a. Diesel generators 3A,                               shall be manually 3B, 3C, and 3D OPERABLE.                     ~
(1)Deenergization of the emergency buses and load shedding from the emergency buses.(2)The diesel starts from ambient con-dition on the auto-start signal, ener-gizes the emergency buses with perman-ently connected lo'ads, energizes the auto-connected emergency loads BFN ,rUnit 3 3.9/4.9-2  
                                                                          , started and loaded to demonstrate operational
: b. Requirements     3.9.A.3                             readiness in    accordance'ith through 3.9.A.6 are                                         the frequency met.                                                 specified in Table 4.9.A on a staggered
: c. At least two of the                                  test basis. The test following offsite power                              shall continue for at sources'are available:                              least a one-hour period at 100% or greater of (1) The 500-kV system                                the continuous rating is available to the                            of the diesel gener-unit  3 shutdown                                ator, and the operation boards through the                              of the diesel fuel oil unit  3  station-                              transfer   pumps               shall service transformer                            be demonstrated.                   Also, TUSS 3B  with no                              the diesel generator credit taken for                              starting air compressor the two 500-kV                                shall be checked for Trinity lines.                                  operation and its ability to recharge air receivers.
Once   per 18 months,                 each diesel generator will be tested at a load of at least 2800 KW to demonstrate     full load carrying capability BFN                                         3.9/4.9-1
,Unit 3
 
4   AUX LIARY ELEC       CAL SYS E LIMITING CONDITIONS   FOR OPERATION                 SURVEILLANCE REQUIREMENTS 3.9.A. Auxi   a   Electrical   E ui ment         4.9.A. Auxilia    Electrical  S stem 3.9.A.l.c.   (Cont'd)                               4.9.A.l.a. (Cont'd)
(2) The  Trinity 161-kV line                          for.an interval of not is available to the                                less than   24 hours.
unit 3 shutdown boards through  a common                                The diesel generator fast station-servt.ce or                                starts   (10 seconds) from cooling tower                                      standby conditions shall
            .'ransformer.                                        be performed once per 184 days in these surveil-NOTE FOR    (2):                                  lance tests. All other engine starts for the If  units 1 and 2 are                              purpose of this test may both in operation and                              be preceeded by an engine claiming the Trinity                              idle start.
                          'All line  as an  offsite source,  TUSS 3B  must                          Additional reporting be claimed as the      other                      requirements due to offsite  source  for                            failures are noted in unit 3.                                            Table 4.9.A.
(3) The Athens 161-kV line                                   diesel generator is available to unit 3                           .starts shall be logged.
shutdown boards through a common   station-service                   b. Once per operating or cooling tower                                  cycle, a test will be transformer.                                      conducted simulating a loss of offsite power and NOTE FOR    (3):                                  similar conditions that would exist with the If either    unit 1 or                            presence of an actual safety-injection signal unit 2  is  claiming the  Athens    line as an                          to demonstrate the offsite source, it may                            following:
not be claimed as an offsite source for                                  (1) Deenergization of the unit 3.                                                emergency buses and load shedding from the emergency buses.
(2) The diesel starts from ambient con-dition on the auto-start signal, ener-gizes the emergency buses with perman-ently connected lo'ads, energizes the auto-connected emergency loads BFN                                       3.9/4.9-2
,rUnit 3
 
4    AUXILIARYELEC      R C L SYSTE LIMITING,CONDITIONS    FOR OPERATION            SURVEILLANCE REQUIREMENTS tern 3.9.A.. Auxilia      Electr  ca                  4.9.A. A        a    Elect  ca gcLuuimerr t                                    '~Ss 3.9.A.l.c.(3) (Cont'd)                          4.9.A.l.b.      (Cont'd) through load sequencing, and operates for greater than or equal to five minutes while its gener-ator is loaded with NOTES FOR    (2)  AND (3):                      the emergency loads.
If both  Athens and                      (3)  On diesel generator breaker trip, the Trinity lines are claimed as the two                            loads are shed from offsite sources for                            the emergency buses unit "3, no credit may                          and the diesel output be taken    for'he                              breaker closes on the Athens-Trinity line                            auto=start signal, the tie  breaker.                                  emergency buses are Specifically, the                              energized with Athens line supplies                            permanently connected unit 3 through common                          loads, the auto-station-service                                connected emergency transformer A or                              loads're      energized cooling tower                                  through load transformer 1, and                            sequencing, and the the  Trinity line                              diesel operates for must supply    unit 3                          greater than or equal through  common  station-                    to five minutes while service transformer    B or                  its generator is cooling tower                                  loaded with the transformer 2.                                emergency loads".
: c. Once a month      the quantity of diesel fuel available shall be loggede
: d. Each  diesel generator shall be given an annual inspection'n accordance with instructions based on the manufacturer's recommendations.
: e. Quarterly the quality of each diesel generator's (3A; 3B, 3C, and 3D) seven-day fuel load.
supply, shall be checked. The fuel  oil quality shall be'ithin the acceptable      limits specified in'Table    1  of ASTM-D975.
BFN                                    3.9/4.9-3 Unit  3
 
4    AUXILIARYELE          CAL SYSTEM LIMITING CONDITIONS    FOR OPERATION                    SURVEILLANCE REQUIREMENTS 3.9.A. Aux    ia    Elect ica    E ui      e t          4.9.A. Aux    ia    Electrical
                                                                  ~Sseem
: 2. The  reactor shall not be                            2~  DC  Power S ste  Unit started up (made critical)                                Batteries (250-V),
from the    HOT STANDBY CONDITION                        Diesel-Generator unless    all of  the following                          Batteries (125-V)and conditions are satisfied:                                Shutdown Board    Batteries'250-V)
: a. At least  one offsite power                        a. Every week the source  is available as                                  specific gravity, specified in 3.9.A.l.c.                                  voltage,  and temperature of the pilot cell, and overall battery voltage shall be measured and logged.
: b. Three  units  3  diesel                            b. Every three months generators shall be                                      the measurements OPERABLE.                                                shall be made of voltage of each cell to nearest 0.1 volt, specific gravity of each cell, and temperature of every
                                                                        'fifth cell.                  These measurements                  shall be logged.
: c. An  additional source of                            c. At least once every power consisting of      one'f 24 months,    a              battery the following:                                      rated discharge (capacity) test (1)  A second  offsite                                  shall  be performed power source  available                            and  the voltage, as specified  in                                    time, and output 3.9.A.l.c.                                          current measurements shall  be logged.
(2) A fourth unit 3 diesel generator OPERABLE.
: d. Requirements 3.9.A.3 through 3.9.Ae6 are met.
                                                                          'AMENDMENT NO. g,              p 9 BFN                                            3.9/4.9-4
.Unit  3
 
4.9    BASES  (Cont'd)
The monthly tests of the diesel generators are primarily to check            for, failures and deterioration in the system since last use. The diesels will  be loaded to at least 100 percent of          its continuous rating (i.e. g 2600 KW) while engine and generator temperatur'es are stabilized (about
      ~one hour). A minimum 75-percent load            will  prevent soot formation in the cylinders and injection        nozzles. Operation  up to an equilibrium temperature ensures      that  there  is  no  overheating  problem. The tests also provide    an  engine  and  generator    operating  history  to be compared with  subsequent    engine-generator    test  data  to identify  and to correct any  mechanical    or electrical  deficiency    before  it can  result in a system failure.
Diesel testing once per        18 months (i.e., at least once per fuel cycle) at, a. minimum'load    of 2800 KW for an interval of not less. than 24 hours assu'res that each diesel generator will be capable of supplying the maximum load during the first 2 hours of a loss of offsite power/loss of coolant accident. This test also demonstrates each diesel generator's long-term load carrying capability.
The  test during refueling outages is more comprehensive, including procedures that are most effectively conducted at that time. These include automatic actuation and functional capability tests to verify that the generators can start and be ready to assume load in 10 seconds.      The annual inspection will detect any. signs of wear long before    failure.
BFN tests the 7-'day diesel generator fuel oil supplies 'in accordance with Table 1 of ASTM-D975-89. Each fuel oil supply is tested quarterly.
Battery maintenance with regard to the floating charge, equalizing charge, and electrolyte level will be based on the manufacturer's instruction and sound maintenance practices. In addition, written records will be maintained of the battery performance. The plant batteries will deteriorate with time but precipitous failure is unlikely. The type of surveillance called for .in this specification is that which has been demonstrated through experience to provide an indication of a cell becoming irregular or unserviceable long before            it becomes    a  failure.
The  equalizing charge, as recommended by the manufacturer, is vital to maintaining the ampere-hour capacity of the battery and will be applied as recommended.
The  testing of the logic system will verify the ability of the logic systems to bring the auxiliary electrical system. to running standby readiness with the presence of an accident signal from any reactor or an undervoltage signal on the start buses or 4-kV shutdown boards.
The  periodic simulation of accident signals in conjunction with diesel generator voltage available signals will confirm the ability of the
      '80-V load shedding logic system to sequentially shed and restart 480-V loads  if  an accident signal were present, and diesel generator voltage were the only source of electrical power.
BFN                                          3.9/4.9-20
.Unit  3
 
4 v 4,9 Refere ces
: 1. Normal  Auxiliary,Power  System (BFNP FSAR Subsection    8.4)
: 2. Standby  AC Power Supply and  Distribution  (BFNP FSAR Subsection 8.5)
: 3. 250-V  DC  Power Supply and  Distribution  (BFNP FSAR Subsection 8.6)
: 4. Memorandum from 'G. M. Wilhoite to  H. J. Green dated December 4, 1981 (LOO 811208 664)    and  memorandum  from C. E. Winn to H. J. Green dated January 10,  1983  (G02  830112  002)
BFN                                      3.9/4.9-21              AMENoMBr NG. I pC
    ~ / Unit 3


4 AUXILIARY ELEC R C L SYSTE LIMITING, CONDITIONS FOR OPERATION SURVEILLANCE REQUIREMENTS 3.9.A..Auxilia Electr ca gcLuuimerr t 3.9.A.l.c.(3)(Cont'd)4.9.A.A a Elect ca'~Ss tern 4.9.A.l.b.(Cont'd)NOTES FOR (2)AND (3): If both Athens and Trinity lines are claimed as the two offsite sources for unit"3, no credit may be taken for'he Athens-Trinity line tie breaker.Specifically, the Athens line supplies unit 3 through common station-service transformer A or cooling tower transformer 1, and the Trinity line must supply unit 3 through common station-service transformer B or cooling tower transformer 2.through load sequencing, and operates for greater than or equal to five minutes while its gener-ator is loaded with the emergency loads.(3)On diesel generator breaker trip, the loads are shed from the emergency buses and the diesel output breaker closes on the auto=start signal, the emergency buses are energized with permanently connected loads, the auto-connected emergency loads're energized through load sequencing, and the diesel operates for greater than or equal to five minutes while its generator is loaded with the emergency loads".c.Once a month the quantity of diesel fuel available shall be loggede d.Each diesel generator shall be given an annual inspection'n accordance with instructions based on the manufacturer's recommendations.
The diesel generator fuel oil system for each unit includes a day tank mounted on the diesel engine skid and a seven-day tank assembly embedded in the diesel generator building floor. Transfer between the seven-day tank assembly and the day tank is accomplished automatically by transfer pumps controlled by float operated switches which sense fuel           oil level in the day tank. New fuel oil added to the seven-day tank assembly is tested in accordance   with plant procedures.       In addition, the auxiliary boiler reservoirs   may be used as a     long-term backup fuel   oil supply. These reservoirs are sampled     quarterly   and fuel oil is not allowed to be transferred   to the seven-day   tank assemblies until the quality is verified to be acceptable   per ASTM-D975,   Table   l.>>
e.Quarterly the quality of each diesel generator's (3A;3B, 3C, and 3D)seven-day fuel load.supply, shall be checked.The fuel oil quality shall be'ithin the acceptable limits specified in'Table 1 of ASTM-D975.
The BFN   surveillance requirements are being revised to specify that the fuel oil supply for each diesel generator is tested quarterly. This change is consistent with standard industry fuel oil sampling practices, regulatory guidelines, and the GE standard TSs. The bases section is being revised to state that BFN tests each seven-day fuel oil supply in accordance with Table 1 of ASTM-D975-89 quarterly.
BFN Unit 3 3.9/4.9-3 4 AUXILIARY ELE CAL SYSTEM LIMITING CONDITIONS FOR OPERATION SURVEILLANCE REQUIREMENTS 3.9.A.Aux ia Elect ica E ui e t 4.9.A.Aux ia Electrical
: 4. Existing   LCO 3.9.A.6 currently reads:
~Sseem 2.The reactor shall not be started up (made critical)from the HOT STANDBY CONDITION unless all of the following conditions are satisfied:
There   shall be a minimum   of 103,300 gallons of diesel fuel in the standby diesel-generator   fuel tanks.
2~DC Power S ste-Unit Batteries (250-V), Diesel-Generator Batteries (125-V)and Shutdown Board Batteries'250-V) a.At least one offsite power source is available as specified in 3.9.A.l.c.
Proposed change to     LCO 3.9.A.6 .would read:
a.Every week the specific gravity, voltage, and temperature of the pilot cell, and overall battery voltage shall be measured and logged.b.Three units 3 diesel generators shall be OPERABLE.b.Every three months the measurements shall be made of voltage of each cell to nearest 0.1 volt, specific gravity of each cell, and temperature of every'fifth cell.These measurements shall be logged.c.An additional source of power consisting of one'f the following:
There shall be a minimum of 35,280 gallons of diesel           fuel in each of the seven-day diesel generator fuel tank assemblies.
(1)A second offsite power source available as specified in 3.9.A.l.c.
Justification for     LCO 3.9.A.6 This specification is being changed to'require that there be a minimum of 35,280 ga'lions of diesel fuel in each of the diesel generator seven-day fuel tank assemblies. This change is made to clarify the nature of the diesel generator fuel oil storage system and make           it applicable to each diesel generator.               e At BFN there are two sets of four diesel generators (Unit 1 and 2 diesel generators A, B, C, and D; and Unit 3 diesel generators 3A, 3B, 3C, and
(2)A fourth unit 3 diesel generator OPERABLE.c.At least once every 24 months, a battery rated discharge (capacity) test shall be performed and the voltage, time, and output current measurements shall be logged.d.Requirements 3.9.A.3 through 3.9.Ae6 are met.BFN.Unit 3 3.9/4.9-4'AMENDMENT NO.g, p 9 4.9 BASES (Cont'd)The monthly tests of the diesel generators are primarily to check for, failures and deterioration in the system since last use.The diesels will be loaded to at least 100 percent of its continuous rating (i.e.g 2600 KW)while engine and generator temperatur'es are stabilized (about~one hour).A minimum 75-percent load will prevent soot formation in the cylinders and injection nozzles.Operation up to an equilibrium temperature ensures that there is no overheating problem.The tests also provide an engine and generator operating history to be compared with subsequent engine-generator test data to identify and to correct any mechanical or electrical deficiency before it can result in a system failure.Diesel testing once per 18 months (i.e., at least once per fuel cycle)at, a.minimum'load of 2800 KW for an interval of not less.than 24 hours assu'res that each diesel generator will be capable of supplying the maximum load during the first 2 hours of a loss of offsite power/loss of coolant accident.This test also demonstrates each diesel generator's long-term load carrying capability.
    ,3D). The current technical specifications imply the existence of one large fuel storage tank for each set of diesel generators and that this tank will be required to contain at least 103,300 gallons of diesel fuel oil. Actually, 'each diesel generator has its own independent seven-day fuel oil storage tank assembly. The diesel fuel oil system has the capability to transfer fuel oil from the yard tank to the seven-day tank assemblies and between the seven-day tank assemblies for each set of diesel generators. However, this transfer system is not seismically qualified; therefore, each diesel generator seven-day fuel tank assembly must contain enough fuel oil to operate the associated diesel generator
The test during refueling outages is more comprehensive, including procedures that are most effectively conducted at that time.These include automatic actuation and functional capability tests to verify that the generators can start and be ready to assume load in 10 seconds.The annual inspection will detect any.signs of wear long before failure.BFN tests the 7-'day diesel generator fuel oil supplies'in accordance with Table 1 of ASTM-D975-89.
    ,for'even days. Regulatory Guide 1.137, Fuel Oil Systems for Standby Diesel Generators, requires an adequate fuel supply for operation-of the diesel engines during the maximum expected time interval between replenishment.
Each fuel oil supply is tested quarterly.
Battery maintenance with regard to the floating charge, equalizing charge, and electrolyte level will be based on the manufacturer's instruction and sound maintenance practices.
In addition, written records will be maintained of the battery performance.
The plant batteries will deteriorate with time but precipitous failure is unlikely.The type of surveillance called for.in this specification is that which has been demonstrated through experience to provide an indication of a cell becoming irregular or unserviceable long before it becomes a failure.The equalizing charge, as recommended by the manufacturer, is vital to maintaining the ampere-hour capacity of the battery and will be applied as recommended.
The testing of the logic system will verify the ability of the logic systems to bring the auxiliary electrical system.to running standby readiness with the presence of an accident signal from any reactor or an undervoltage signal on the start buses or 4-kV shutdown boards.The periodic simulation of accident signals in conjunction with diesel generator voltage available signals will confirm the ability of the'80-V load shedding logic system to sequentially shed and restart 480-V loads if an accident signal were present, and diesel generator voltage were the only source of electrical power.BFN.Unit 3 3.9/4.9-20 4 v 4,9 Refere ces 1.Normal Auxiliary, Power System (BFNP FSAR Subsection 8.4)2.Standby AC Power Supply and Distribution (BFNP FSAR Subsection 8.5)3.250-V DC Power Supply and Distribution (BFNP FSAR Subsection 8.6)4.Memorandum from'G.M.Wilhoite to H.J.Green dated December 4, 1981 (LOO 811208 664)and memorandum from C.E.Winn to H.J.Green dated January 10, 1983 (G02 830112 002)BFN Unit 3~/3.9/4.9-21 AMENoMBr NG.I pC  The diesel generator fuel oil system for each unit includes a day tank mounted on the diesel engine skid and a seven-day tank assembly embedded in the diesel generator building floor.Transfer between the seven-day tank assembly and the day tank is accomplished automatically by transfer pumps controlled by float operated switches which sense fuel oil level in the day tank.New fuel oil added to the seven-day tank assembly is tested in accordance with plant procedures.
In addition, the auxiliary boiler reservoirs may be used as a long-term backup fuel oil supply.These reservoirs are sampled quarterly and fuel oil is not allowed to be transferred to the seven-day tank assemblies until the quality is verified to be acceptable per ASTM-D975, Table l.>>The BFN surveillance requirements are being revised to specify that the fuel oil supply for each diesel generator is tested quarterly.
This change is consistent with standard industry fuel oil sampling practices, regulatory guidelines, and the GE standard TSs.The bases section is being revised to state that BFN tests each seven-day fuel oil supply in accordance with Table 1 of ASTM-D975-89 quarterly.
4.Existing LCO 3.9.A.6 currently reads: There shall be a minimum of 103,300 gallons of diesel fuel in the standby diesel-generator fuel tanks.Proposed change to LCO 3.9.A.6.would read: There shall be a minimum of 35,280 gallons of diesel fuel in each of the seven-day diesel generator fuel tank assemblies.
Justification for LCO 3.9.A.6 This specification is being changed to'require that there be a minimum of 35,280 ga'lions of diesel fuel in each of the diesel generator seven-day fuel tank assemblies.
This change is made to clarify the nature of the diesel generator fuel oil storage system and make it applicable to each diesel generator.
e At BFN there are two sets of four diesel generators (Unit 1 and 2 diesel generators A, B, C, and D;and Unit 3 diesel generators 3A, 3B, 3C, and ,3D).The current technical specifications imply the existence of one large fuel storage tank for each set of diesel generators and that this tank will be required to contain at least 103,300 gallons of diesel fuel oil.Actually,'each diesel generator has its own independent seven-day fuel oil storage tank assembly.The diesel fuel oil system has the capability to transfer fuel oil from the yard tank to the seven-day tank assemblies and between the seven-day tank assemblies for each set of diesel generators.
However, this transfer system is not seismically qualified; therefore, each diesel generator seven-day fuel tank assembly must contain enough fuel oil to operate the associated diesel generator ,for'even days.Regulatory Guide 1.137, Fuel Oil Systems for Standby Diesel Generators, requires an adequate fuel supply for operation-of the diesel engines during the maximum expected time interval between replenishment.
0391k/27}}
0391k/27}}

Latest revision as of 15:46, 3 February 2020

Proposed Changes to Tech Spec Bases Section 4.9 Indicating That Diesel Generator Fuel Oil Tested in Accordance W/ Table 1 of ASTM-D975-89
ML18033B301
Person / Time
Site: Browns Ferry  Tennessee Valley Authority icon.png
Issue date: 05/14/1990
From:
TENNESSEE VALLEY AUTHORITY
To:
Shared Package
ML18033B300 List:
References
NUDOCS 9005170261
Download: ML18033B301 (29)


Text

Enclosure Revisions To TVA BFN TS 277 Browns Ferry Nuclear Plant Units l, 2, and 3 9005170261 900514 PDR ADOCK 05000259 P PDC

UNIT 1 EFFECTIVE PAGE LIST REMOVE INSERT 3.9/4.9-1 3.9/4.9-1 3.9/4.9-2 3.9/4.9-2*

3.9/4.9-3 3.9/4.9-3*

3.9/4.9-4 3.9/4.9 4+

3.9/4.9-21 3.9/4.9-21 3.9/4.9-22 3.9/4.9.-22*

  • Denotes overleaf or spillover page.
3. 4. AUXILIARYELEC RICAL SYSTEM LIMITING CONDITIONS FOR OPERATION SURVEILLANCE REQUIREMENTS 3.9 Auxil a ectrica S ste 4.9 Aux a Electrical S stem licab Applies to all the auxiliary Applies to the periodic electrical power system. testing requirements of the e

auxiliary electrical system.

Ob ective ~Ob ective To assure an adequate supply of Verify the .operability of the electrical power for operation of auxiliary electrical system.

those systems required for safety.

S ecification S ecification A. Auxi ia Electrical E ui ment A. Auxilia Electrical S stem

1. PRIOR TO STARTUP from a Diesel Generators COLD CONDITION, the follow-ing must be satisfied: a. Each diesel generator shall be manually
a. Diesel generators A, started and loaded to B, C, and demonstrate operational D OPERABLE.

readiness in accordance

b. Requirements 3.9.A.3 with the frequency through 3.9.A.6 are specified in Table 4.9.A met. on a staggered test basis. The test shall
c. At least two of the continue for at least a following offsite power one-hour period at 100%

sources are available: or greater of the con-tinuous rating of the (1) The 500-kV.system diesel generator, and is available to the the operation of the units 1 and 2 shut- diesel fuel oil trans-down boards through fer pumps shall be the unit 1 station- demonstrated. Also, service transformer the diesel generator TUSS/1B with no starting air compressor credit taken for shall be checked for the two 500-kV operation and its Trinity lines. If ability to recharge the unit 2 station- air receivers.

service transformer is the second Once per 18 months, choice, a minimum each diesel generator of two 500-kV lines. will be tested at a load must be available. of at least 2800 KW to demonstrate full load carrying capability for

'FN "3.9/4.9-1 Unit 1

4 AUXILIARYELECTRICAL S STE LIMITING CONDITIONS FOR OPERATION SURVEILLANCE REQUIREMENTS 3.9.A. uxilia Electrical E ui ment 4.9.A. Auxilia Electrical S ste 3.9.A.l.c. (Cont'd) 4.9.A.l.a. (Cont'd)

(2) The 500-kV system is an interval of not less available to the units 1 than 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br />.

and 2 shutdown boards through the unit 2 The diesel generator .

station-service fast starts (10 seconds) transformer TUSS 2B with from standby conditions no credit taken for the shall be performed once two 500-kV Trinity lines. per 184 days in these If the unit 1 station- surveillance tests. All other engine starts for service transformer is the second choice, a minimum the purpose of this test of two 500-kV lines must may be preceeded by an be available. engine idle start.

(3) The Trinity 161-kV line is Additional reporting available to the units' requirements due to and 2 shutdown boards failures are noted in through both common Table 4.9.A.

station-service transformers. All diesel generator starts shall be logged.

Notes for (3): b. Once per operating cycle, a test will be (a) If unit 3 is claiming conducted simulating a the Trinity line as an loss of offsite power offsite source, see and similar conditions unit '3 technical that would- exist with specifications, Section the presence of an 3.9.A.l.c.2. actual safety-injection signal to demonstrate (b) If unit 1 is in cold the following:

shutdown, only one common station-service (1) Deenergization o f the transformer is required. emergency buses and load shedding from the emergency buses.

(2) The diesel starts from ambient condition on the auto-start signal, energizes the emergency buses with permanently connected loads, energizes the auto-connected emer-gency loads through BFN 3.9/4.9-2

.Unit 1

LIMITING CONDITIONS FOR OPERATION SURVEILLANCE REQUIREMENTS 3.9.A. Auxilia E ectrical E ui ment 4.9.A. Auxilia Electrical S stem 3.9.A.l.c. (Cont'd) 4.9.A.l.b (Cont'd)

(4) The Athens 161-kV line is available to the units 1 load sequencing, and and 2 shutdown boards operates for greater through a common than or equal to five station-service minutes while its gener-transformer when unit* 1 is ator is loaded with the in Cold Shutdown and unit 3 emergency loads.

is not claiming the Athens line as an offsite source. (3) On diesel generator breaker trip, the loads NOTE FOR (3) AND (4): are shed from the emer-gency buses and the diesel With no cooling tower pumps output breaker recloses or fans running, a cooling on the auto-start signal, to~er transformer may be the emergency buses are substituted for a common energized with permanently station-service transformer. connected loads, the auto-connected emergency loads are energized through load sequencing, and the diesel operates for gre'ater than or equal to five minutes while its generator is loaded with the emergency loads.

c. Once a month the quantity of diesel fuel available shall be logged.
d. Each diesel generator shall be given an annual inspec-tion in accordance with instructions based on the manufacturer's recommendations.
e. Quarterly the qual'ity of each diesel generator's (A, B, C, and D) seven-day fuel supply shall be checked. The fuel oil quality shall be within the acceptable limits specified in Table 1 of ASTM-D975.

BFN 3.9/4.9-3 Unit 1

4 AUXILIARYELECTRICAL SYSTEM LIMITING CONDITIONS FOR OPERATION SURVEILLANCE REQUIREMENTS 3.9.A. Auxilia Electrical E ui ment 4.9.A. Auxilia Electrical S stem

2. The reactor shall not be 2~ DC Power System Unit started up (made critical) Batteries (250-V), Diesel-from the HOT STANDBY CONDITION Generator Batteries (125-V) unless all of the following and Shutdown Board Batteries conditions are satisfied: (250-V)
a. At least one offsite power a. Every week the specific source is'" available as gravity, voltage and specified in 3.9.A.l.c. temperature of the pilot cell and overall battery voltage shall be measured and logged.
b. Three units .1 and 2 diesel b. Every three months the generators shall be measurement shall be made OPERABLE. of voltage of each cell to nearest O.l volt, specific gravity of each cell, and temperature of every fifth cell. These measurements shall be

~

logged.

c. An additional source of c. At least once every 24 power consisting of one months, a battery rated of the following: ~ discharge (capacity) test shall be performed (1) A second offsite and the voltage, time, power source available and output current as specified in measurements shall 3.9.A.l.c. be logged.

(2) A fourth OPERABLE units 1 and 2 diesel generator.

d. Requirements 3.9.A.3 through 3.9.A.6 are met.

BFN 3.9/4.9-4 AMENDMENT go yg8

.Unit 1

4.9 BASES (Cont'd)

The monthly test of the diesel generators -is primarily to check for failures and deterioration in the system since last use. The diesels will be loaded to at least 100 percent of its continuous rating (i.e., g 2600 KW) while engine and generator temperatures are stabilized (about one hour). ,A minimum 75-percent load will prevent soot formation in the cylinders and injection nozzles. Operation up to an equilibrium temperature ensures that there is no overheating problem. The tests also provide an engine and generator operating history to be compared with subsequent engine-generator test data to identify and to correct any mechanical or electrical deficiency before it can result in a system failure. 1 Diesel testing once per 18 months (i.e., at least once per fuel cycle) at a minimum load of 2800 KW for an interval of not less than 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br />, assures that each diesel generator will be capable of supplying the maximum load during the first 2 hours2.314815e-5 days <br />5.555556e-4 hours <br />3.306878e-6 weeks <br />7.61e-7 months <br /> of a loss of offsite power/loss of coolant accident. This test also demonstrates each diesel generator's long-term load carrying capability.

The test during refueling outages is more comprehensive, including procedures that are most effectively conducted at that time. These include automatic actuation and functional capability tests to verify that the generators can"start and be ready to assume load in 10 seconds. The annual inspection will detect any signs of wear long before failure.

'BFN tests the 7-day diesel generator fuel oil supplies in accordance with Table 1 of ASTM-D975-89. Each fuel oil supply is tested quarterly.

Battery maintenance with regard to the floating charge, equalizing charge, and electrolyte level will be based on the manufacturer's instruction and sound maintenance practices. Xn addition, written records will be maintained of the battery performance. The plant batteries will deteriorate with time but precipitous failure is unlikely. The type of surveillance called for in this specification is that which has been demonstrated through experience to provide an indication of a cell becoming irregular or unserviceable long before it becomes a failure.

The equalizing charge, as recommended by the manufacturer, is vital to maintaining the ampere-hour capacity of the battery and will be applied as recommended.

The testing of the logic systems will verify the ability of the logic systems to bring the auxiliary electrical system to running standby readiness with the presence of an accident signal from any reactor or an undervoltage signal on the 4-kV shutdown boards.

The periodic simulation of accident signals in conjunction with diesel generator voltage available signals will confirm the ability of the 480-V load shedding logic system to sequentially shed and restart 480-V loads if an accident signal were present, and diesel generator voltage was the only source of electrical power.

BFN

,Unit 1

4.9 BASES (Cont'd)

REFERENCES

1. Normal Auxiliary Power System (BFNP FSAR Subsection 8.4)
2. Standby AC Power Supply and Distribution (BFNP FSAR Subsection 8.5)
3. 250-V DC Power Supply and Distribution (BFNP FSAR Subsection 8.6)
4. Memorandum from Gene M. Wilhoite to H. J. Green dated December 4, 1981 (LOO 811208 664) and memorandum from C. E. Winn to H. J. Green dated January 10, 1983 (G02 830112 002)

~

'FN MIBDMEHTNO. y gg 3.9/4.9-22 Unit 1

UNIT 2 EFFECTIVE PAGE LIST REMOVE INSERT 3.9/4.9-1 3.9/4.9-1 3.9/4.9-2 3.9/4.9-2*

3.9/4.9-3 3.9/4.9-3*

3.9/4.9-4 3.9/4.9 4+

3.9/4.9-21 3.9/4.9-21 3.9/4.9-22 3.9/4.9-22*

  • Denotes overleaf or spillover page.

4 AUXIL ARY ELECTRICAL SYS EM LIMITING CONDITIONS FOR OPERATION SURVEILLANCE REQUIREMENTS 3.9 ILIARY ELECTRICAL SYS E 4.9 AUXILIARYELEC R CAL SYSTEM A 1 cabi it A icab t Applies to all the auxiliary Applies to the periodic electrical power system. testing requirements of the auxiliary electrical system.

Ob ective Ob ective To assure an adequate supply of Verify the operability of the electrical power for operation of auxiliary electrical system.

those systems required for safety.

S ecification S ecification A. uxi ia Electrica F. ui ment A. uxilia Electrical S stem

1. PRIOR TO STARTUP from a 1. Diesel Generators COLD CONDITION, the follow-ing must be satisfied:
a. Each diesel generator
a. Diesel generators A, shall be manually B, C, and D OPERABLE. . started and loaded to demonstrate operational
b. Requirements 3.9.A.3 readiness in accordance through 3.9.A.6 are with the frequency met. specified in Table 4.9.A on a staggered
c. At least two of the test basis. The test following offsite power shall continue for at sources are available: least a one-hour period at 100% or greater of (1) The 500-kV system the continuous rating is available to the of the diesel generator, units 1 and 2 shut- and the operation of down boards through the diesel fuel oil the unit 1 station- transfer pumps shall service transformer be demonstrated. Also TUSS 1B with no the di'esel generator credit taken for starting air compressor the two 500-kV shall be checked for Trinity lines. I f operation and its the unit 2 station- ability to recharge service transformer air receivers.

is the second sourc'e, a minimum Once per 18 months, each of two 500-kV lines diesel generator will must be available. be tested at a load of at least 2800 KW to demonstrate full load carrying capability for BFN 3.9/4.9-1

,. Unit 2

/4 AUXILIARYELECTR CAL SYS EM LIMITING CONDITIONS FOR OPERATION SURVEILLANCE REQUIREMENTS 3.9.A. Auxilia Electr cal E ui ment 4.9.A. Auxilia E ect ica S ste 3.9.A.l.c. (Cont'd) 4.9.A.l.a. (Cont'd)

(2) The 500 kV system is an interval of not less available to the units 1 than 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br />.

and 2 shutdown boards through the unit 2 The diesel generator station-service fast starts (10 seconds) transformer TUSS 2B with from standby conditions no credit taken for the shall be performed once two 500-kV Trinity lines. per 184 days in these

.If the unit 1 station- surveillance tests. All service transformer is the other engine starts for second choice, a minimum the purpose of this test of two 500-kV lines must may be preceeded by an be available. engine idle'start.

(3) The Trinity 161-kV line is Additional reporting available to the units 1 requirements due to and 2 shutdown boards failures are noted in through both common Table 4.9.A.

station-service transformers. . All diesel generator starts shall be logged.

NOTES FOR (3):

b. Once per operating (a) If unit 3 is claiming cycle, a test. will be the Trinity line as an conducted simulating a offsite source, see loss of offsite power unit 3 technical and similar conditions specifications, Section that would exist with 3.9.A.l.c.2. the presence of an actual safety-injection (b) If unit 1 is in- cold signal to demonstrate the following:

shutdown, only one common station-service transformer is required. (1) Deenergization of the emergency buses and load shedding from the emergency buses.

(2) The diesel starts from ambient con-dition on the auto-start signal, energizes the emer-gency buses with permanently connec-ted loads, energizes the auto-connected BFN 3.9/4.9-2 Unit 2

4 AUXIL ARY ELEC R CAL SYSTEM LIMITING CONDITIONS FOR OPERATION SURVEILLANCE REQUIREMENTS 3.9.A. Auxilia Electrical E ui ment 4.9.A. Auxilia Electrica S stem 3.9.A.l.c. (Cont'd) 4.9.A.l.b. (Cont'd) emergency loads through load sequencing, and operates for greater than or equal to five minutes while its generator is loaded with the emergency loads.

(4) The Athens 161-kV line is (3) On diesel generator available to the units 1 breaker trip, the and 2 shutdown boards loads are shed from through a common the emergency buses station-service and the diesel output transformer when unit 1 is breaker recloses on in Cold Shutdown and unit 3 the .auto-start signal, is not. claiming the Athens the emergency buses line as an offsite source. are energized with permanently connected NOTE FOR (3) AND (4): ~

loads, the auto-connected emergency With no cooling tower pumps loads are energized or fans running, a cooling through load tower transformer may be sequencing, and the substituted for a common diesel operates for station-service transformer. greater than or equal to five minutes while its generator is loaded with the emergency loads.

c. Once a month the quantity of diesel fuel available shall be logged.
d. Each diesel generator shall be given an annual inspec-tion in accordance with instructions based on the manufacturer's recommendations.
e. Quarterly the quality of each diesel generator's (A, B, C, and D) seven-day fuel supply shall be checked. The fuel oil quality shall be within the acceptable limits speci-fied in Table 1 of ASTM-D975.

BFN 3.9/4.9-3

.:Unit 2

4. AUXILIARYELEC AL SYSTE LIMITING CONDITIONS FOR OPERATION SURVEILLANCE REQUIREMENTS 3;9.A. Auxilia Electrical E ui ment 4.9.A. Auxilia Electrical S stem
2. The reactor shall not be 2; DC Power System Unit started up (made critical) Batteries (250-V), Diesel-from the HOT STANDBY CONDITION Generator Batteries (125-V) unless all of the following and Shutdown Board Batteries conditions are satisfied: (250-V)
a. At least one offsite power a. Every week the specific source is available as gravity, voltage and specified in 3.9.A.l.c. temperature of the pilot cell and overall battery voltage shall be measured and logged.
b. Three units 1 and 2 diesel b. Every three months the generators shall be measurement shall be made'f OPERABLE. voltage of each cell to nearest 0.1 volt, specific gravity of each

~

cell, and temperature of every fifth cell. These measurements shall be logged.

c. An additional source of c. At least once every 24 power consisting of one 'months, a battery rated of the following: discharge (capacity) test shall be performed (1) A second offsite and the voltage, time, power source available and output current as specified in measurements shall 3.9.A.l.c. be logged.

(2) A fourth OPERABLE units 1 and 2 diesel generator.

d. Requirements 3.9.A.3 through 3.9.A.6 are met.

BFN 3.9/4.9-4 AMPHORA'5 NP gg$

,Unit 2

4.9 BASES (Cont'd)

The monthly tests of the diesel generators are primarily to check for failures and deterioration in the system since last use. The diesels will be loaded to at least 100 percent of its continuous rating (i.e., g 2600 KW) while engine and generator temperatures are stabilized (about one hour). A minimum 75-percent load will prevent soot formation in the cylinders and injection nozzles. Operation up to an equilibrium temperature ensures that there is no overheating problem. The tests also provide an engine and generator operating history to be compared with .subsequent engine-generator test data to identify and to correct any mechanical or electrical deficiency before it can result in a system failure.

Diesel testing once per 18 months (i.e., at least once per fuel cycle).

at a minimum load of 2800 KW for an interval of not less than 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br /> assures that each diesel generator will be capable of supplying the maximum load during the first 2 hours2.314815e-5 days <br />5.555556e-4 hours <br />3.306878e-6 weeks <br />7.61e-7 months <br /> of a loss of offsite power/loss of coolant accident. This test also demonstrates each diesel generator's long-term load carrying capability.

The test during refueling outages is more comprehensive, including procedures that are most effectively conducted at that time. These include automatic actuation and functional capability tests to verify that the generators can start and be ready to assume load in 10 seconds. The annual inspection will detect any signs of wear long before failure. The. diesel generators are shared by units 1 and 2.

Therefore, the capability for the units 1 and 2 diesel generators to accept the emergency loads will be performed during the unit 1 operating cycle using the unit 1 loads.

BFN tests the 7-day diesel generator fuel oil supplies=in accordance with Table 1 of ASTM-D975-89. Each fuel oil supply is tested quarterly.

Battery maintenance with regard to the floating charge, equalizing =

charge, and electrolyte level will be based on the manufacturer's instruction and sound maintenance practices. In addition, written records will be maintained of the battery performance. The plant batteries will deteriorate with time but precipitous failure is unlikely.. The type of surveillance called for in this specification is that which has been demonstrated through experience to provide an indication of a cell becoming irregular or unserviceable long before it becomes a failure.

The equalizing charge, as recommended by the manufacturer, is vital to maintaining the ampere-hour capacity of the battery and will be applied as recommended.

The testing of the logic systems will verify the ability of the logic systems to bring the auxiliary electrical system to running standby readiness with the presence of an accident signal from any reactor or an undervoltage signal on the 4-kV shutdown boards.

BFN 3.9/4."9-21 Unit 2

4.9 BASES (Cont'd)

The'eriodic simulation of accident signals in conjunction with diesel generator voltage available signals will confirm the ability of the 480-V load shedding logic system to sequentially shed and restart 480-V loads if an accident signal were present, and diesel generator voltage were the only source of electrical power.

I REFERENCES

1. Normal Auxiliary Power System (BFNP FSAR Subsection 8.4)
2. Standby AC Power Supply and Distribution (BFNP FSAR Subsection 8.5)
3. 250-V DC Power Supply and Distribution (BFNP FSAR Subsection 8.6)
4. Memorandum from Gene M. Wilhoite to H. J. Green dated December 4, 1981 (LOO 811208 664) and memorandum from C. E. Winn. to H. J. Green dated January 10, 1983 (G02 830112 002)

BFN Unit 2 3 9/4 9-22

~ AMENDMENTNO.

I4 9

UNIT 3 EFFECTIVE PAGE LIST REMOVE INSERT 3.9/4.9-1 3.9/4.9-1 3.9/4.9-2 3.9/4.9-2*

3.9/4.9-3 3.9/4.9-3*

3.9/4.9-4 3.9/4.9 4*

3.9/4.9-20 3.9/4.9-20 3.9/4.9-21 3.9/4.9-21*

  • Denotes overleaf or spillover page.
4. AUXILIARYELECTRICAL S STEM LIMITING CONDITIONS FOR OPERATION SURVEILLANCE REQUIREMENTS 3.9 Auxiliar Electrical S st 4.9 Auxilia E ectr cal S stem A licabi it A licabilit Applies to all the auxiliary Applies to the periodic electrical power system. testing requirements of the auxiliary electrical system.

Ob ective ~Ob ective To assure an adequate supply of Verify the operability of the electrical power'or operation of auxiliary electrical system.

those systems required for safety.

S ecification S ecification A. u ilia Electrica .E ui ment A. Aux lia Electrica S stem

1. PRIOR TO STARTUP from a COLD 1. Diesel Generators CONDITION, the following must be satisfied:
a. Each diesel generator
a. Diesel generators 3A, shall be manually 3B, 3C, and 3D OPERABLE. ~

, started and loaded to demonstrate operational

b. Requirements 3.9.A.3 readiness in accordance'ith through 3.9.A.6 are the frequency met. specified in Table 4.9.A on a staggered
c. At least two of the test basis. The test following offsite power shall continue for at sources'are available: least a one-hour period at 100% or greater of (1) The 500-kV system the continuous rating is available to the of the diesel gener-unit 3 shutdown ator, and the operation boards through the of the diesel fuel oil unit 3 station- transfer pumps shall service transformer be demonstrated. Also, TUSS 3B with no the diesel generator credit taken for starting air compressor the two 500-kV shall be checked for Trinity lines. operation and its ability to recharge air receivers.

Once per 18 months, each diesel generator will be tested at a load of at least 2800 KW to demonstrate full load carrying capability BFN 3.9/4.9-1

,Unit 3

4 AUX LIARY ELEC CAL SYS E LIMITING CONDITIONS FOR OPERATION SURVEILLANCE REQUIREMENTS 3.9.A. Auxi a Electrical E ui ment 4.9.A. Auxilia Electrical S stem 3.9.A.l.c. (Cont'd) 4.9.A.l.a. (Cont'd)

(2) The Trinity 161-kV line for.an interval of not is available to the less than 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br />.

unit 3 shutdown boards through a common The diesel generator fast station-servt.ce or starts (10 seconds) from cooling tower standby conditions shall

.'ransformer. be performed once per 184 days in these surveil-NOTE FOR (2): lance tests. All other engine starts for the If units 1 and 2 are purpose of this test may both in operation and be preceeded by an engine claiming the Trinity idle start.

'All line as an offsite source, TUSS 3B must Additional reporting be claimed as the other requirements due to offsite source for failures are noted in unit 3. Table 4.9.A.

(3) The Athens 161-kV line diesel generator is available to unit 3 .starts shall be logged.

shutdown boards through a common station-service b. Once per operating or cooling tower cycle, a test will be transformer. conducted simulating a loss of offsite power and NOTE FOR (3): similar conditions that would exist with the If either unit 1 or presence of an actual safety-injection signal unit 2 is claiming the Athens line as an to demonstrate the offsite source, it may following:

not be claimed as an offsite source for (1) Deenergization of the unit 3. emergency buses and load shedding from the emergency buses.

(2) The diesel starts from ambient con-dition on the auto-start signal, ener-gizes the emergency buses with perman-ently connected lo'ads, energizes the auto-connected emergency loads BFN 3.9/4.9-2

,rUnit 3

4 AUXILIARYELEC R C L SYSTE LIMITING,CONDITIONS FOR OPERATION SURVEILLANCE REQUIREMENTS tern 3.9.A.. Auxilia Electr ca 4.9.A. A a Elect ca gcLuuimerr t '~Ss 3.9.A.l.c.(3) (Cont'd) 4.9.A.l.b. (Cont'd) through load sequencing, and operates for greater than or equal to five minutes while its gener-ator is loaded with NOTES FOR (2) AND (3): the emergency loads.

If both Athens and (3) On diesel generator breaker trip, the Trinity lines are claimed as the two loads are shed from offsite sources for the emergency buses unit "3, no credit may and the diesel output be taken for'he breaker closes on the Athens-Trinity line auto=start signal, the tie breaker. emergency buses are Specifically, the energized with Athens line supplies permanently connected unit 3 through common loads, the auto-station-service connected emergency transformer A or loads're energized cooling tower through load transformer 1, and sequencing, and the the Trinity line diesel operates for must supply unit 3 greater than or equal through common station- to five minutes while service transformer B or its generator is cooling tower loaded with the transformer 2. emergency loads".

c. Once a month the quantity of diesel fuel available shall be loggede
d. Each diesel generator shall be given an annual inspection'n accordance with instructions based on the manufacturer's recommendations.
e. Quarterly the quality of each diesel generator's (3A; 3B, 3C, and 3D) seven-day fuel load.

supply, shall be checked. The fuel oil quality shall be'ithin the acceptable limits specified in'Table 1 of ASTM-D975.

BFN 3.9/4.9-3 Unit 3

4 AUXILIARYELE CAL SYSTEM LIMITING CONDITIONS FOR OPERATION SURVEILLANCE REQUIREMENTS 3.9.A. Aux ia Elect ica E ui e t 4.9.A. Aux ia Electrical

~Sseem

2. The reactor shall not be 2~ DC Power S ste Unit started up (made critical) Batteries (250-V),

from the HOT STANDBY CONDITION Diesel-Generator unless all of the following Batteries (125-V)and conditions are satisfied: Shutdown Board Batteries'250-V)

a. At least one offsite power a. Every week the source is available as specific gravity, specified in 3.9.A.l.c. voltage, and temperature of the pilot cell, and overall battery voltage shall be measured and logged.
b. Three units 3 diesel b. Every three months generators shall be the measurements OPERABLE. shall be made of voltage of each cell to nearest 0.1 volt, specific gravity of each cell, and temperature of every

'fifth cell. These measurements shall be logged.

c. An additional source of c. At least once every power consisting of one'f 24 months, a battery the following: rated discharge (capacity) test (1) A second offsite shall be performed power source available and the voltage, as specified in time, and output 3.9.A.l.c. current measurements shall be logged.

(2) A fourth unit 3 diesel generator OPERABLE.

d. Requirements 3.9.A.3 through 3.9.Ae6 are met.

'AMENDMENT NO. g, p 9 BFN 3.9/4.9-4

.Unit 3

4.9 BASES (Cont'd)

The monthly tests of the diesel generators are primarily to check for, failures and deterioration in the system since last use. The diesels will be loaded to at least 100 percent of its continuous rating (i.e. g 2600 KW) while engine and generator temperatur'es are stabilized (about

~one hour). A minimum 75-percent load will prevent soot formation in the cylinders and injection nozzles. Operation up to an equilibrium temperature ensures that there is no overheating problem. The tests also provide an engine and generator operating history to be compared with subsequent engine-generator test data to identify and to correct any mechanical or electrical deficiency before it can result in a system failure.

Diesel testing once per 18 months (i.e., at least once per fuel cycle) at, a. minimum'load of 2800 KW for an interval of not less. than 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br /> assu'res that each diesel generator will be capable of supplying the maximum load during the first 2 hours2.314815e-5 days <br />5.555556e-4 hours <br />3.306878e-6 weeks <br />7.61e-7 months <br /> of a loss of offsite power/loss of coolant accident. This test also demonstrates each diesel generator's long-term load carrying capability.

The test during refueling outages is more comprehensive, including procedures that are most effectively conducted at that time. These include automatic actuation and functional capability tests to verify that the generators can start and be ready to assume load in 10 seconds. The annual inspection will detect any. signs of wear long before failure.

BFN tests the 7-'day diesel generator fuel oil supplies 'in accordance with Table 1 of ASTM-D975-89. Each fuel oil supply is tested quarterly.

Battery maintenance with regard to the floating charge, equalizing charge, and electrolyte level will be based on the manufacturer's instruction and sound maintenance practices. In addition, written records will be maintained of the battery performance. The plant batteries will deteriorate with time but precipitous failure is unlikely. The type of surveillance called for .in this specification is that which has been demonstrated through experience to provide an indication of a cell becoming irregular or unserviceable long before it becomes a failure.

The equalizing charge, as recommended by the manufacturer, is vital to maintaining the ampere-hour capacity of the battery and will be applied as recommended.

The testing of the logic system will verify the ability of the logic systems to bring the auxiliary electrical system. to running standby readiness with the presence of an accident signal from any reactor or an undervoltage signal on the start buses or 4-kV shutdown boards.

The periodic simulation of accident signals in conjunction with diesel generator voltage available signals will confirm the ability of the

'80-V load shedding logic system to sequentially shed and restart 480-V loads if an accident signal were present, and diesel generator voltage were the only source of electrical power.

BFN 3.9/4.9-20

.Unit 3

4 v 4,9 Refere ces

1. Normal Auxiliary,Power System (BFNP FSAR Subsection 8.4)
2. Standby AC Power Supply and Distribution (BFNP FSAR Subsection 8.5)
3. 250-V DC Power Supply and Distribution (BFNP FSAR Subsection 8.6)
4. Memorandum from 'G. M. Wilhoite to H. J. Green dated December 4, 1981 (LOO 811208 664) and memorandum from C. E. Winn to H. J. Green dated January 10, 1983 (G02 830112 002)

BFN 3.9/4.9-21 AMENoMBr NG. I pC

~ / Unit 3

The diesel generator fuel oil system for each unit includes a day tank mounted on the diesel engine skid and a seven-day tank assembly embedded in the diesel generator building floor. Transfer between the seven-day tank assembly and the day tank is accomplished automatically by transfer pumps controlled by float operated switches which sense fuel oil level in the day tank. New fuel oil added to the seven-day tank assembly is tested in accordance with plant procedures. In addition, the auxiliary boiler reservoirs may be used as a long-term backup fuel oil supply. These reservoirs are sampled quarterly and fuel oil is not allowed to be transferred to the seven-day tank assemblies until the quality is verified to be acceptable per ASTM-D975, Table l.>>

The BFN surveillance requirements are being revised to specify that the fuel oil supply for each diesel generator is tested quarterly. This change is consistent with standard industry fuel oil sampling practices, regulatory guidelines, and the GE standard TSs. The bases section is being revised to state that BFN tests each seven-day fuel oil supply in accordance with Table 1 of ASTM-D975-89 quarterly.

4. Existing LCO 3.9.A.6 currently reads:

There shall be a minimum of 103,300 gallons of diesel fuel in the standby diesel-generator fuel tanks.

Proposed change to LCO 3.9.A.6 .would read:

There shall be a minimum of 35,280 gallons of diesel fuel in each of the seven-day diesel generator fuel tank assemblies.

Justification for LCO 3.9.A.6 This specification is being changed to'require that there be a minimum of 35,280 ga'lions of diesel fuel in each of the diesel generator seven-day fuel tank assemblies. This change is made to clarify the nature of the diesel generator fuel oil storage system and make it applicable to each diesel generator. e At BFN there are two sets of four diesel generators (Unit 1 and 2 diesel generators A, B, C, and D; and Unit 3 diesel generators 3A, 3B, 3C, and

,3D). The current technical specifications imply the existence of one large fuel storage tank for each set of diesel generators and that this tank will be required to contain at least 103,300 gallons of diesel fuel oil. Actually, 'each diesel generator has its own independent seven-day fuel oil storage tank assembly. The diesel fuel oil system has the capability to transfer fuel oil from the yard tank to the seven-day tank assemblies and between the seven-day tank assemblies for each set of diesel generators. However, this transfer system is not seismically qualified; therefore, each diesel generator seven-day fuel tank assembly must contain enough fuel oil to operate the associated diesel generator

,for'even days. Regulatory Guide 1.137, Fuel Oil Systems for Standby Diesel Generators, requires an adequate fuel supply for operation-of the diesel engines during the maximum expected time interval between replenishment.

0391k/27