- 05000331/LER-1995-011, :on 951019,during Surveillance Test Procedure, a Sdg Outboard Bearing Temp Reached 205 F.Caused by Incorrectly Installed Room Temp Controller.Controller Reconfigured + (ML20094R773)
- ML20094R777 + (ML20094R777)
- ML20094R790 + (ML20094R790)
- ML20094R824 + (ML20094R824)
- 05000325/LER-1992-007, :on 920310,12 H Noble Gas Grab Sample for Reactor Bldg Radioactive Gaseous Effluent Monitoring Instrumentation Overdue.Caused by Chemistry Technician Error.Use of Nonroutine Log Enhanced + (ML20094R829)
- ML20094R831 + (ML20094R831)
- ML20094R832 + (ML20094R832)
- ML20094R854 + (ML20094R854)
- 05000458/LER-1995-009-02, :on 951101,surveillance Was Missed Due to Error in Change of Surveillance Test Interval Scheduling.Caused by Human Error & Inadequate Review.Discussed Inappropriate Schedule Frequency Change + (ML20094R856)
- ML20094R863 + (ML20094R863)
- ST-HL-AE-1109, Responds to NRC Re Violations Noted in IE Insp Repts 50-498/84-04 & 50-499/84-04.Corrective Actions:Site Std for Nonconformance Reporting Revised + (ML20094R905)
- BSEP-95-0513, Requests Approval for Plant to Use Alternative to ASME B&PV Code Requirements for Preparation & Submittal of Inservice Summary Rept + (ML20094R916)
- 05000369/LER-1992-001-02, :on 920116,Unit 1 Shutdown Due to Leakage Increased to 235 Gallons Per Day.Caused by Failure to Remove Steam Generator Tube from Svc.Three Tubes Removed from Steam Generator 2c for Lab Analysis + (ML20094R920)
- ML20094R931 + (ML20094R931)
- 05000302/LER-1995-024, :on 951030,annubar Flow Tap Orientation Caused Seismic Qualification Concerns Resulted in Operation Outside Design Basis of Plant.Caused by Personnel Error.Placed Aft Under Administrative Control + (ML20094R932)
- 05000277/LER-1992-001-03, :on 920310,determined That PCIS LSFT for Group III Isolation Defeated Automatic Capability of PCIS Group III Channels.Caused by No Formal 10CFR50.59 Review Being Performed.Pcis & LSFT Were Deleted + (ML20094R937)
- 05000301/LER-1992-001, Forwards LER 92-001-00.Rept Initially Submitted on 920317 as Improperly Numbered LER 92-003-00.Requests That LER 92-003-00 Be Withdrawn & Replaced W/Encl + (ML20094R938)
- 05000301/LER-1992-001-01, :on 920217,one Channel of Overtemp Delta T Protection Rendered Inoperable During Performance of power- Range Axial Offset Calibr.Caused by Personnel Error.Channel Restored to Svc & Procedure Revised + (ML20094R943)
- 05000249/LER-1984-005-07, :on 840716,east LPCI Corner Room Submarine Door Found Open.Caused by Stationmen Working in Area.Door Closed & Tech Specs Requiring Door to Be Closed Emphasized. Annunciators Will Be Installed + (ML20094R952)
- AECM-84-0422, Monthly Operating Rept for Jul 1984 + (ML20094R953)
- 05000271/LER-1992-010, :on 920308,12 & 17,liquid Radwaste Valve, Feedwater Check Valve & CRD Valves Found W/Seat Leakage Above Ts.Caused by Equipment Wear/Age & Mfg Defect.Valves Repaired,Replaced or Successfully Retested + (ML20094R972)
- ML20094S016 + (ML20094S016)
- ML20094S035 + (ML20094S035)
- ML20094S043 + (ML20094S043)
- 05000285/LER-1995-006, :on 950824,improper Start of Number 1 DG Caused Rt.Caused by Inadequate Administrative Controls on Critical Parameter.Provided Addl Administrative Controls to Ensure That Governor Was Operated Correctly + (ML20094S046)
- 05000458/LER-1995-007, :on 950905,HPCS Unit Cooler Fan Hub Failed. Caused by Casting Defect Consisting of High Porosity & Iron Rich Precipitates Along Grain Boundaries.Repaired & Restored HPCS Unit Cooler to Operational Status + (ML20094S054)
- ML20094S060 + (ML20094S060)
- ML20094S096 + (ML20094S096)
- 05000325/LER-1992-006, :on 920312,discovered That Instrument Rack Supports to Floor Corroded Through.Caused by High Humidity, Salt Air Environ in Intake Canal.Mounting Bolts Repaired by Replacing Bolts W/Stainless Steel + (ML20094S147)
- ML20094S148 + (ML20094S148)
- ML20094S149 + (ML20094S149)
- ML20094S153 + (ML20094S153)
- ML20094S157 + (ML20094S157)
- ML20094S169 + (ML20094S169)
- ML20094S172 + (ML20094S172)
- ML20094S184 + (ML20094S184)
- ML20094S198 + (ML20094S198)
- U-602526, Submits Written Confirmation of Implementation of Plant Mod for Compliance W/Station Blackout Rule + (ML20094S208)
- NRC-95-0131, Comment on Petition for Rulemaking PRM-50-62 Re Changes to QA Program.Agrees That Changes Needed in Process for QA Program Revs + (ML20094S209)
- ML20094S211 + (ML20094S211)
- ML20094S234 + (ML20094S234)
- ML20094S240 + (ML20094S240)
- ML20094S241 + (ML20094S241)
- ML20094S242 + (ML20094S242)
- ML20094S243 + (ML20094S243)
- ML20094S245 + (ML20094S245)
- ML20094S246 + (ML20094S246)
- ML20094S249 + (ML20094S249)
- PM-91-075, Monthly Operating Rept for Apr 1991 for Shoreham Nuclear Power Station + (ML20094S254)
- PM-91-037, Monthly Operating Rept for Feb 1991 for Shoreham Nuclear Power Station + (ML20094S259)
- ML20094S262 + (ML20094S262)