Search by property
Jump to navigation
Jump to search
This page provides a simple browsing interface for finding entities described by a property and a named value. Other available search interfaces include the page property search, and the ask query builder.
List of results
- 2CAN049511, Application for Amend to License NPF-6,revising Spec 3.6.1.3 to Allow Entry & Exit of Containment Air Locks to Perform Maint on Air Lock Components + (12:18:54, 14 December 2024)
- ML20082D411 + (12:18:54, 14 December 2024)
- ML20082D405 + (12:18:55, 14 December 2024)
- ML20082D400 + (12:18:55, 14 December 2024)
- ML20082D392 + (12:18:56, 14 December 2024)
- ML20082D391 + (12:18:57, 14 December 2024)
- AECM-83-0706, Interim Deficiency Rept Re Possible Defect on Wj Woolley Co Drywell Personnel Airlock Seals.Evaluation of Reportability Per Part 21 Continuing + (12:18:58, 14 December 2024)
- ML20082D389 + (12:18:58, 14 December 2024)
- RBG-16-352, Final Deficiency Rept DR-119 Re Threaded Weld Studs for Cable Tray Supports.Item Determined Not Reportable Under 10CFR50.55(e) + (12:18:59, 14 December 2024)
- 2CAN049510, Application for Amend to License NPF-6,revising TS Surveillances 4.3.4.1.2.a & 4.3.4.1.2.b Re Turbine Valve Testing Interval + (12:19:00, 14 December 2024)
- NRC-95-4421, Forwards Proposed Criteria for AP600 safety-related & non- Safety Related Testing.In Addition,W Requests Meeting Be Held to Discuss NRC Comments on Proposed Criteria + (12:19:00, 14 December 2024)
- 05000423/LER-1995-003-01, :on 950304,separate Components in Independent Trains of ECCS Declared Inoperable Due to Loose Terminal Block in Exhaust Fan Circuitry.Tightened Terminal Block & Secured Retaining Cover + (12:19:02, 14 December 2024)
- ML20082D358 + (12:19:04, 14 December 2024)
- ML20082D356 + (12:19:05, 14 December 2024)
- ML20082D351 + (12:19:06, 14 December 2024)
- ML20082D353 + (12:19:06, 14 December 2024)
- 05000336/LER-1995-010, :on 950303,determined That Each Circuit Contained an Auxiliary Contact Off Smoke Detector Circuit Which de-energizes Fan During Fire.Caused by Inadequate Design.Design Change Being Processed + (12:19:08, 14 December 2024)
- ML20082D347 + (12:19:12, 14 December 2024)
- ML20082D344 + (12:19:12, 14 December 2024)
- ML20082D342 + (12:19:13, 14 December 2024)
- 3F0791-08, Forwards Comprehensive Annual Financial Rept,City of Ocala, Fl Fy Ended Sept 1990 & City of Bushenell,Fl General Purpose Financial Statments for Fy Ended Sept 1990 + (12:19:14, 14 December 2024)
- ML20082D334 + (12:19:16, 14 December 2024)
- 05000483/LER-1991-002, :on 910619,tech Spec Violation Occurred Re Blown Fuse for Ultimate Heat Sink Cooling Tower Fan Causing Inoperability of Both Trains of Safety Injection Pumps. Fuses Replaced + (12:19:18, 14 December 2024)
- 05000374/LER-1991-004-08, :on 910621,pressure Differential Switch Found Failed.Caused by Diaphram Failure.Cause of Diaphram Failure Unknown.Replacement Switch Installed,Calbr & Functionally Tested Satisfactorily + (12:19:20, 14 December 2024)
- 05000327/LER-1983-136-03, /03L-0:on 831018,diesel Generator 2B-B Declared Inoperable Due to Loss of Associated 125-volt Dc Battery Bank.Caused by Cell 28 Specific Gravity Below Allowable Value.Cell Replaced + (12:19:22, 14 December 2024)
- BECO-83-278, Monthly Operating Rept for Oct 1983 + (12:19:23, 14 December 2024)
- ML20082D321 + (12:19:24, 14 December 2024)
- 3F0791-13, Notifies NRC of Plans to Utilize Seismic Experience Data to Demonstrate Seismic Adequacy for Future Commercial Grade Replacement Components & sub-components in Safety Related Systems + (12:19:25, 14 December 2024)
- 05000338/LER-1983-077-03, /03L-0:on 831017,three Snubbers Failed Visual Insp Periodic Tests.Two Found W/Uncovered Hydraulic Fluid Ports & Third W/Low Oil Level.Snubbers Replaced + (12:19:26, 14 December 2024)
- 05000413/LER-1991-011-01, :on 910514,violation Occurred Re Incorrect Flow Orifice Orientation.Caused by Mgt Deficiencies,Inappropriate Action & Defective Procedure.Training Conducted to Ensure Proper Orifice Plate Orientation + (12:19:28, 14 December 2024)
- 3F0791-12, Forwards to EPA Re Discharge of Hydrazine from Facility in Aug or Sept 1991.Toxicity Test Will Be Performed to Determine If Hydrazine Can Be Discharged W/O Exceeding Acute Toxicity Limits + (12:19:29, 14 December 2024)
- ML20082D301 + (12:19:30, 14 December 2024)
- ML20082D302 + (12:19:30, 14 December 2024)
- ML20082D300 + (12:19:31, 14 December 2024)
- 05000321/LER-1991-012-01, :on 910619,discovered Instrument Calibr of post-LOCA Radiation Monitoring Sys Radiation Detector 1D11-N022A-D Not Performed at Required Frequency.Caused by Procedural Deficiency.Procedures Revised + (12:19:35, 14 December 2024)
- ML20082D294 + (12:19:36, 14 December 2024)
- ML20082D292 + (12:19:36, 14 December 2024)
- BECO-83-282, Application for Amend to License DPR-35,changing Tech Specs Re Fire Protection.Areas Include Fire Suppression Water Sys,Spray &/Or Sprinkler Sys & Fire Hose Stations.Upcoming Complete Submittal Should Be Considered as Application + (12:19:37, 14 December 2024)
- ML20082D290 + (12:19:37, 14 December 2024)
- 05000395/LER-1983-123-03, /03L-0:on 831022,w/plant in Mode 1,inlet Damper to Auxiliary Bldg Charcoal Exhaust Filter Fan B Failed to Open.Caused by Linkage Binding.Linkage Cleaned & Lubricated + (12:19:39, 14 December 2024)
- ML20082D272 + (12:19:40, 14 December 2024)
- 05000254/LER-1991-010-02, :on 910614,RHR Shutdown Cooling Isolation Valves 1-1001-47 & 50 Isolated While Performing Instrument Functional Test.Caused by Procedural Deficiencies.Calibr & Functional Test Procedure Will Be Revised + (12:19:42, 14 December 2024)
- 05000348/LER-1983-072-03, /03L-0:on 831013,14 & 17,instrumentation Channel for Flow Transmitter FT-495 Declared Inoperable Due to Erroneous Indication.Cause Not Determined.Msivs Closed & Limiting Condition for Operation Cleared + (12:19:44, 14 December 2024)
- 05000348/LER-1983-071-03, /03L-0:on 831012,train B Air Conditioner Compressor Tripped.Caused by Solenoid Valve Linkage on Evaporator Line Being Out of Adjustment.Linkage Adjusted + (12:19:45, 14 December 2024)
- 05000361/LER-1983-128-03, /03L-0:on 831007,containment Airborne Radiation Monitor 2RT-7804 Channel C Discovered in Alarm Defeat.Cause Not Stated.Channel C Reset.Administrative Controls on Monitor Being Revised + (12:19:47, 14 December 2024)
- ML20082D252 + (12:19:48, 14 December 2024)
- ML20082D246 + (12:19:49, 14 December 2024)
- 05000361/LER-1983-132-03, /03L-0:on 831008,remote Shutdown Monitoring Instrumentation Pressure Indicator 2PI-1013C3 for Steam Generator E-089 Declared Inoperable.Caused by Failure of Lumigraph Assembly.Assembly Replaced + (12:19:50, 14 December 2024)
- ML20082D242 + (12:19:52, 14 December 2024)
- 05000373/LER-1983-100-03, Downstream Isolation Valve 1VQ050 Would Not Close.Caused by Dirty Torque Switch Contacts.Valve Manually Closed & Taken Out of Svc.Torque Cleaned + (12:19:53, 14 December 2024)
- 05000254/LER-1990-021, :on 900812,RHR Valve 1001-50 Failed to Open During Shutdown Cooling & Startup Operations.Caused by Thermal Binding of Valve & Hydraulic Lock of Valve Operator.Valve Manually Operated + (12:19:55, 14 December 2024)