Search by property
Jump to navigation
Jump to search
This page provides a simple browsing interface for finding entities described by a property and a named value. Other available search interfaces include the page property search, and the ask query builder.
List of results
- 05000416/LER-1982-112, Forwards LER 82-112/03L-0 + (15:10:31, 16 December 2024)
- RBG-40677, Updates 911223 Response to GL 88-20,Suppl 4,informing That as Discussed Recently W/Nrc,Submittal Date for IPEEE for Plant Revised from 940724 to 1231.Reason for Extension Listed + (15:10:31, 16 December 2024)
- ML20070A060 + (15:10:32, 16 December 2024)
- RBG-40675, Responds to NRC Re Violations Noted in Insp Rept 50-458/94-08.Corrective Action:Individuals Were Counseled on Procedural & Adminstered Disciplinary Action + (15:10:33, 16 December 2024)
- ML20070A057 + (15:10:33, 16 December 2024)
- 05000416/LER-1982-118-03, /03L-0:on 821104,smoke Detectors in Piping Penetration,Rhr C Pump & LPCS Rooms of Auxiliary Bldg Annunciated W/O Presence of Smoke or Fumes.Caused by Accumulation of Dust on Detectors + (15:10:35, 16 December 2024)
- 3F0694-15, Provides Info Requested in Suppl 6 to GL 89-10,re Program Status,Schedular Extension & Response to NRC + (15:10:37, 16 December 2024)
- ML20070A051 + (15:10:37, 16 December 2024)
- ML20070A042 + (15:10:38, 16 December 2024)
- ML20070A039 + (15:10:40, 16 December 2024)
- ML20070A036 + (15:10:41, 16 December 2024)
- ML20070A037 + (15:10:41, 16 December 2024)
- ML20070A033 + (15:10:49, 16 December 2024)
- 05000325/LER-1982-132-03, /03L-0:on 821105,routine Surveillance Revealed Lack of Position Indication for PCIV 1-B32-F042B Located at RIP-X-243A.Caused by Blown Valve Operator Solenoid Power Supply Fuse.Fuse Replaced + (15:10:51, 16 December 2024)
- ML20070A028 + (15:10:52, 16 December 2024)
- 05000416/LER-1982-118, Forwards LER 82-118/03L-0 + (15:10:53, 16 December 2024)
- ML20070A014 + (15:10:58, 16 December 2024)
- ML20070A012 + (15:10:59, 16 December 2024)
- 05000325/LER-1982-132, Forwards LER 82-132/03L-0 + (15:11:00, 16 December 2024)
- ML20070A010 + (15:11:00, 16 December 2024)
- 05000321/LER-1982-097-01, /01T-0:on 821116,spent Fuel Rod Broken During Visual Insp of Several Spent Fuel Bundles.Caused by Severely Degraded Cladding at Point of Separation Due to Corrosion. Rod Will Be Placed Back Into Bundle & Bundle Flagged + (15:11:02, 16 December 2024)
- ML20070A004 + (15:11:03, 16 December 2024)
- 05000281/LER-1982-068-03, /03L-0:on 821112,during Performance of PT 18.6B, TV-CC-209B Would Not Close When Manually Operated from Control Room.Caused by Sticking Pilot Valve That Controls Air Flow from Valve Actuator.Pilot Valve Replaced + (15:11:04, 16 December 2024)
- ML20069Q681 + (15:11:07, 16 December 2024)
- ML20069Q676 + (15:11:08, 16 December 2024)
- ML20069Q675 + (15:11:09, 16 December 2024)
- 05000321/LER-1982-097, Forwards LER 82-097/01T-0.Detailed Event Analysis Encl + (15:11:12, 16 December 2024)
- ML20069Q663 + (15:11:12, 16 December 2024)
- 05000325/LER-1982-128-03, /03L-0:on 821103,primary Containment Atmosphere Oxygen Analyzer 1-CAC-1259-2 Tripped & Could Not Be Restarted.Caused by Failed Low Sample Flow Relay in Instrument Photohelic Unit.Photohelic Unit Replaced + (15:11:14, 16 December 2024)
- 05000281/LER-1982-069-03, /03L-0:on 821104,charging Pump Svc Water Pump 2-SW-P-10B Experienced Loss of Suction Pressure.Caused by Insufficient Npsh.Pump Vented to Restore NPSH + (15:11:16, 16 December 2024)
- 05000325/LER-1982-128, Forwards LER 82-128/03L-0 + (15:11:20, 16 December 2024)
- 05000281/LER-1982-065-03, /03L-0:on 821106,charging Pump Svc Water Pump 2-SW-P-10A Failed to Develop Sufficient Discharge Pressure. Caused by Corroded Carbon Steel Stud on Packing Gland Housing & Lack of Npsh.Packing Matl & Studs Replaced + (15:11:21, 16 December 2024)
- ML20069Q633 + (15:11:23, 16 December 2024)
- ML20069Q639 + (15:11:23, 16 December 2024)
- ML20069Q626 + (15:11:26, 16 December 2024)
- 05000261/LER-1982-016-03, /03L-0:on 821103,containment Fan Cooler HVH-3 Failed to Restart During Periodic Test Performance.Caused by Defective Time Delay Relay in Motor Breaker Control Circuit.Time Delay Relay Replaced + (15:11:28, 16 December 2024)
- ML20069Q616 + (15:11:29, 16 December 2024)
- 3F0694-01, Updates Status of Remaining Unimplemented GSIs Identified in NRC + (15:11:30, 16 December 2024)
- ML20069Q611 + (15:11:30, 16 December 2024)
- 05000366/LER-1982-125-03, /03L-0:on 821103,w/reactor Protection Sys (RPS) Alternate Supply Out of Svc for Maint,Rps Supply Over Voltage Relay Discovered Out of Calibr.Caused by Component Failure Due to Setpoint Drift.Relay Recalibr + (15:11:32, 16 December 2024)
- 05000366/LER-1982-125, Forwards LER 82-125/03L-0 + (15:11:36, 16 December 2024)
- 05000261/LER-1982-016, Forwards LER 82-016/03L-0 + (15:11:37, 16 December 2024)
- ML20069Q584 + (15:11:37, 16 December 2024)
- SNRC-1783, Informs of Expiration of Operator License for M Holland, Effective 901221 + (15:11:38, 16 December 2024)
- ML20069Q583 + (15:11:38, 16 December 2024)
- 05000259/LER-1982-093-01, /01T-0:on 821118,safety Injection Valves 4.2.B-31, 4.2.B-36 & 4.2.B-37 Left in Normally Open Position Contrary to Requirement That Valves Be Administratively Controlled W/ Power Lifted.Caused by Procedural Inadequacy + (15:11:40, 16 December 2024)
- ML20069Q575 + (15:11:41, 16 December 2024)
- 05000338/LER-1982-068-03, /03L-0:on 821102,charging Pumps & Boric Acid Flowpaths Rendered Inoperable.Caused by Maint on Charging Pump C Normal Suction Valve MOV-1270A Which Required Removal of Valve Bonnet.Valve Bonnet Replaced + (15:11:43, 16 December 2024)
- 05000416/LER-1982-128-03, /03L-0:on 821102,standby Diesel Generator 12 Placed in Maint Mode While Diesel Generator 11 Also Down for Maint.Caused by Need to Perform Regular Maint.Generator 11 Repaired & Returned to Svc on 821118 + (15:11:45, 16 December 2024)
- 05000338/LER-1982-068, Forwards LER 82-068/03L-0 + (15:11:46, 16 December 2024)
- 05000259/LER-1982-093, Forwards LER 82-093/01T-0 + (15:11:47, 16 December 2024)
- 05000416/LER-1982-128, Forwards LER 82-128/03L-0 + (15:11:47, 16 December 2024)