List of results
- ML20086E893 + (ML20086E893)
- ML20086E906 + (ML20086E906)
- ML20086E914 + (ML20086E914)
- ML20086E930 + (ML20086E930)
- 05000455/LER-1991-004-13, :on 911030,spurious Train B Feedwater Isolation Signal Generated,Causing Tempering Line Flow Control & Downstream Isolation Valves to Close.Caused by Failure of Logic Card.Isolation Reset + (ML20086E943)
- ML20086E980 + (ML20086E980)
- ML20086E997 + (ML20086E997)
- ML20086F020 + (ML20086F020)
- ML20086F026 + (ML20086F026)
- 05000261/LER-1977-008, :on 770424,control Rod N-9 Failed to Fall Into Core Following Power Reactor Trip.Caused by Drive Mechanism Malfunction.Shutdown Bank a Withdrawn & Realigned w/N-9.Rod Drop Test Performed + (ML20086F036)
- 05000261/LER-1977-007, :on 770422,isolation Valve for Compressed Air Supply Discovered Closed.Caused by Personnel Error.Valve Opened.Penetration Pressurized + (ML20086F037)
- 05000261/LER-1977-006, :on 770326,during 0% Power,Valve V2-14A Failed to Open While Attempting to Feed Steam Generator a Through Valve W/Steam Driven Auxiliary Feedwater Pump.Caused by Binding Valve Seat Surfaces.Valve Recycled + (ML20086F038)
- 05000261/LER-1977-005, :on 770324,containment Spray Pump a Discovered Not in Svc.Caused by Personnel Error.Personnel Instructed to Review Applicable Tech Specs Re Equipment Required for Critical Plant Operations + (ML20086F039)
- 05000261/LER-1977-004, :on 770317,while Constant Axial Offset Control Out of Svc,Axial Flux Differences Not Logged as Required Per Plant Procedures.Caused by Failure to Maintain Log.Operating Procedures & Out of Svc Logs Combined + (ML20086F040)
- 05000261/LER-1977-003, :on 770131,during Normal Operation,Boric Acid Transfer Pump B Tripped Due to High Pump Motor Temp Cutout. Caused by Improper Setting of Motor Temp Cutout.Motor Temp Cutout Reset.New Stator Installed + (ML20086F042)
- 05000261/LER-1977-002, :on 770125,flow Paths from Boric Acid Storage Tanks Made Inoperable for Maint of Two Chemical & Vol Control Sys Valves.Caused by Personnel Error.Personnel Lectured to Ensure Tech Specs Understood + (ML20086F046)
- 05000261/LER-1977-001, :on 770124,during Normal Operations Boric Acid Transfer Pump B Tripped Due to High Pump Motor Temp Cutout. Caused by Equipment Malfunction.Pump Balance Line Cleaned & Restarted + (ML20086F047)
- 05000277/LER-1977-007-03, /03L:on 761121,rod Block Monitor Functional Surveillance Test Not Performed for Nov 1976.Caused by Personnel Error.Test Performed on Schedule in Dec + (ML20086F048)
- 05000277/LER-1977-006-03, /03L:on 770111,transient in-core Machine Probe Travelled Beyond in-shield Limit Switch During Withdrawal. Caused by Personnel Misoperation & Short Circuit in Backup Circuit.Short Corrected + (ML20086F049)
- 05000277/LER-1977-004-01, /01T:on 770106,main Steam Relief Valve 71E Failed Open.Caused by Excessive Pilot Valve Seat Leakage.Valve 71D Replaced.Pilot Valve Section Replaced on Valves 71E & 71K + (ML20086F050)
- 05000277/LER-1977-003-01, /01T:on 770103,insp of Four Relief Valves Revealed Delamination & Overheating of Air Operator Diaphragms.Cause Not Stated.Diaphragms Replaced + (ML20086F051)
- 05000277/LER-1977-002-03, /03L:on 770102,control Rods 30-27 & 54-23 Did Not Fully Insert on Auto Scram Signal.Cause Undetermined.Rods Successfully scram-timed & friction-tested + (ML20086F052)
- 05000277/LER-1977-001-01, /01T:on 770104,reservoirs of Hydraulic Snubber Relief Valves RV-71E & SS-C6 Found Empty.Caused by Reservoir Leak & Loose Locking Nut Allowing Unit to Turn Upside Down. Repairs Made & Reservoirs Filled + (ML20086F053)
- ML20086F069 + (ML20086F069)
- ML20086F073 + (ML20086F073)
- RBG-41682, Informs That Pending Resolution of 950525 Submittal of 10CFR50.90 Change,Requesting Exception to Physical Security Plan,C/A Commitment Per Violation 50-458/9505-01 to Modify Backup Power Supply for Security Sys Placed on Hold + (ML20086F077)
- ML20086F080 + (ML20086F080)
- ML20086F101 + (ML20086F101)
- ML20086F110 + (ML20086F110)
- 05000000/LER-1977-005-01, /1P:on 770114,failure of High Pressure Svc Water/Emergency Svc Water & Emergency Cooling Water Pumps to Meet FSAR Seismic Requirements Noted.Caused by Change in Calculational Techniques.Bolts/Restraints to Be Added + (ML20086F132)
- 05000000/LER-1977-005, Updated LER 77-005/1T:on 770114,failure of High Pressure Svc Water/Emergency Svc Water & Emergency Cooling Water Pumps to Meet FSAR Seismic Requirements Noted.Caused by Change in Calculation Techniques + (ML20086F137)
- ML20086F145 + (ML20086F145)
- 05000293/LER-1991-026, :on 911030 & 31,automatic Actuations Occurred in RWCU Sys Portion of Primary Containment Isolation Control Sys.Possibly Caused by Momentary Fluctuations in RWCU Sys Flow.High Flow Sensor Settings Verified + (ML20086F148)
- ML20086F157 + (ML20086F157)
- BECO-LTR-91-999, Responds to Violations Noted in Electrical Distribution Sys Functional Insp Rept 50-293/91-80 on 910722-26.Corrective Actions:Personnel Received Root Cause Analysis Training & Root Cause Analysis & Evaluation Procedures to Be Revised + (ML20086F158)
- ML20086F161 + (ML20086F161)
- RBG-35-981, Informs of Two Deviations Between Plant & Simulator Resulting from Mods to Plant Control Room,Per Exceptions Noted in 901217 Submittal of NRC Form 474, Simulation Facility Certification + (ML20086F167)
- ML20086F176 + (ML20086F176)
- ML20086F181 + (ML20086F181)
- 05000454/LER-1991-005-08, :on 911027,Mode 4 Entered W/Containment Spray Sys & ECCS Recirculation Sump Isolation Valves Inoperable. Caused by Control Room Personnel Failure.Mode Change Checklists Will Be Revised + (ML20086F187)
- BECO-LTR-91-995, Ack Receipt of Requesting That Util Respond to Review Comments of T Urbanik (Kld Assoc) Re Evacuation Time Estimate Sensitivity Study for Beach Populations.Util Already Responded to Issues Raised by Kld Assoc + (ML20086F193)
- 05000277/LER-1976-065-36, /03L:on 760828,APRM a Trip Points Found to Be Less Conservative than Tech Spec Required W/Reactor in Run Mode. Caused by Instrument Drift.Aprm Recalibr & Returned to Svc + (ML20086F195)
- 05000277/LER-1976-064-03, /03L:on 760829,containment Atmosphere Dilution Sys Declared Inoperable Because Liquid Nitrogen Tank Relief Valve Failed to Reseat,Blowing Down Content Below Limits. Blowback Ring Replaced + (ML20086F196)
- 05000277/LER-1976-063-01, /01T:on 760825,suppressor on Recirculation Pump B Found W/Empty Reservoir.Caused by Broken Sight Glass.Site Glass Replaced & Suppressor Refilled & Checked for Leaks + (ML20086F197)
- 05000277/LER-1976-062-01, /01T:on 760825,suppressor on Main Steam Relief Valve Discharge Line C Found W/Empty Reservoir.No Apparent Cause Found.Suppressor Refilled & Leak Checked Prior to Reinstallation + (ML20086F198)
- 05000277/LER-1976-061-03, /03L:on 760823,drywell Radioactive Gas Sample Pumps Tripped & Sample Sys Isolated,Removing Sys from Svc. Relay GE CR120AD04041AA Failed in Fail Safe Position.Relay Replaced & Sys Returned to Svc + (ML20086F199)
- 05000277/LER-1976-060-03, /03L:on 760821,improper Sample Obtained from Drywell Radioactive Gas Sampling Sys Due to Leakage.Caused by Loose Fitting on Electrical Penetration.Fitting Tightened + (ML20086F200)
- 05000277/LER-1976-059-03, /03L:on 760824,outboard Drywell Purge Exhaust Valve A0-2507 Found Partially Closed.Caused by Sheared Alignment Key.Valve & Actuator Realigned & New Key Installed + (ML20086F202)
- NRC-95-4502, Forwards Proprietary Notrump Preliminary Validation Rept for Osu Tests. Encl Rept Withheld Per 10CFR2.790 + (ML20086F203)
- 05000277/LER-1976-058-01, /01T:on 760820,torus Vol Fell Below Tech Spec Level.Caused by Defective Positioner on Control Valve Returning Condensate to Torus.Valve Positioner Repaired & Valve Returned to Svc + (ML20086F205)
- 05000277/LER-1976-056-03, /03L:on 760803,control Room Ventilation Radiation Monitor RIS-0160A Displayed Abnormal Reading.Caused by Failure of Integrating Circuit in Exponent Counting Circuit of Trapelo DRM-100 Digital Process Radiation Monitor + (ML20086F207)