- 05000029/LER-1982-044-03, /03L-0:on 821208,continuous Flow Discovered Through Alarm Check Auxiliary Valve After Special Hazards Header Flow Alarm Received.Caused by Insufficient Seating Between Auxiliary Valve Seat & Disc.Valve Disc Replaced + (23:45:08, 20 December 2024)
- 05000361/LER-1982-157-03, /03L-0:on 821124,samples from Control Room Emergency Air Cleanup Sys Train a Charcoal Absorber Failed to Satisfy Methyl Iodine Removal Capability.Caused by Activated Charcoal Degradation.Charcoal Replaced + (23:45:10, 20 December 2024)
- IR 05000272/1982030 + (23:45:12, 20 December 2024)
- 05000361/LER-1982-153-03, /03L-0:on 821130,following Turbine Trip,Low Pressure Turbine Stop Valve 2UV-2200R Failed to Close.Caused by Excessive Galling Between Disc Stub Shafts & Casing Bore. Clearance Between Shaft & Bore Increased + (23:45:13, 20 December 2024)
- ML20028D294 + (23:45:15, 20 December 2024)
- ML20028D297 + (23:45:15, 20 December 2024)
- 05000029/LER-1982-044, Forwards LER 82-044/03L-0 + (23:45:17, 20 December 2024)
- ML20028D289 + (23:45:18, 20 December 2024)
- 05000387/LER-1982-069-03, /03L-0:on 821207,during Startup Testing,Hpci Sys Declared Operable Prior to Closing Out Open Equipment Release Form.Caused by Work Program Design Weakness.Present Work Practice Modified + (23:45:19, 20 December 2024)
- ML20028D286 + (23:45:21, 20 December 2024)
- IR 05000352/1982014 + (23:45:22, 20 December 2024)
- ML20028D281 + (23:45:24, 20 December 2024)
- 05000387/LER-1982-069, Forwards LER 82-069/03L-0 + (23:45:25, 20 December 2024)
- ML20028D271 + (23:45:27, 20 December 2024)
- 05000321/LER-1982-100-03, /03L-0:on 821201,discovered 8 of 20 Newly Installed Cables Deliberately Cut.Caused by Vandalism by Person or Persons Unknown.Cables Repaired + (23:45:28, 20 December 2024)
- 05000416/LER-1982-165-03, /03L-0:on 821213,Divs I & II Diesels Declared Inoperable Due to Discovery of Unqualified Cable in Diesel Generator Control Circuitry.Caused by Vendor Notification That Cables Failed IEEE Flame Test.Controls Deemed Adequate + (23:45:33, 20 December 2024)
- IR 05000329/1982023 + (23:45:35, 20 December 2024)
- 05000387/LER-1982-062, Forwards LER 82-062/01T-0 + (23:45:36, 20 December 2024)
- 05000321/LER-1982-100, Forwards LER 82-100/03L-0 + (23:45:38, 20 December 2024)
- RBG-14-093, Interim Deficiency Rept DR-30 Re Interpretation of Radiographs Performed by Bf Shaw Co.Approx 99% of Radiographs Reviewed & Defective Welds Identified in Nonconformance & Disposition 3098.Final Rept by 830315 + (23:45:41, 20 December 2024)
- 05000416/LER-1982-165, Forwards LER 82-165/03L-0 + (23:45:44, 20 December 2024)
- ML20028D256 + (23:45:45, 20 December 2024)
- ML20028D254 + (23:45:50, 20 December 2024)
- 05000387/LER-1982-061, Forwards LER 82-061/01T-0 + (23:45:51, 20 December 2024)
- 05000325/LER-1982-109-03, /03L-0:on 821208,during Routine Surveillance, Outer Door of Reactor Bldg Secondary Containment Personnel Airlock Was Inoperable.Caused by Missing 2-inch Section of Door Gasket.Missing Section Replaced + (23:45:53, 20 December 2024)
- 05000366/LER-1982-129-03, /03L-0:on 821130,during Performance of Diesel Generator Manual Start Procedure,Diesel Generator B Started & Immediately Tripped.Caused by Personnel Failure to Remove Jumpers After Maint.Jumpers Removed + (23:45:54, 20 December 2024)
- ML20028D248 + (23:45:55, 20 December 2024)
- 05000366/LER-1982-129, Forwards LER 82-129/03L-0 + (23:45:57, 20 December 2024)
- 05000261/LER-1980-009, Updated LER 80-009/01T-1:on 800414,primary to Secondary Leak of Approx 0.5 Gpm Detected in B Steam Generator,Exceeding Tech Spec Limit.Caused by Leaking Tubes.Leaks Repaired by Explosive Plugging + (23:45:58, 20 December 2024)
- 05000325/LER-1982-109, Forwards LER 82-109/03L-0 + (23:46:00, 20 December 2024)
- ML20028D237 + (23:46:01, 20 December 2024)
- ML20028D236 + (23:46:02, 20 December 2024)
- ML20028D232 + (23:46:04, 20 December 2024)
- ML20028D223 + (23:46:11, 20 December 2024)
- 05000416/LER-1982-170-03, /03L-0:on 821213,smoke Detectors in Zone Covering Auxiliary Bldg Hallway on 119-ft Elevation Found Covered in Order to Prevent Possible Damage from Welding in Area. Welding Completed & Detectors Returned to Svc + (23:46:13, 20 December 2024)
- ML20028D218 + (23:46:14, 20 December 2024)
- ML20028D215 + (23:46:17, 20 December 2024)
- 05000416/LER-1982-170, Forwards LER 82-170/03L-0 + (23:46:18, 20 December 2024)
- IR 05000446/1982011 + (23:46:20, 20 December 2024)
- ML20028D207 + (23:46:21, 20 December 2024)
- ML20028D205 + (23:46:26, 20 December 2024)
- ML20028D202 + (23:46:27, 20 December 2024)
- ML20028D203 + (23:46:27, 20 December 2024)
- ML20028D201 + (23:46:28, 20 December 2024)
- ML20028D200 + (23:46:29, 20 December 2024)
- 05000325/LER-1982-148-03, /03L-0:on 821208,instrument Chart Paper Indicating post-accident Monitoring Suppression Pool Level Data Found Not Advancing.Caused by Unscrewed Drive Front Sprocket Gear. Sprocket Gear Positioned & Fastened + (23:46:33, 20 December 2024)
- 05000325/LER-1982-148, Forwards LER 82-148/03L-0 + (23:46:35, 20 December 2024)
- 05000325/LER-1982-150-03, /03L-0:on 821209,main Steam Line Flow High Primary Containment Isolation Signal 1-B21-PDTM-N006-D-1 Showed Instrument Downscale Indication.Caused by Defective Amplifier Board in Instrument Transmitter B21-DPT-N006D + (23:46:37, 20 December 2024)
- 05000325/LER-1982-150, Forwards LER 82-150/03L-0 + (23:46:42, 20 December 2024)
- 05000324/LER-1982-138-03, /03L-0:on 821207,during Plant Operation,Rbma Inoperable Annunciator Received When Any of 15 Listed Control Rods Selected.Caused by Failed Q10 Transistor on First Level Multiplexer Card.Card Replaced + (23:46:43, 20 December 2024)
- 05000324/LER-1982-138, Forwards LER 82-138/03L-0 + (23:46:45, 20 December 2024)