List of results
- 05000249/LER-1981-003-03, /03L-0:on 810120,Model 288 Differential Pressure Indicating switch,3-1349B,tripped Above Tech Spec Limit. Caused by Instrument Drift.Switch Readjusted & Repeatability Verified + (19:43:02, 23 December 2024)
- ML20003B781 + (19:43:03, 23 December 2024)
- ML20003B782 + (19:43:03, 23 December 2024)
- 05000302/LER-1981-006-03, /03L-0:on 810123,breaker for Control Complex Emergency Ventilation Fan AHF-18A Found Open.Caused by Inadvertent Bumping of Breaker.Breaker Shut,Operability Checks Performed & Personnel Advised to Exercise Caution + (19:43:04, 23 December 2024)
- ML20003B779 + (19:43:05, 23 December 2024)
- ML20003B778 + (19:43:06, 23 December 2024)
- 05000302/LER-1981-006, Forwards LER 81-006/03L-0 + (19:43:07, 23 December 2024)
- ML20003B775 + (19:43:08, 23 December 2024)
- 05000346/LER-1981-007-03, /03L-0:on 810122,door 306 Found Partially Open,So That Spent Fuel Pool Emergency Ventilation Sys Could Not Have Maintained Area at Correct Pressure.Caused by Maladjusted Door Closure.Maint Work Order Issued + (19:43:09, 23 December 2024)
- 05000255/LER-1981-008-03, /03L-0:on 810124,component Cooling Water Pump P-52C Motor Caught on Fire.Caused by Motor Bearing Failure Due to Oil Loss.Motor Replaced + (19:43:11, 23 December 2024)
- ML20003B772 + (19:43:13, 23 December 2024)
- 05000346/LER-1981-007, Forwards LER 81-007/03L-0 + (19:43:14, 23 December 2024)
- 05000324/LER-1981-010-03, /03L-0:on 810120,RHR Svc Water Subsys a Suction valve,2-SW-V101,would Not Open Fully.Caused by Two Hex Nuts on Input Shaft of Valve Motor Operator,Model H3BC-SMB-00, Freezing to Shaft.Nuts & Shaft Reworked & Lubricated + (19:43:16, 23 December 2024)
- 05000324/LER-1981-010, Forwards LER 81-010/03L-0 + (19:43:19, 23 December 2024)
- 05000318/LER-1981-006-03, /03L-0:on 810113 Diesel Generator 12 Switchgear Would Not Close in on 21 4-kV Bus Per Tech Spec.Caused by High Resistance at Secondary Disconnect.Continuity of Closing Circuit Interlocks Verified & Switchgear Tested + (19:43:25, 23 December 2024)
- 05000318/LER-1981-007, Forwards LER 81-007/03L-0 + (19:43:27, 23 December 2024)
- 05000029/LER-1981-001-03, /03L-0:on 810122,low Main Coolant Flow Sys B Under Current Relays 2A & 4C Failed to Drop Out When de-energized. Caused by Residue Buildup on Relay Activation Plunger.Relay Plungers in Sys a & B Inspected & Cleaned as Require + (19:43:29, 23 December 2024)
- 05000029/LER-1981-001, Forwards LER 81-001/03L-0 + (19:43:30, 23 December 2024)
- 05000317/LER-1981-005-03, /03L-0:on 810119,during Surveillance Testing, Containment Cooler 14 Would Not Start in Slow Speed.Caused by Contacts Not Closing on Slow Speed Motor Starter Interlock Contact Assembly Due to Cracked Case + (19:43:32, 23 December 2024)
- 05000318/LER-1981-006, Forwards LER 81-006/03L-0 + (19:43:34, 23 December 2024)
- 05000317/LER-1981-005, Forwards LER 81-005/03L-0 + (19:43:35, 23 December 2024)
- ML20003B750 + (19:43:38, 23 December 2024)
- ML20003B749 + (19:43:39, 23 December 2024)
- 05000267/LER-1981-013-01, /01T-0:on 810203,following Liquid Waste Release 429,tritium Concentration Exceeded Tech Spec.Caused by Sys Design Inadequacy W/Oil Separator on Liquid Waste Discharge Line.Bypass Installed Around Oil Separator + (19:43:41, 23 December 2024)
- PNO-I-81-025, on 810218,licensee Reported 9.65 Ci Kr-85 Released from Device Used for Leak Testing Electronic Components During Sampling Prior to Returning Device to Manufacturer.Stack Concentration Exceed 10CFR20 Limits + (19:43:45, 23 December 2024)
- 05000267/LER-1981-013, Forwards LER 81-013/01T-0.Detailed Event Analysis Submitted + (19:43:46, 23 December 2024)
- PNO-I-81-023, liquid Observed in Truck Carrying Radiography Device & Nine Drums Phosphoric Acid Containing Natural U. Caused by Leaking Drum.Truck & Contents Surveyed for Radioactive Matl Leakage + (19:43:48, 23 December 2024)
- 05000296/LER-1981-007-03, /03L-0:on 810202,setpoint for 3-PS-1-76 Below Tech Specs Limit.Caused by B2TA12SS Setpoint Drift.Switch Recalibr & Verified.Switch to Be Replaced W/Analog Trip Sys by DCR 1398 + (19:43:50, 23 December 2024)
- PNO-I-81-021, on 810213,based on Results from Charpy V-notch Impact Tests,Licensee Notified That Hydrostatic Test of RCS in Mar 1980 Performed at 27 Degrees Below Min Pressurization Temp + (19:43:52, 23 December 2024)
- 05000296/LER-1981-007, Forwards LER 81-007/03L-0 + (19:43:53, 23 December 2024)
- PNO-I-81-022, on 810216,licensee Informed That Thickness Gauge Containing 17 Mci Cs-137 Was Missing.Caused When Gauge Taken Off Line in Jan 1981 & Placed in Salvage Dept.Gauge Shipped to Prolerized Scrap Metal Company by Mistake + (19:43:55, 23 December 2024)
- ML20003B736 + (19:43:56, 23 December 2024)
- PNO-I-81-024, on 810210,patient Implanted w/40 Seeds of I-125.As of 810218,three Seeds Were Unaccounted For.Probably Caused by Patient Voiding Seeds or Seeds Remaining in Patient But Undetected by x-rays + (19:43:58, 23 December 2024)
- ML20003B734 + (19:43:59, 23 December 2024)
- ML20003B733 + (19:44:02, 23 December 2024)
- ML20003B732 + (19:44:05, 23 December 2024)
- ML20003B731 + (19:44:05, 23 December 2024)
- ML20003B730 + (19:44:06, 23 December 2024)
- ML20003B729 + (19:44:07, 23 December 2024)
- ML20003B728 + (19:44:08, 23 December 2024)
- ML20003B727 + (19:44:09, 23 December 2024)
- ML20003B726 + (19:44:10, 23 December 2024)
- ML20003B724 + (19:44:11, 23 December 2024)
- ML20003B723 + (19:44:12, 23 December 2024)
- ML20003B722 + (19:44:13, 23 December 2024)
- ML20003B721 + (19:44:14, 23 December 2024)
- ML20003B720 + (19:44:15, 23 December 2024)
- ML20003B715 + (19:44:27, 23 December 2024)
- ML20003B711 + (19:44:31, 23 December 2024)
- ML20003B707 + (19:44:33, 23 December 2024)
- ML20003B708 + (19:44:33, 23 December 2024)