- ML20053B699 + (09:02:51, 18 December 2024)
- ML20053B695 + (09:02:55, 18 December 2024)
- 05000325/LER-1982-022, Forwards LER 82-022/03L-0 + (09:02:57, 18 December 2024)
- 05000324/LER-1982-072-03, /03L-0:on 820411,RHR Pump 2C Motor Breaker Tripped Upon Start.Cause Not Determined.Breaker 5HK250 Racked Out,Inspected & Tested.Pump Started + (09:03:01, 18 December 2024)
- ML20053B689 + (09:03:04, 18 December 2024)
- 05000280/LER-1982-052-03, /03L-0:on 820428,amplifier for Heat Tracing Panel B,Circuit 2B,read Below Acceptance Criteria.Caused by Excessive Heat.Defective Heat Tracing Replaced & Tested. Design Change Initiated + (09:03:09, 18 December 2024)
- ML20053B687 + (09:03:11, 18 December 2024)
- 05000324/LER-1982-072, Forwards LER 82-072/03L-0 + (09:03:16, 18 December 2024)
- 05000280/LER-1982-046-03, /03L-0:on 820419,process Vent Particulate Radiation Monitor Filter Fault Alarm Observed.Filter Paper Unable to Advance Due to Swelling Caused by Water Absorption.Caused by Lifting of Relief Valve RV-GW-107 + (09:03:18, 18 December 2024)
- ML20053B683 + (09:03:19, 18 December 2024)
- ML20053B682 + (09:03:20, 18 December 2024)
- ML20053B681 + (09:03:21, 18 December 2024)
- ML20053B678 + (09:03:26, 18 December 2024)
- ML20053B677 + (09:03:27, 18 December 2024)
- 05000328/LER-1982-044-01, /01T-0:on 820409,containment Purge Air Exhaust Radiation Monitor Declared Inoperable Due to Inadequate Sample Points.Caused by Const Drawing Failure to Indicate Flows to & from Radiation Monitors.Piping Reworked + (09:03:29, 18 December 2024)
- ML20053B672 + (09:03:38, 18 December 2024)
- 05000328/LER-1982-044, Forwards LER 82-044/01T-0 + (09:03:39, 18 December 2024)
- 05000325/LER-1982-042-03, /03L-0:on 820423,post-accident Monitoring Control Room Recorder/Indicator 1-CAC-AR-1263 Exhibited Unvarying Indication of Drywell Oxygen Concentration.Caused by Broken Drive Cord Due to Normal Wear.Drive Cord Replaced + (09:03:41, 18 December 2024)
- 05000327/LER-1982-051-03, /03L-0:on 820423,containment Ventilation Isolation Sys Declared Inoperable Due to Loss of Automatic Initiation Capability.Caused by Design Error Which Prevents Automatic Reactuation After Isolation Signal Reset + (09:03:43, 18 December 2024)
- ML20053B666 + (09:03:44, 18 December 2024)
- 05000327/LER-1982-051, Forwards LER 82-051/03L-0 + (09:03:48, 18 December 2024)
- 05000325/LER-1982-042, Forwards LER 82-042/03L-0 + (09:03:50, 18 December 2024)
- ML20053B660 + (09:03:51, 18 December 2024)
- 05000302/LER-1982-034-03, /03L-0:on 820507,radiation Monitoring Instrument RM-A5,iodine Channel,Inoperable.Caused by Dirty Contact Surface on High Voltage Potentiometer.Surface Cleaned + (09:03:52, 18 December 2024)
- ML20053B658 + (09:03:54, 18 December 2024)
- 05000302/LER-1982-034, Forwards LER 82-034/03L-0 + (09:03:55, 18 December 2024)
- ML20053B654 + (09:03:57, 18 December 2024)
- 05000261/LER-1982-004-01, /01T-0:on 820426,insp of Steam Generators B & C Revealed 173 Defective Tubes.Total Was More than 1% of Total Number of Tubes,Placing Results in Category C-3.All Defective Tubes Mechanically Plugged + (09:03:58, 18 December 2024)
- ML20053B651 + (09:04:00, 18 December 2024)
- ML20053B649 + (09:04:01, 18 December 2024)
- ML20053B647 + (09:04:02, 18 December 2024)
- 05000261/LER-1982-004, Forwards LER 82-004/01T-0 + (09:04:08, 18 December 2024)
- 05000271/LER-1982-008-03, /03L-0:on 820422,cooling Fan for RPIS Power Supply in Crp 9-27 Failed,Causing Loss of Rod Position Indication. Sequence Occurred Several Times.Fan Replaced + (09:04:10, 18 December 2024)
- ML20053B643 + (09:04:12, 18 December 2024)
- ML20053B641 + (09:04:13, 18 December 2024)
- ML20053B639 + (09:04:14, 18 December 2024)
- ML20053B638 + (09:04:15, 18 December 2024)
- 05000271/LER-1982-008, Forwards LER 82-008/03L-0 + (09:04:16, 18 December 2024)
- 05000029/LER-1982-007-03, /03L-0:on 820420,check Valve HC-V-119 Found Leaking from Inlet & Outlet Flanges.Caused by Relaxation of Bolting for Flanged Mating Surfaces.Bolting Replaced & Torqued + (09:04:18, 18 December 2024)
- ML20053B634 + (09:04:19, 18 December 2024)
- ML20053B633 + (09:04:21, 18 December 2024)
- 05000029/LER-1982-007, Forwards LER 82-007/03L-0 + (09:04:22, 18 December 2024)
- ML20053B629 + (09:04:28, 18 December 2024)
- 05000278/LER-1982-006-01, /01T-0:on 820504,GE Notified Util That Odyn Pressurization Event MCPR Values May Be Nonconservative. Caused by Nonconservative Value of Active Fuel Length Used in Reload 4 Odyn Transient Analysis + (09:04:30, 18 December 2024)
- 05000278/LER-1982-006, Forwards LER 82-006/01T-0.Detailed Event Analysis Submitted + (09:04:32, 18 December 2024)
- ML20053B624 + (09:04:34, 18 December 2024)
- 05000247/LER-1982-017-01, /01T-0:on 820505,motors for Central Control Room Air Conditioning Sys Booster Fans Failed.Caused by Previous Operation of 3-phase Motors in Single Phase Mode.Motors Replaced + (09:04:35, 18 December 2024)
- 05000247/LER-1982-017, Forwards LER 82-017/01T-0 + (09:04:37, 18 December 2024)
- 05000029/LER-1982-006-03, /03L-0:on 820420,primary Vent Stack Iodine Radiation Monitor Ratemeter Failed High.Caused by Failure of Air Dryer Due to Moisture.Detector Replaced + (09:04:39, 18 December 2024)
- ML20053B609 + (09:04:41, 18 December 2024)
- 05000029/LER-1982-006, Forwards LER 82-006/03L-0 + (09:04:43, 18 December 2024)