- ML20066F039 + (23:24:33, 16 December 2024)
- 05000455/LER-1990-010-11, :on 901220,severe Steam Leak Reported in Main Steam Tunnel.Caused by Improper Installation of Sample Probe During Initial Const.One Inch Nozzle Capped & Weld in Place by Temporary Alteration 90-2-66 + (23:24:37, 16 December 2024)
- 05000280/LER-1982-112-03, /03L-0:on 821017,one of Two Required Boric Acid Flow Paths to Core Became Unavailable & Boron Injection Tank Recirculation Terminated Due to Temporary Loss of Boric Acid Transfer Pump 1-CH-P-2A.Caused by Motor Trip + (23:24:40, 16 December 2024)
- ML20066F027 + (23:24:44, 16 December 2024)
- ML20066F025 + (23:24:45, 16 December 2024)
- ML20066F023 + (23:24:45, 16 December 2024)
- ML20066F019 + (23:24:46, 16 December 2024)
- ML20066F018 + (23:24:47, 16 December 2024)
- 0CAN118210, Provides Addl Info Re 820701 App R Exemption Requests,Per 821006 Meeting W/Nrc.Info Addresses Fire Zone Exemption Requests Being Considered for Denial by NRC + (23:24:53, 16 December 2024)
- 05000366/LER-1982-114-03, /03L-0:on 821011,with Unit Operating steady-state at 2415 Mwt,Inventory Trouble Alarm 2R44-S003 Received. Caused by Component Failure.Inverter Leg (Including Fan) Replaced,Tested & Returned to Svc + (23:24:56, 16 December 2024)
- 05000366/LER-1982-114, Forwards LER 82-114/03L-0 + (23:24:57, 16 December 2024)
- 05000440/LER-1990-040, :on 901218,RWCU Isolation Occurred While Correcting Cause of RWCU Sys Outboard Isolation Valves Not Opening.Caused by Personnel Error.Panel & Tools Inspected for Shorting & Fuses Replaced + (23:25:01, 16 December 2024)
- 1CAN019111, Responds to NRC 881220 Bulletin 88-011, Pressurizer Surge Line Thermal Stratification. Addl 30 Days Requested to Submit Notification That Actions Completed + (23:25:02, 16 December 2024)
- 2CAN019109, Responds to NRC 881220 Bulletin 88-011, Pressurizer Surge Line Thermal Stratification. Addl 30 Days Requested to Submit Notification That Actions Completed + (23:25:03, 16 December 2024)
- ML20066E988 + (23:25:05, 16 December 2024)
- ML20066E987 + (23:25:05, 16 December 2024)
- ML20066E985 + (23:25:06, 16 December 2024)
- ML20066E983 + (23:25:06, 16 December 2024)
- 05000324/LER-1982-120-03, /03L-0:on 821016,suppression Chamber Water Temp Recorder 2-CAC-TR-778 Was Recording Temps Intermittently. Caused by Recorder Print Actuation Solenoid Linkage Being Out of Adjustment.Linkage Adjusted + (23:25:16, 16 December 2024)
- 05000324/LER-1982-120, Forwards LER 82-120/03L-0 + (23:25:20, 16 December 2024)
- ML20066E969 + (23:25:21, 16 December 2024)
- ML20066E965 + (23:25:22, 16 December 2024)
- ML20066E968 + (23:25:22, 16 December 2024)
- ML20066E962 + (23:25:24, 16 December 2024)
- ML20066E957 + (23:25:25, 16 December 2024)
- 05000424/LER-1990-023-01, :on 901218,4160/480 Volt non-1E Transformer Experienced Internal Fault.Cause Indeterminate.Failed Transformer Replaced & Further Study of Possible Factors Which May Have Led to Failure in Progress + (23:25:27, 16 December 2024)
- 05000366/LER-1982-113-03, /03L-0:on 821009,during Testing,Discharge Check Valve on RHR Svc Water Pump Stuck Open.Caused by Corroded Flapper Shaft.Check Valve Rebuilt & Returned to Svc + (23:25:29, 16 December 2024)
- ML20066E952 + (23:25:30, 16 December 2024)
- ML20066E950 + (23:25:31, 16 December 2024)
- 05000336/LER-1990-022-01, :on 901115,svc Water Header cross-tie Valve, 2-SW-97A Found Open.Cause Unknown But Most Likely Due to Improper Positioning of cross-tie Valve.Procedures Will Be Changed & Valve Position Indication Enhanced + (23:25:33, 16 December 2024)
- 05000366/LER-1982-113, Forwards LER 82-113/03L-0 + (23:25:34, 16 December 2024)
- 05000366/LER-1990-013-03, :on 901220,three Valves Found Misaligned in Offgas post-treatment Radiation Monitoring Sys.Cause Inconclusive.Valve Lineups Verified,Standing Order Issued & Appropriate Procedures Revised + (23:25:43, 16 December 2024)
- ML20066E937 + (23:25:44, 16 December 2024)
- ML20066E933 + (23:25:49, 16 December 2024)
- 05000416/LER-1982-104-03, /03L-0:on 821014,w/no Fire or Smoke Present,Smoke Detection Zones 1-11 & 2-01 Alarmed & Would Not Reset.Caused by Dust Accumulation on Detectors N511H & N582A.Detectors Cleaned & Returned to Svc + (23:25:51, 16 December 2024)
- 05000416/LER-1982-104, Forwards LER 82-104/03L-0 + (23:25:53, 16 December 2024)
- ML20066E928 + (23:25:53, 16 December 2024)
- ML20066E924 + (23:25:54, 16 December 2024)
- 05000302/LER-1982-064-01, /01T-0:on 821029,containment Isolation Valve WDV-61 Declared Inoperable Due to Omission of Leak Rate Test Following Maint.Caused by Personnel Error.Personnel Reinstructed + (23:25:55, 16 December 2024)
- ML20066E922 + (23:26:00, 16 December 2024)
- ML20066E917 + (23:26:06, 16 December 2024)
- 05000261/LER-1982-014-03, /03L-0:on 821012,letdown Relief Valve CVC-203 Lifted & Did Not Reseat Completely.Cause of Valve Lifting Undetermined.Failure to Reseat Caused by Seat Damage Due to Valve Chatter.Valve Repaired & Returned to Svc + (23:26:14, 16 December 2024)
- 05000302/LER-1982-064, Forwards LER 82-064/01T-0 + (23:26:15, 16 December 2024)
- 05000374/LER-1990-013-08, :on 901217,MSIV Isolation Signals Received When MSIV Half Isolation Not Reset After Testing.Caused by Personnel Error.Isolation Signal Reset & Technicians Counseled + (23:26:18, 16 December 2024)
- 05000261/LER-1982-014, Forwards LER 82-014/03L-0 + (23:26:22, 16 December 2024)
- ML20066E886 + (23:26:34, 16 December 2024)
- AECM-82-543, Forwards Revision 12 to Emergency Procedulevel Control - Safety-Related, Incorporating NSSS Vendor Comments,Per SER & NUREG-0737,Item I.C.7,in Response to 821103 Commitment. Meetings Scheduled for 821117 & 18 + (23:26:38, 16 December 2024)
- ML20066E878 + (23:26:39, 16 December 2024)
- 05000324/LER-1982-130-01, /01T-0:on 821029,during Insp of drywell,through- Wall Linear Indication Discovered at Weld R-20,located on RHR Shutdown Cooling Suction Line Between Line Manual isolation,E11-F067 & Downstream Elbow.Caused by Flaw + (23:26:41, 16 December 2024)
- 05000324/LER-1982-130, Forwards LER 82-130/01T-0 + (23:26:47, 16 December 2024)
- 05000321/LER-1982-096-03, /03L-0:on 821008,oil Pump Trip Signal Received for B Recirculation Pump.Caused by Supply Breaker to Operating Oil Pump Being Placed in Off Position.Breaker Reset & B Recirculation Pump Returned to Svc + (23:26:48, 16 December 2024)