- 05000315/LER-1982-073-03, /03L-0:on 820831,fire Door 373 Found Unable to Latch During Refueling Operations.Probably Caused by Misalignment of Inactive Leaf within Frame.Leaf Realigned by Shimming to Improve Flush Bolt Engagement (← links)
- 05000315/LER-1982-072-03, /03L-0:on 820817,min Average Ice Weight of Sample Baskets from Radial Rows 8 & 9 Found to Be Less than 1,220 1b/basket at 95% Confidence Level.Apparently Caused by Natural Sublimation.Ice Mass Added to Lacking Row Groups (← links)