1CAN030901, License Amendment Request on Technical Specification Change to Delete Low Pressurizer Level Limit: Difference between revisions

From kanterella
Jump to navigation Jump to search
(Created page by program invented by StriderTol)
 
(Created page by program invented by StriderTol)
Line 3: Line 3:
| issue date = 03/10/2009
| issue date = 03/10/2009
| title = License Amendment Request on Technical Specification Change to Delete Low Pressurizer Level Limit
| title = License Amendment Request on Technical Specification Change to Delete Low Pressurizer Level Limit
| author name = Mitchell T G
| author name = Mitchell T
| author affiliation = Entergy Operations, Inc
| author affiliation = Entergy Operations, Inc
| addressee name =  
| addressee name =  
Line 14: Line 14:
| page count = 12
| page count = 12
| project =  
| project =  
| stage = Other
| stage = Request
}}
}}


Line 115: Line 115:
March 10, 2009.  
March 10, 2009.  


Sincerely, TGM/dbb Attachments:  
Sincerely, TGM/dbb Attachments:
: 1. Analysis of Proposed Technical Specification Change  
: 1. Analysis of Proposed Technical Specification Change
: 2. Proposed Technical Specification Changes (mark-up)  
: 2. Proposed Technical Specification Changes (mark-up)  


Line 255: Line 255:
meet the criteria of 10 CFR 50.36 for inclusion in the TSs. An evaluation of the 10 CFR 50.36  
meet the criteria of 10 CFR 50.36 for inclusion in the TSs. An evaluation of the 10 CFR 50.36  


criteria is included below.  
criteria is included below.
: 1. The minimum Pressurizer level limit is not installed instrumentation that is used to detect, and indicate in the control room, a significant abnormal degradation of the reactor coolant  
: 1. The minimum Pressurizer level limit is not installed instrumentation that is used to detect, and indicate in the control room, a significant abnormal degradation of the reactor coolant  


Line 268: Line 268:
function. As discussed above, automatic or manual action is taken for any deviation in Pressure level, well in advance of level reaching a point where indication would be off-
function. As discussed above, automatic or manual action is taken for any deviation in Pressure level, well in advance of level reaching a point where indication would be off-


scale. Therefore, the minimum Pressurizer level limit does not satisfy Criterion 1.  
scale. Therefore, the minimum Pressurizer level limit does not satisfy Criterion 1.
: 2. The minimum Pressurizer level limit is not a process variable, design feature, or operating restriction that is an initial condition of a DBA or transient analysis that either  
: 2. The minimum Pressurizer level limit is not a process variable, design feature, or operating restriction that is an initial condition of a DBA or transient analysis that either  


Line 275: Line 275:
Only high levels in the Pressurizer are of concern with regard to the safety analysis.   
Only high levels in the Pressurizer are of concern with regard to the safety analysis.   


Therefore, the minimum Pressurizer level limit does not satisfy Criterion 2.  
Therefore, the minimum Pressurizer level limit does not satisfy Criterion 2.
: 3. The minimum Pressurizer level limit is not a structure, system or component that is part of the primary success path and which functions or actuates to mitigate a DBA or  
: 3. The minimum Pressurizer level limit is not a structure, system or component that is part of the primary success path and which functions or actuates to mitigate a DBA or  


Line 289: Line 289:
to 1CAN030901  
to 1CAN030901  


Page 3 of 5  
Page 3 of 5
: 4. The minimum Pressurizer level limit is not a structure, system, or component which operating experience or probabilistic risk assessment has shown to be significant to  
: 4. The minimum Pressurizer level limit is not a structure, system, or component which operating experience or probabilistic risk assessment has shown to be significant to  


Line 308: Line 308:
==5.0 REGULATORY ANALYSIS==
==5.0 REGULATORY ANALYSIS==


===5.1 Applicable===
5.1 Applicable Regulatory Requirements/Criteria
Regulatory Requirements/Criteria


General Design Criterion (GDC) 10, 13, 15, 20, 23, and 24 govern the requirements for the  
General Design Criterion (GDC) 10, 13, 15, 20, 23, and 24 govern the requirements for the  
Line 350: Line 349:
Entergy Operations, Inc. has evaluated whether or not a significant hazards consideration is involved with the proposed amendment by focusing on the three standards set forth in  
Entergy Operations, Inc. has evaluated whether or not a significant hazards consideration is involved with the proposed amendment by focusing on the three standards set forth in  


10 CFR 50.92, "Issuance of amendment," as discussed below:  
10 CFR 50.92, "Issuance of amendment," as discussed below:
: 1. Does the proposed change involve a significant increase in the probability or consequences of an accident previously evaluated?
: 1. Does the proposed change involve a significant increase in the probability or consequences of an accident previously evaluated?
Response:  No.
Response:  No.
Line 368: Line 367:
Therefore, the proposed change does not involve a significant increase in the  
Therefore, the proposed change does not involve a significant increase in the  


probability or consequences of an accident previously evaluated.  
probability or consequences of an accident previously evaluated.
: 2. Does the proposed change create the possibility of a new or different kind of accident from any accident previously evaluated?
: 2. Does the proposed change create the possibility of a new or different kind of accident from any accident previously evaluated?
Response:  No.
Response:  No.
Line 376: Line 375:
Therefore, the proposed change does not create the possibility of a new or different  
Therefore, the proposed change does not create the possibility of a new or different  


kind of accident from any previously evaluated.  
kind of accident from any previously evaluated.
: 3. Does the proposed change involve a significant reduction in a margin of safety?  
: 3. Does the proposed change involve a significant reduction in a margin of safety?  


Line 402: Line 401:
Page 5 of 5  
Page 5 of 5  


===5.3 Environmental===
5.3 Environmental Considerations  
Considerations  


The proposed amendment does not involve (i) a significant hazards consideration, (ii) a  
The proposed amendment does not involve (i) a significant hazards consideration, (ii) a  
Line 417: Line 415:
10 CFR 51.22(b), no environmental impact stat ement or environmental assessment need be prepared in connection with the proposed amendment.  
10 CFR 51.22(b), no environmental impact stat ement or environmental assessment need be prepared in connection with the proposed amendment.  


===6.0 PRECEDENCE===
6.0 PRECEDENCE A review of all other U.S. B&W commercial nuclear power plant TSs was performed. All other  
 
A review of all other U.S. B&W commercial nuclear power plant TSs was performed. All other  


related plant TSs, with the exception of Three Mile Island, no longer contain a minimum level  
related plant TSs, with the exception of Three Mile Island, no longer contain a minimum level  
Line 434: Line 430:
Pressurizer 3.4.9 ANO-1 3.4.9-1 Amendment No. 215 , 3.4 REACTOR COOLANT SYSTEM (RCS)  
Pressurizer 3.4.9 ANO-1 3.4.9-1 Amendment No. 215 , 3.4 REACTOR COOLANT SYSTEM (RCS)  


====3.4.9 Pressurizer====
3.4.9 Pressurizer  


LCO  3.4.9 The pressurizer shall be OPERABLE with:  
LCO  3.4.9 The pressurizer shall be OPERABLE with:
: a. Pressurizer water level  45 inches and  320 inches; and  
: a. Pressurizer water level  45 inches and  320 inches; and
: b. A minimum of 126 kW of Engineered Safeguards (ES) bus powered pressurizer heaters OPERABLE.  
: b. A minimum of 126 kW of Engineered Safeguards (ES) bus powered pressurizer heaters OPERABLE.  
  ----------------------------------------------NOTE-------------------------------------------  
  ----------------------------------------------NOTE-------------------------------------------  

Revision as of 02:41, 12 July 2019

License Amendment Request on Technical Specification Change to Delete Low Pressurizer Level Limit
ML090690819
Person / Time
Site: Arkansas Nuclear Entergy icon.png
Issue date: 03/10/2009
From: Mitchell T
Entergy Operations
To:
Document Control Desk, Office of Nuclear Reactor Regulation
References
1CAN030901
Download: ML090690819 (12)


Text

1CAN030901

March 10, 2009

U.S. Nuclear Regulatory Commission

Attn: Document Control Desk

Washington, DC 20555

SUBJECT:

License Amendment Request Technical Specification Change To Delete Low Pressurizer Level Limit

Arkansas Nuclear One, Unit 1

Docket No. 50-313

License No. DPR-51

Dear Sir or Madam:

Pursuant to 10 CFR 50.90, Entergy Operations, Inc. (Entergy) hereby requests the following

amendment for Arkansas Nuclear One, Unit 1 (ANO-1). Currently, Technical Specification (TS) 3.4.9, Pressurizer, contains a maximum and minimum level for the Pressurizer. Entergy proposes to delete the minimum level require ment. This change is consistent with NUREG 1430, Rev. 3.1, Standard Technical Specifications (STS) for Babcock & Wilcox Plants.

Limiting the maximum operating water level in the Pressurizer preserves the steam space for

pressure control. The TS limit has been established to ensure the capability to establish and

maintain pressure control for steady state operation and to minimize the consequences of

potential overpressure transients. Requiring the presence of a steam bubble is also consistent

with analytical assumptions.

However, the STS contain no minimum level requirement. During the conversion of the

ANO-1 TSs to STS, the minimum level was retained because it was present in the original

ANO-1 custom TSs. The TS Bases for this limit was simply to ensure sufficient volume was

maintained in the Pressurizer above the minimum detectable level.

While maintaining level in the Pressurizer is preferred and controlled by procedures and

automatic control systems, a minimum level is not required to prevent or mitigate an accident.

Level and pressure control systems act to maintain Pressurizer level at a pre-determined

setpoint. Station procedures provide immediate guidance for operators when level is found

outside the control band, which include verification that automatic control systems are

responding to restore level to within the normal range. Operators may also establish manual

control of makeup and letdown systems to restor e level. If control systems cannot restore level, the reactor is manually tripped. Rapid level reduction would result in an automatic reactor trip on Low RCS Pressure. Entergy Operations, Inc.

1448 S.R. 333 Russellville, AR 72802

Tel 479-858-3110 Timothy G. Mitchell Vice President, Operations A rkansas Nuclear One

1CAN030901 Page 2 of 3

The ANO-1 Safety Analysis Report (SAR) credits the maximum Pressurizer level to protect

against high Reactor Coolant System (RCS) pressures (overfill transients). Because the

minimum level is not a SAR assumption to preclude or mitigate an accident, this limit does not

meet the criteria of 10 CFR 50.36 for inclusion in the TSs.

A detailed explanation of the proposed change is provided in Attachment 1. A markup of the

affected TS pages is contained in Attachment 2 of this submittal.

The proposed change has been evaluated in accordance with 10 CFR 50.91(a)(1) using

criteria in 10 CFR 50.92(c) and it has been determined that the changes involve no significant

hazards consideration. The bases for these determinations are included in the attached

submittal.

The proposed change does not include any new commitments.

Entergy requests approval of the proposed amendment by April 1, 2010.

Once approved, the amendment shall be implemented within 90 days.

If you have any questions or require additional information, please contact David Bice at

479-858-5338.

I declare under penalty of perjury that the foregoing is true and correct. Executed on

March 10, 2009.

Sincerely, TGM/dbb Attachments:

1. Analysis of Proposed Technical Specification Change
2. Proposed Technical Specification Changes (mark-up)

1CAN030901 Page 3 of 3

cc: Mr. Elmo E. Collins Regional Administrator U. S. Nuclear Regulatory Commission Region IV 612 E. Lamar Blvd., Suite 400 Arlington, TX 76011-4125

NRC Senior Resident Inspector Arkansas Nuclear One P. O. Box 310

London, AR 72847

U. S. Nuclear Regulatory Commission

Attn: Mr. Alan B. Wang

MS O-7 D1

Washington, DC 20555-0001

Mr. Bernard R. Bevill

Arkansas Department of Health

Radiation Control Section

4815 West Markham Street Slot #30 Little Rock, AR 72205 Attachment 1 1CAN030901 Analysis of Proposed Technical Specification Change to 1CAN030901

Page 1 of 5

1.0 DESCRIPTION

This letter is a request to amend Operating License DPR-51 for Arkansas Nuclear One, Unit 1 (ANO-1).

Currently, Technical Specification (TS) 3.4.9, Pressurizer, contains a maximum and minimum

level for the Pressurizer. Entergy proposes to delete the minimum level requirement. This

change is consistent with NUREG 1430, Rev. 3.1, Standard Technical Specifications (STS)

for Babcock & Wilcox Plants.

2.0 PROPOSED CHANGE

The proposed change will delete TS 3.4.9 minimum limit on Pressurizer level. As a result of

this deletion, Surveillance Requirement (SR) 3.4.9.1 is revised to eliminate verification of the

minimum level requirement. Both the TS and the SR will maintain requirements governing

the maximum Pressurizer level limit.

A markup of the affected TS page is included in Attachment 2.

3.0 BACKGROUND

To maintain a constant Pressurizer water level, total makeup to the Reactor Coolant System (RCS) must equal that which is letdown from the system. Total makeup consists of the seal

injection water through the Reactor Coolant Pump (RCP) shaft seals and makeup returned to

the system through the Pressurizer level control valve. The Pressurizer level controller

provides automatic control of the valve to maintain the desired pressurizer water level. RCS

volume changes during plant load changes exceed the capability of the volume control valve, and thus result in variations in pressurizer level. The level is returned to normal as the

system returns to steady state conditions.

Limiting the maximum operating water level in the Pressurizer preserves the steam space for

pressure control. The TS limit has been established to ensure the capability to establish and

maintain pressure control for steady state operation and to minimize the consequences of

potential overpressure transients. Requiring the presence of a steam bubble is also

consistent with analytical assumptions.

However, the STS contain no minimum level requirement. During the conversion of the

ANO-1 TSs to STS, the minimum level was retained because it was present in the original

ANO-1 custom TSs. The TS Bases for this limit was simply to ensure sufficient volume was

maintained in the Pressurizer above the minimum detectable level. Furthermore, it is normal

and expected for Pressurizer level to dip below the low-end of the level control band during

some transients and following a reactor trip. The automatic level control system is designed

to accommodate such level responses. In addition, operators may take manual action to

restore level as needed. Pressurizer level indications are available on instruments and

computer trends in various control room locations, and control room alarms alert operators

when level deviates from control system setpoint.

to 1CAN030901

Page 2 of 5

4.0 TECHNICAL ANALYSIS

While maintaining level in the Pressurizer is preferred and controlled by procedures and

automatic control systems, a minimum level is not required to prevent or mitigate an accident.

Level and pressure control systems act to maintain Pressurizer level at a pre-determined

setpoint. Station procedures provide immediate guidance for operators when level is found

outside the control band, which include verification that automatic control systems are

responding to restore level to within the normal range. Operators may also establish manual

control of makeup and letdown systems to restore level. If Pressurizer level cannot be

restored, the reactor is manually tripped. Rapid level reduction would result in an automatic reactor trip on Low RCS Pressure.

In addition, it is not necessary for TSs to establish a minimum Pressurizer level limit solely to

ensure level indications remain on-scale. As described above, automatic and/or manual

action is taken immediately upon deviation from level setpoint and, if unsuccessful, the

reactor will be manually tripped prior to Pressurizer level indication being lost. Again, for rapid

transients, the reactor will automatically trip on Low RCS Pressure as RCS inventory is lost.

The ANO-1 Safety Analysis Report (SAR) credits the maximum Pressurizer level to protect

against high Reactor Coolant System (RCS) pressures (overfill transients). Because the

minimum level is not a SAR assumption to preclude or mitigate an accident, this limit does not

meet the criteria of 10 CFR 50.36 for inclusion in the TSs. An evaluation of the 10 CFR 50.36

criteria is included below.

1. The minimum Pressurizer level limit is not installed instrumentation that is used to detect, and indicate in the control room, a significant abnormal degradation of the reactor coolant

pressure boundary. Pressurizer level is a required control room indication governed by

TS 3.3.15, Post Accident Monitoring (PAM) Instrumentation. While the indication itself

can be used to detect an abnormal degradation in the RCS pressure boundary, no

minimum level need be specified in order for the instrument to perform its design

function. As discussed above, automatic or manual action is taken for any deviation in Pressure level, well in advance of level reaching a point where indication would be off-

scale. Therefore, the minimum Pressurizer level limit does not satisfy Criterion 1.

2. The minimum Pressurizer level limit is not a process variable, design feature, or operating restriction that is an initial condition of a DBA or transient analysis that either

assumes the failure of or presents a challenge to the integrity of a fission product barrier.

Only high levels in the Pressurizer are of concern with regard to the safety analysis.

Therefore, the minimum Pressurizer level limit does not satisfy Criterion 2.

3. The minimum Pressurizer level limit is not a structure, system or component that is part of the primary success path and which functions or actuates to mitigate a DBA or

transient that either assumes the failure of or presents a challenge to the integrity of a

fission product barrier. Pressurizer level losses that are beyond the capability of normal

makeup and control systems are mitigated by actuation of the emergency core cooling

systems. These systems will re spond to prevent violation of any safety limit regardless of the initial Pressurizer level which existed prior to the event. Therefore, the minimum

Pressurizer level limit does not satisfy Criterion 3.

to 1CAN030901

Page 3 of 5

4. The minimum Pressurizer level limit is not a structure, system, or component which operating experience or probabilistic risk assessment has shown to be significant to

public health and safety. As discussed above, automatic control systems and specific procedures are provided to maintain Pressurizer level within a normal operating band, dependent on the plant mode of operation. The existence of a minimum level

requirement in the TSs does not alter these mechanisms, nor does the limit prevent

reductions in Pressurizer level below setpoint during transients or following a reactor trip.

In addition, rapid reduction of Pressurizer level is protected by the on Low RCS Pressure

automatic reactor trip signal. Therefore, deletion of the minimum Pressurizer level limit

from the TSs has no significant risk impact to plant systems or safe plant operation.

Note also that the TS Bases do not present a 10 CFR 50.36 criterion for minimum Pressurizer level: In MODES 1 and 2, the maximum pressurizer water level limit satisfies Criterion 2 of 10 CFR 50.36 (Ref. 2). In MODE 3 and MODE 4 above the LTOP enable temperature, the maximum pressurizer water level limit satisfies Criterion 4 of 10 CFR 50.36.

Based on the above, Entergy believes it is acceptable to delete the TS minimum level requirement for the pressurizer.

5.0 REGULATORY ANALYSIS

5.1 Applicable Regulatory Requirements/Criteria

General Design Criterion (GDC) 10, 13, 15, 20, 23, and 24 govern the requirements for the

reactor coolant system (RCS), instrumentation, and protective system design. Entergy

Operations, Inc. (Entergy) proposes to delete minimum Pressurizer level requirements from

Arkansas Nuclear One, Unit 1 (ANO-1) Technical Specification (TS) 3.4.9. Deletion of this

requirement will not adversely affect any GDC.

In addition, the proposed change is consistent with NUREG 1430, Rev. 3.1, Standard Technical Specifications for Babcock & Wilcox Plants (STS). Automatic control systems and manual oper ations specified in station procedures will continue to maintain a desired Pressurizer level. These functions are not dependent on the

minimum Pressurizer level limit currently specified in the TSs. The maximum Pressurizer TS

level limit, required to ensure appropriate pressure and inventory control during transients, is

unaffected by this change.

In conclusion, Entergy has determined that the proposed change does not require any

exemptions or relief from regulatory requirements, other than the TS, and does not affect

conformance with any GDC differently than descr ibed in the Safety Analysis Report (SAR).

5.2 No Significant Hazards Consideration

A change is proposed to the Arkansas Nuclear One, Unit 1 (ANO-1) Technical Specification (TS) 3.4.9, Pressurizer. Specifically, the minimum Pressure level limit is proposed to be

deleted from the TS. This change is consistent with NUREG 1430, Rev. 3.1, Standard

Technical Specifications for Babcock & Wilcox Plants (STS). The minimum level specified in

the TS is not an assumption contained in the accident analysis to preclude or mitigate an

accident evaluated in the ANO-1 Safety Analysis Report (SAR). to 1CAN030901

Page 4 of 5

Entergy Operations, Inc. has evaluated whether or not a significant hazards consideration is involved with the proposed amendment by focusing on the three standards set forth in

10 CFR 50.92, "Issuance of amendment," as discussed below:

1. Does the proposed change involve a significant increase in the probability or consequences of an accident previously evaluated?

Response: No.

The minimum Pressure level limit currently specified in the TSs does not act to ensure

specified fuel design limits are protected. Accident and transient analyses assume

lowering or a loss of Pressurizer level. Safety systems are designed and maintained

available to mitigate the consequences of an accident or transient that may involve a

loss of Reactor Coolant System (RCS) inv entory. None of these systems rely upon a predetermined minimum Pressurizer level in order to perform their intended function.

Furthermore, the minimum Pressure level limit is unrelated to any anticipated accident

initiator.

Therefore, the proposed change does not involve a significant increase in the

probability or consequences of an accident previously evaluated.

2. Does the proposed change create the possibility of a new or different kind of accident from any accident previously evaluated?

Response: No.

No physical changes to the facility are initiated by the proposed change. In addition, the proposed change has no affect on plant configuration, or method of operation of

plant structures, systems, or components.

Therefore, the proposed change does not create the possibility of a new or different

kind of accident from any previously evaluated.

3. Does the proposed change involve a significant reduction in a margin of safety?

Response: No.

Installed automatic control systems will continue to maintain Pressurizer level at a

predetermined setpoint and are independent of a prescribed minimum TS level limit.

The deletion of the current TS limit has no impact on guidance or operational

response to pressurizer level deviations. Furthermore, the minimum Pressure level

limit is not an assumed value for accident prevention or mitigation in the ANO-1 SAR.

Therefore, the proposed change does not involve a significant reduction in a margin of

safety.

Based on the above, Entergy concludes that the proposed amendment presents no significant

hazards consideration under the standards set forth in 10 CFR 50.92(c), and, accordingly, a

finding of "no significant hazards consideration" is justified.

to 1CAN030901

Page 5 of 5

5.3 Environmental Considerations

The proposed amendment does not involve (i) a significant hazards consideration, (ii) a

significant change in the types or significant increase in the amounts of any effluent that may

be released offsite, or (iii) a significant increase in individual or cumulative occupational

radiation exposure. Accordingly, the proposed amendment meets the eligibility criterion for

categorical exclusion set forth in 10 CFR 51.22(c)(9). Therefore, pursuant to

10 CFR 51.22(b), no environmental impact stat ement or environmental assessment need be prepared in connection with the proposed amendment.

6.0 PRECEDENCE A review of all other U.S. B&W commercial nuclear power plant TSs was performed. All other

related plant TSs, with the exception of Three Mile Island, no longer contain a minimum level

for Pressurizer level. Three Mile Island is a custom TS plant and has not yet converted to

STS.

7.0 REFERENCES

None

Attachment 2 1CAN030901 Proposed Technical Specification Changes (mark-up)

Pressurizer 3.4.9 ANO-1 3.4.9-1 Amendment No. 215 , 3.4 REACTOR COOLANT SYSTEM (RCS)

3.4.9 Pressurizer

LCO 3.4.9 The pressurizer shall be OPERABLE with:

a. Pressurizer water level 45 inches and 320 inches; and
b. A minimum of 126 kW of Engineered Safeguards (ES) bus powered pressurizer heaters OPERABLE.

NOTE-------------------------------------------

OPERABILITY requirements on pressurizer heaters do not apply in

MODE 4.


APPLICABILITY: MODES 1, 2, and 3, MODE 4 with RCS temperature > 262°F.

ACTIONS CONDITION REQUIRED ACTION COMPLETION TIME A. Pressurizer water level not within limits.

A.1 Restore level to within limits. 1 hour1.157407e-5 days <br />2.777778e-4 hours <br />1.653439e-6 weeks <br />3.805e-7 months <br /> B. Required Action and associated Completion

Time of Condition A not

met. B.1 Be in MODE 3.

AND B.2 Be in MODE 4 with RCS temperature 262°F. 6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br />

24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br /> C. Capacity of ES bus powered pressurizer

heaters less than limit.

C.1 Restore pressurizer heater capacity.

72 hours8.333333e-4 days <br />0.02 hours <br />1.190476e-4 weeks <br />2.7396e-5 months <br /> D. Required Action and associated Completion

Time of Condition C not

met. D.1 Be in MODE 3.

AND D.2 Be in MODE 4.

6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br />

12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br />

Pressurizer 3.4.9 ANO-1 3.4.9-2 Amendment No. 215 , SURVEILLANCE REQUIREMENTS SURVEILLANCE FREQUENCY SR 3.4.9.1 Verify pressurizer water level 45 inches and 320 inches.

12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br />

SR 3.4.9.2 Verify capacity of ES bus powered pressurizer heaters 126 kW. 18 months