Search by property
Jump to navigation
Jump to search
This page provides a simple browsing interface for finding entities described by a property and a named value. Other available search interfaces include the page property search, and the ask query builder.
List of results
- ML20083F651 + (ML20083F651)
- ML20083F652 + (ML20083F652)
- 05000327/LER-1983-177-03, /03L-0:on 831122,diesel Generator 2A-A Declared Inoperable Due to Failure to Trip on Demand During Relay Testing.Cause of Failure of Differential Relay 87A Unknown. Relay Replaced + (ML20083F657)
- BSEP-83-3994, Nonroutine 30-day Radiological Environ Event Rept 2-SR-83-32 Re Gamma Analysis Results of Bottom Sediment sample.Co-60 Activity Increased by Factor of 10 Above MDA + (ML20083F658)
- 05000275/LER-1983-030-03, /03L-0:on 831116,discovered That Tech Spec Surveillance Requirement 4.3.3.3.1 for Channel Functional Test of Triaxial Time History Accelographs Not Performed. Caused by Personnel Error + (ML20083F660)
- ML20083F663 + (ML20083F663)
- GO2-83-108, Responds to NRC Re Violations Noted in IE Insp Rept 50-397/83-14.Corrective Actions:Sampling Plan Developed to Provide 95% Confidence Level That Less than 5% Defects Exist in Sample Lot + (ML20083F666)
- 05000325/LER-1983-054-03, /03L-0:on 831119,routine Surveillance Revealed That Div I Primary Containment Atmosphere Oxygen/Hydrogen Analyzer Not Showing Expected Decrease in Oxygen Concentration.Caused by Worn Seals + (ML20083F670)
- 05000289/LER-1983-044-01, /01T-1:on 831114,during Walkdown,Emergency Feedwater Automatic Initiation Redundant Circuits Discovered Routed in Same Cable Bundle.Caused by Failure to Include Circuits in Upgrade Design + (ML20083F671)
- ML20083F674 + (ML20083F674)
- 05000220/LER-1983-042-03, /03L-0:on 831122,fuel Zone Water Level Measuring Sys (Accurex) Taken Out of Svc to Modify Program to Improve Accuracy.Accurex Modified Per GE Recommendations & Returned to Svc in 1 H + (ML20083F679)
- ML20083F680 + (ML20083F680)
- 05000220/LER-1983-043-03, /03L-0:on 831128,fuel Zone Water Level Measuring Sys (Accurex) Found in Sys Idle Condition for Channel 11(A) at Time of Planned Surveillance Procedure N1-ISP-36- Icc.Cause Not Yet Known.Investigation Under Way + (ML20083F684)
- ST-HL-AE-1039, Final Deficiency Rept Re Tight Seal on Target Rock Pilot Actuated Solenoid Valves.Initially Reported on 831118.Valves May Be Replaced or Supplemented.Item Not Reportable Per 10CFR50.55(e) + (ML20083F685)
- 05000317/LER-1983-032-03, Containment Isolation Signal Logic Module B Would Not Actuate.Caused by Defective Electronic Logic Components.Module Replaced,Tested & Returned to Svc + (ML20083F688)
- 05000324/LER-1983-097-01, /01T-0:on 831212,during IE Bulletin 83-02 Testing, Crack Indications Identified in 19 of 131 Welds.Caused by Intergranular Stress Corrosion Cracking.Eight Welds Repaired.Remaining Indications Acceptable + (ML20083F691)
- ML20083F693 + (ML20083F693)
- ML20083F698 + (ML20083F698)
- 05000361/LER-1983-151-03, /03L-0:on 831114,w/unit in Mode 1,reactor Manually Tripped Due to Unexpected Pressurizer Pressure & Level Decrease.Caused by Operator Opening Emergency Boration Valve 2HV-9247.Training Program Revamped + (ML20083F699)
- ML20083F711 + (ML20083F711)
- ML20083F712 + (ML20083F712)
- ML20083F716 + (ML20083F716)
- IR 05000336/2020010 + (ML20083F717)
- ML20083F727 + (ML20083F727)
- ML20083F728 + (ML20083F728)
- ML20083F729 + (ML20083F729)
- 05000325/LER-1983-056-03, /03L-0:on 831127,control Board Position Indication Problems Identified in Control Rods 14-19,22-03 & 38-31. Caused by Defective Position Indication Probe Connectors or Reed Switches in Subj Rods + (ML20083F730)
- ML20083F735 + (ML20083F735)
- ML20083F738 + (ML20083F738)
- ML20083F739 + (ML20083F739)
- ML20083F742 + (ML20083F742)
- 05000338/LER-1983-086-03, /03L-0:on 831209,w/unit at 100% Power,Open Penetration Discovered in Fire Wall Between Motor Driven Auxiliary Feedwater Pump Room & Steam Driven Auxiliary Feedwater Pump Room.Wall Not Included in Test + (ML20083F745)
- ML20083F746 + (ML20083F746)
- ML20083F749 + (ML20083F749)
- ML20083F753 + (ML20083F753)
- 3F1283-33, Responds to NRC Re Violations Noted in IE Safeguards Insp Rept 50-302/83-28.Corrective Actions Withheld + (ML20083F754)
- ML20083F760 + (ML20083F760)
- ML20083F767 + (ML20083F767)
- ML20083F775 + (ML20083F775)
- ML20083F776 + (ML20083F776)
- ML20083F778 + (ML20083F778)
- 05000368/LER-1983-049-01, /01T-0:on 831212,due to Procedural & Personnel Errors Identified in Station Battery Surveillance Requirements,Review of Addl Surveillances Conducted.Addl Past Inadequacies Discovered + (ML20083F779)
- AECM-84-0023, Forwards Proprietary Affidavit & Figures Referenced in Util 840106 Response to NRC Questions Re Agastat Relays.Encls Withheld (Ref 10CFR2.790) + (ML20083F789)
- ML20083F796 + (ML20083F796)
- 05000251/LER-1983-021-03, /03L-0:on 831207,while Adding Nitrogen to Accumulators,Accumulator 4B Relief Valve Lifted Prematurely at Setpoint Below Tech Spec Limit.Caused by Premature Lifting of Relief Valve 858B + (ML20083F799)
- 05000331/LER-1983-046-03, /03L-0:on 831201,reactor Protection Sys Electric Assembly B2 Failed to Trip Output Breaker at Required Frequency.Caused by Setpoint Drift.Test Results Will Be Monitored + (ML20083F800)
- ML20083F811 + (ML20083F811)
- ML20083F813 + (ML20083F813)
- ML20083F814 + (ML20083F814)
- ML20083F816 + (ML20083F816)
- ML20083F817 + (ML20083F817)