- ML20027B167 + (02:54:35, 21 December 2024)
- 05000311/LER-1982-079, Forwards LER 82-079/03L-0.Detailed Event Analysis Encl + (02:54:36, 21 December 2024)
- 05000272/LER-1982-059, Forwards LER 82-059/03L-0.Detailed Event Analysis Encl + (02:54:38, 21 December 2024)
- 05000338/LER-1982-056-03, /03L-0:on 820808,insp of 1A Reactor Coolant Pump Impeller End of Pump & Pump Casing Revealed Seven Failed Socket Head Cap Screws to Diffuser Adapter.Cause Under Investigation.Screws Replaced + (02:54:39, 21 December 2024)
- ML20027B161 + (02:54:40, 21 December 2024)
- RBG-13-275, Interim Deficiency Rept Re Valen Engineering Ltd Valve Stud Matl Not Recognized for Use Under ASME Section 3.Initially Reported on 820629.Investigation Incomplete.Next Rept to Be Submitted on 821014 + (02:54:41, 21 December 2024)
- 05000338/LER-1982-056, Forwards LER 82-056/03L-0 + (02:54:46, 21 December 2024)
- ML20027B156 + (02:54:47, 21 December 2024)
- ML20027B154 + (02:54:54, 21 December 2024)
- ML20027B153 + (02:54:55, 21 December 2024)
- 05000302/LER-1982-053-03, /03L-0:on 820808,outer Door of Reactor Bldg Personnel Hatch Reported Inoperable.Caused by Failure of Cam Roller Bearings in Mechanical Interlock.Bearings Replaced.Mod to Eliminate Problem Completed on 820831 + (02:54:56, 21 December 2024)
- ML20027B149 + (02:55:00, 21 December 2024)
- ML20027B148 + (02:55:01, 21 December 2024)
- 05000302/LER-1982-053, Forwards LER 82-053/03L-0 + (02:55:02, 21 December 2024)
- ML20027B145 + (02:55:03, 21 December 2024)
- ML20027B144 + (02:55:03, 21 December 2024)
- 05000335/LER-1982-034-03, /03L-0:on 820804,refueling Water Tank Level Transmitter LT-07-2B Failed High.Caused by Leakage Past Diaphragm.Transmitter Dismantled,Reassembled & Tested Satisfactorily + (02:55:04, 21 December 2024)
- 05000272/LER-1982-060-03, /03L-0:on 820807,control Operator Attempting to Perform Containment Pressure Relief,Discovered Valve 1VC5 Would Not Open from Control Console.Caused by Failure of Control Air Solenoid Valve on Actuator.Solenoid Replaced + (02:55:06, 21 December 2024)
- ML20027B141 + (02:55:07, 21 December 2024)
- ML20027B140 + (02:55:08, 21 December 2024)
- IR 05000321/1982023 + (02:55:10, 21 December 2024)
- 05000335/LER-1982-034, Forwards LER 82-034/03L-0 + (02:55:12, 21 December 2024)
- 05000325/LER-1982-070-03, /03L-0:on 820809,review Revealed That Operability Surveillance of Fire Hose Stations Required Once Per 18 Months Not Provided for in Fire Protection Sys Surveillance Procedures.Caused by Personnel Oversight + (02:55:13, 21 December 2024)
- 05000272/LER-1982-060, Forwards LER 82-060/03L-0.Detailed Event Analysis Encl + (02:55:15, 21 December 2024)
- ML20027B131 + (02:55:17, 21 December 2024)
- 05000324/LER-1982-102-03, /03L-0:on 820810,attempt to Operate a Loop Core Spray Subsystem Room Cooler Determined That Svc Water Discharge Valve 2-SW-V128 Would Not Operate Properly. Caused by Grease on Valve Due to Moisture from Air Lines + (02:55:18, 21 December 2024)
- 05000272/LER-1982-057-03, /03L-0:on 820803,during Routine Operation, Circulator 13A Tripped Resulting in Rapid Load Reduction. Caused by Grass & Debris Clogging Travelling Screen.Screen Cleaned & Circulator Returned to Svc + (02:55:20, 21 December 2024)
- 05000324/LER-1982-102, Forwards LER 82-102/03L-0 + (02:55:21, 21 December 2024)
- 05000272/LER-1982-057, Forwards LER 82-057/03L-0.Detailed Event Analysis Encl + (02:55:23, 21 December 2024)
- 0CAN098206, Provides Current Status of Listed NUREG-0737 Items Per 820505 Request.Adequate Justification Provided for Items Not Meeting Required Schedule + (02:55:24, 21 December 2024)
- 05000272/LER-1982-056-03, /03L-0:on 820802,during Performance of Procedure SP(o)4.0.5-P on Auxiliary Feed Pump 11,recirculation Valve 11AF40 Would Not Open.Caused by Isolated Low Side of Transmitter.Operator Counseled + (02:55:27, 21 December 2024)
- 05000302/LER-1982-054-03, /03L-0:on 820812,remote Reactor Coolant Temp Indicator RC-4A-T12 Discovered Inoperable.Caused by Dirty Terminals.Instrument Lugs & Terminals Cleaned + (02:55:28, 21 December 2024)
- 05000325/LER-1982-070, Forwards LER 82-070/03L-0 + (02:55:30, 21 December 2024)
- 05000302/LER-1982-054, Forwards LER 82-054/03L-0 + (02:55:32, 21 December 2024)
- 05000155/LER-1982-024-03, /03L-0:on 820811,120-s Initiation Timer for One of Four Sensor Channels Failed to Trip During Monthly Reactor Depressurization Sys Testing.Caused by Defect in Timer Operation Due to Failure of Integrated Circuit Unit + (02:55:34, 21 December 2024)
- 05000272/LER-1982-056, Forwards LER 82-056/03L-0.Detailed Event Analysis Encl + (02:55:35, 21 December 2024)
- 05000155/LER-1982-024, Forwards LER 82-024/03L-0 + (02:55:40, 21 December 2024)
- IR 05000269/1982014 + (02:55:42, 21 December 2024)
- 05000325/LER-1982-097-03, /03L-0:on 820812,review of Procedures Revealed That Plant Procedures Did Not Provide for Required Once Per 18-month Visual Insp of Aog Bldg Fire Doors.Caused by Personnel Oversight During Development of PT-35.18.2 + (02:55:43, 21 December 2024)
- ML20027B106 + (02:55:44, 21 December 2024)
- 05000325/LER-1982-097, Forwards LER 82-097/03L-0 + (02:55:46, 21 December 2024)
- IR 05000416/1982059 + (02:55:48, 21 December 2024)
- 05000313/LER-1982-022-03, /03L-0:on 820807,during Cooldown W/Rcs Temp at 307 F,Control Rod Drive Dc Breaker Did Not Trip as Required. Caused by Undervoltage Trip Device Out of Adjustment. Proper Adjustments Made & Breaker Tested Satisfactorily + (02:55:49, 21 December 2024)
- RBG-13-340, Interim Deficiency Rept DR-61 Re Length of Capscrew Holding Starting Air Valve Assembly in Standby Emergency Diesel Generator Cylinder Head.Initially Reported on 820618.Insp & Capscrews to Be Replaced Feb 1983.Also Reported Per Part 21 + (02:55:50, 21 December 2024)
- 05000313/LER-1982-022, Forwards LER 82-022/03L-0 + (02:55:53, 21 December 2024)
- ML20027B095 + (02:55:54, 21 December 2024)
- ML20027B094 + (02:55:56, 21 December 2024)
- 05000311/LER-1982-087-03, /03L-0:on 820816,diesel Generator 2A Air Supply Isolation valves,21DA12C & 22DA12C,discovered Closed.Caused by Personnel Error.Valves Immediately Restored to Open Position.Addl Security/Safety Measures Implemented + (02:55:57, 21 December 2024)
- ML20027B090 + (02:55:58, 21 December 2024)
- ML20027B088 + (02:56:00, 21 December 2024)
- 05000311/LER-1982-087, Forwards LER 82-087/03L-0.Detailed Event Analysis Encl + (02:56:02, 21 December 2024)