- BECO-83-278, Monthly Operating Rept for Oct 1983 + (12:19:23, 14 December 2024)
- ML20082D321 + (12:19:24, 14 December 2024)
- 3F0791-13, Notifies NRC of Plans to Utilize Seismic Experience Data to Demonstrate Seismic Adequacy for Future Commercial Grade Replacement Components & sub-components in Safety Related Systems + (12:19:25, 14 December 2024)
- 05000338/LER-1983-077-03, /03L-0:on 831017,three Snubbers Failed Visual Insp Periodic Tests.Two Found W/Uncovered Hydraulic Fluid Ports & Third W/Low Oil Level.Snubbers Replaced + (12:19:26, 14 December 2024)
- 05000413/LER-1991-011-01, :on 910514,violation Occurred Re Incorrect Flow Orifice Orientation.Caused by Mgt Deficiencies,Inappropriate Action & Defective Procedure.Training Conducted to Ensure Proper Orifice Plate Orientation + (12:19:28, 14 December 2024)
- 3F0791-12, Forwards to EPA Re Discharge of Hydrazine from Facility in Aug or Sept 1991.Toxicity Test Will Be Performed to Determine If Hydrazine Can Be Discharged W/O Exceeding Acute Toxicity Limits + (12:19:29, 14 December 2024)
- ML20082D301 + (12:19:30, 14 December 2024)
- ML20082D302 + (12:19:30, 14 December 2024)
- ML20082D300 + (12:19:31, 14 December 2024)
- 05000321/LER-1991-012-01, :on 910619,discovered Instrument Calibr of post-LOCA Radiation Monitoring Sys Radiation Detector 1D11-N022A-D Not Performed at Required Frequency.Caused by Procedural Deficiency.Procedures Revised + (12:19:35, 14 December 2024)
- ML20082D294 + (12:19:36, 14 December 2024)
- ML20082D292 + (12:19:36, 14 December 2024)
- BECO-83-282, Application for Amend to License DPR-35,changing Tech Specs Re Fire Protection.Areas Include Fire Suppression Water Sys,Spray &/Or Sprinkler Sys & Fire Hose Stations.Upcoming Complete Submittal Should Be Considered as Application + (12:19:37, 14 December 2024)
- ML20082D290 + (12:19:37, 14 December 2024)
- 05000395/LER-1983-123-03, /03L-0:on 831022,w/plant in Mode 1,inlet Damper to Auxiliary Bldg Charcoal Exhaust Filter Fan B Failed to Open.Caused by Linkage Binding.Linkage Cleaned & Lubricated + (12:19:39, 14 December 2024)
- ML20082D272 + (12:19:40, 14 December 2024)
- 05000254/LER-1991-010-02, :on 910614,RHR Shutdown Cooling Isolation Valves 1-1001-47 & 50 Isolated While Performing Instrument Functional Test.Caused by Procedural Deficiencies.Calibr & Functional Test Procedure Will Be Revised + (12:19:42, 14 December 2024)
- 05000348/LER-1983-072-03, /03L-0:on 831013,14 & 17,instrumentation Channel for Flow Transmitter FT-495 Declared Inoperable Due to Erroneous Indication.Cause Not Determined.Msivs Closed & Limiting Condition for Operation Cleared + (12:19:44, 14 December 2024)
- 05000348/LER-1983-071-03, /03L-0:on 831012,train B Air Conditioner Compressor Tripped.Caused by Solenoid Valve Linkage on Evaporator Line Being Out of Adjustment.Linkage Adjusted + (12:19:45, 14 December 2024)
- 05000361/LER-1983-128-03, /03L-0:on 831007,containment Airborne Radiation Monitor 2RT-7804 Channel C Discovered in Alarm Defeat.Cause Not Stated.Channel C Reset.Administrative Controls on Monitor Being Revised + (12:19:47, 14 December 2024)
- ML20082D252 + (12:19:48, 14 December 2024)
- ML20082D246 + (12:19:49, 14 December 2024)
- 05000361/LER-1983-132-03, /03L-0:on 831008,remote Shutdown Monitoring Instrumentation Pressure Indicator 2PI-1013C3 for Steam Generator E-089 Declared Inoperable.Caused by Failure of Lumigraph Assembly.Assembly Replaced + (12:19:50, 14 December 2024)
- ML20082D242 + (12:19:52, 14 December 2024)
- 05000373/LER-1983-100-03, Downstream Isolation Valve 1VQ050 Would Not Close.Caused by Dirty Torque Switch Contacts.Valve Manually Closed & Taken Out of Svc.Torque Cleaned + (12:19:53, 14 December 2024)
- 05000254/LER-1990-021, :on 900812,RHR Valve 1001-50 Failed to Open During Shutdown Cooling & Startup Operations.Caused by Thermal Binding of Valve & Hydraulic Lock of Valve Operator.Valve Manually Operated + (12:19:55, 14 December 2024)
- ML20082D229 + (12:19:57, 14 December 2024)
- ML20082D230 + (12:19:57, 14 December 2024)
- ML20082D222 + (12:19:58, 14 December 2024)
- ML20082D220 + (12:19:59, 14 December 2024)
- ML20082D215 + (12:19:59, 14 December 2024)
- ML20082D213 + (12:20:00, 14 December 2024)
- 05000346/LER-1983-051-03, Snubber SR-4-R-3 Found W/Oil in Reservoir.Caused by Cracked O-ring in Fluid Reservoir.Snubber Replaced W/Spare.Insp Interval Reduced from 18 to 12 Months + (12:20:01, 14 December 2024)
- ML20082D197 + (12:20:02, 14 December 2024)
- ML20082D192 + (12:20:03, 14 December 2024)
- ML20082D190 + (12:20:03, 14 December 2024)
- 3F1183-08, Forwards Revised Pages 12,28 & 42 to Detailed Control Room Design Review Program Plan,Per 831031 Submittal Re NUREG-0737,Item I.D.1, Control Room Design Reviews + (12:20:04, 14 December 2024)
- ML20082D186 + (12:20:04, 14 December 2024)
- ML20082D182 + (12:20:05, 14 December 2024)
- ML20082D181 + (12:20:06, 14 December 2024)
- ML20082D179 + (12:20:07, 14 December 2024)
- ML20082D178 + (12:20:09, 14 December 2024)
- PLA-1952, Responds to IE Bulletin 83-06 Nonconforming Matls Supplied by Tube-Line Corp. Analysis Revealed Elbows Meet Requirements of ASME SA-403 Type 304 Spec & Were Furnished in solution-treated,nonsensitized Condition + (12:20:10, 14 December 2024)
- ML20082D171 + (12:20:11, 14 December 2024)
- JAFP-91-0410, Advises That Util Unable to Meet Completion Date of Jul 1991 to Correct Violations Noted in Insp Rept 50-333/90-17 Re Procedures for Radiological Protection Program.Review Completion Extended Until 910901 + (12:20:15, 14 December 2024)
- ML20082D163 + (12:20:15, 14 December 2024)
- ML20082D157 + (12:20:16, 14 December 2024)
- BECO-83-289, Responds to NRC Requesting Plans & Schedules for Mods Associated w/NUREG-0737,Item II.K.3.22, Automatic Switchover of RCIC Sys Suction. Mod Will Be Factored Into long-term Program + (12:20:17, 14 December 2024)
- ML20082D150 + (12:20:17, 14 December 2024)
- ML20082D144 + (12:20:19, 14 December 2024)
- ML20082D149 + (12:20:19, 14 December 2024)