- NRC-91-0128, Forwards Response to Generic Ltr 91-06, Resolution of Generic Issue A-30, Adequacy of Safety-Related DC Power Supplies + (08:12:21, 14 December 2024)
- ML20085K967 + (08:12:24, 14 December 2024)
- ML20085K971 + (08:12:24, 14 December 2024)
- ML20085K965 + (08:12:25, 14 December 2024)
- 05000259/LER-1983-052-03, /03L-0:on 830912,while Performing Surveillance Instruction 4.11.C.3 & 4 on Reactor Bldg Elevation 593 Fixed Spray Zone 1E Heat Detector Relay Discovered Inoperable. Caused by Random Failure.Relay Replaced + (08:12:27, 14 December 2024)
- ML20085K957 + (08:12:28, 14 December 2024)
- ML20085K958 + (08:12:28, 14 December 2024)
- ML20085K954 + (08:12:29, 14 December 2024)
- ML20085K952 + (08:12:29, 14 December 2024)
- 05000251/LER-1983-015-03, /03L-0:on 830913,local Leak Rate Test on Containment Personnel Hatch Airlock Revealed Leakage in Excess of Tech Specs.Caused by Equalizing Vent Valve on Inner Door Not Fully Closed.Valve Tightened + (08:12:31, 14 December 2024)
- ML20085K948 + (08:12:32, 14 December 2024)
- RBG-16-179, Summarizes Analysis of Inclusion of Redundant Chlorine & Ammonia Detectors in Control Bldg Ventilation Sys Design. NRC Reconsideration of Requirement Requested.Meeting in Bethesda,Md in Nov Proposed + (08:12:36, 14 December 2024)
- ML20085K939 + (08:12:37, 14 December 2024)
- ML20085K936 + (08:12:38, 14 December 2024)
- ML20085K931 + (08:12:39, 14 December 2024)
- 05000316/LER-1983-094-03, /03L-0:on 830914,during Normal Operation,Loop 4 Steam Line Pressure Channel 2 Removed from Svc Because of Indications Instrument Line Obstructed.Cause Not Stated. Instrument Isolation Valve Bonnet Removed + (08:12:40, 14 December 2024)
- ML20085K924 + (08:12:42, 14 December 2024)
- BSEP-95-0291, Forwards Engineering Svc Request ESR 95-00765,Rev 2, Unit 1 Core Shroud Evaluation Based on B11OR1 Insp Results + (08:12:43, 14 December 2024)
- ML20085K913 + (08:12:45, 14 December 2024)
- ML20085K912 + (08:12:46, 14 December 2024)
- BSEP-95-0269, Forwards Review of Preliminary Accident Sequence Precursor Analysis + (08:12:47, 14 December 2024)
- 05000316/LER-1983-072, Forwards Updated LER 83-072/03X-1 & LER 83-094/03L-0 + (08:12:48, 14 December 2024)
- ML20085K895 + (08:12:48, 14 December 2024)
- ML20085K892 + (08:12:49, 14 December 2024)
- 05000423/LER-1995-011-01, :on 950515,mussel Shells Found in Recirculation Spray Sys Heat Exchanger.Caused by High Density of Mussel Plantigrades in Spring 1994.Hypochlorite Metering Pumps Installed + (08:12:50, 14 December 2024)
- ST-HL-AE-3884, Application for Amends to Licenses NPF-76 & NPF-80,deleting Tech Spec Table 5.7-1, Component Cyclic or Transient Limits Which Is Implemented by Plant Procedure Per Requirements in Updated FSAR + (08:12:51, 14 December 2024)
- ML20085K887 + (08:12:52, 14 December 2024)
- 05000315/LER-1983-094-03, /03L-0:on 830922,4-kV Loss of Voltage Relays 27-1-T11D & 27-3-T11D Exceeded Tolerance.Caused by Instrument Drift.Relays Reset + (08:12:54, 14 December 2024)
- RBG-16-170, Interim Deficiency Rept DR-135.Investigation Incomplete. Next Rept Will Be Submitted by 831130 + (08:12:55, 14 December 2024)
- 05000315/LER-1983-093-03, /03L-0:on 830915,false Event Recorded on Diesel Generator Cd Room Peak Recording Accelerometer.Cause Not Stated.Personnel Cautioned + (08:12:56, 14 December 2024)
- ST-HL-AE-5110, Responds to Violations Noted in Insp Rept 50-498/95-06. Corrective Actions:Problem Solving Discussion Seminar Conducted W/Appropriate Supervision + (08:12:57, 14 December 2024)
- BSEP-95-0290, Forwards Plant Annual Radiation Exposure Rept Data for 940101-1231 + (08:13:08, 14 December 2024)
- ML20085K867 + (08:13:08, 14 December 2024)
- ML20085K862 + (08:13:09, 14 December 2024)
- ML20085K861 + (08:13:11, 14 December 2024)
- ST-HL-AE-1017, Final Deficiency Rept Re Computer Program Verification. Initially Reported on 810508.Verification Program for Review & Acceptance of Brown & Root Computer Calculations Implemented + (08:13:12, 14 December 2024)
- ML20085K851 + (08:13:13, 14 December 2024)
- 05000336/LER-1995-021, :on 950517,design Error Confirmed to Be Present in Esas.Caused by ESAS Design Deficiency.Delay Circuit Installed on SIAS Actuation Module Relay Output + (08:13:14, 14 December 2024)
- ML20085K842 + (08:13:17, 14 December 2024)
- ML20085K838 + (08:13:18, 14 December 2024)
- ML20085K833 + (08:13:19, 14 December 2024)
- ML20085K837 + (08:13:19, 14 December 2024)
- ML20085K826 + (08:13:20, 14 December 2024)
- ML20085K825 + (08:13:20, 14 December 2024)
- 05000416/LER-1983-139-03, /03L-0:on 830912,Div 1 Reactor Protective Sys Motor Generator Set Tripped,Causing Half Scram Signal & Loss of Shutdown Cooling.Caused by Motor Winding Short.Motor Replaced + (08:13:22, 14 December 2024)
- ML20085K813 + (08:13:23, 14 December 2024)
- RBG-16-169, Interim Deficiency Rept DR-134.Investigation Incomplete. Next Rept Will Be Submitted by 831123 + (08:13:23, 14 December 2024)
- 05000298/LER-1983-014-03, /03L-0:on 830915,during Surveillance Testing, Pressurization of Suppression Chamber Air Space Noted During HPCI Turbine Operation.Caused by Error in Vacuum Breaker Design/Installation.Breaker Replaced + (08:13:25, 14 December 2024)
- 05000249/LER-1983-035-01, /01T-0:on 831004,during Drywell Insp,Water Observed Leaking from Recirculation Pump Bowl Drain A. Caused by 2-inch Crack on Tee.Affected Piping Will Be Cut Out.Isolation Valves & Tee Will Be Replaced + (08:13:27, 14 December 2024)
- ML20085K784 + (08:13:28, 14 December 2024)
- ML20085K778 + (08:13:29, 14 December 2024)