Search by property
Jump to navigation
Jump to search
This page provides a simple browsing interface for finding entities described by a property and a named value. Other available search interfaces include the page property search, and the ask query builder.
List of results
- ML20081A822 + (ML20081A822)
- ML20081A829 + (ML20081A829)
- AECM-83-0679, RO 83-09210:on 830910,listed Control Room fire-rated Penetrations Opened to Implement Design Change Package.Fire Watch Established.Penetrations Resealed on 831007 + (ML20081A833)
- ML20081A834 + (ML20081A834)
- 05000370/LER-1983-046-03, /03L-0:on 830912,during Removal of Tachometer for calibr,turbine-driven Auxiliary Feedwater Pump Started & Could Not Be Stopped from Either Local Panel or Control Room.Caused by Blown Fuse.Fuse Replaced + (ML20081A839)
- W3P84-0562, Advises That Sser 5 Provides Incorrect Listings of CPC Penalty Factors Resulting from Rod Bow Penalty.Requests That Corrected Table of Penalty Factors Be Included in Next Sser + (ML20081A852)
- ML20081A853 + (ML20081A853)
- ML20081A854 + (ML20081A854)
- ML20081A857 + (ML20081A857)
- ML20081A858 + (ML20081A858)
- 05000260/LER-1983-054-03, /03L-0:on 830916,west Side Scram Discharge Vol High Water Level Switch LS-85-45C Would Not Reset Following Scram.Caused by Setpoint Drift.Switch Recalibr + (ML20081A859)
- 05000364/LER-1983-040-03, /03L-0:on 830918,during Performance of RCS Pressure Isolation Valve Leak Test,Check Valve Q2E11V051A Declared Inoperable When Valve Found Leaking Excessively. Caused by Incomplete Contact Between Valve Disc & Seat + (ML20081A860)
- 05000364/LER-1983-041-03, /03L-0:on 830921,instrumentation Channel Associated W/Rcp Bus Underfrequency Relay a Declared Inoperable Due to Response Time Being 1.64 Above Tech Spec Time of 0.6 S.Caused by Dirty Contacts + (ML20081A863)
- NLS8400073, Forwards Descriptions of Reg Guide 1.97 Requirements & Schedule for Implementation of Emergency Response Capability,Per NUREG-0737,Suppl 1 + (ML20081A865)
- ML20081A869 + (ML20081A869)
- ML20081A870 + (ML20081A870)
- ML20081A875 + (ML20081A875)
- 3F0284-13, Revised Application for Amend to License DPR-72,changing Tech Specs to Reflect Addition of Two independent,in-place Hydrogen Monitors.Certificate of Svc Encl + (ML20081A876)
- ML20081A877 + (ML20081A877)
- ML20081A882 + (ML20081A882)
- ML20081A883 + (ML20081A883)
- AECM-83-0678, RO 83-091/0:on 830910,during Surveillance Testing,Fire Door OC713 on Elevation 189 Ft in Control Bldg Found W/O Lock. Fire Door OC713 Not Designed to Lock.Door Deleted from Procedure 06-OP-SP64-W-0045,Rev 20.Fire Watch Established + (ML20081A884)
- 05000255/LER-1983-065-01, /01T-0:on 831006,during Walkdown of Safety Injection Sys Pipe Hangers,Discovered Overload Condition on Baseplate & Anchor Bolts of Hanger H214.Caused by Design Analysis Error.Hanger Support Redesigned + (ML20081A885)
- ML20081A888 + (ML20081A888)
- ML20081A894 + (ML20081A894)
- AECM-83-0673, RO 83-093/0:on 830914 & 15,control Room Upper Cable Spreading Room Ambient Air Temp Exceeded Area Temp Limit of 77 F in Tech Spec 3.7.8-1.c During 36 H Period.Max Qualification Temp Not Exceeded + (ML20081A895)
- ML20081A898 + (ML20081A898)
- ML20081A900 + (ML20081A900)
- 05000316/LER-1983-096-03, /03L-0:on 830918,during Attempt to Rectify Order of Procedural Steps Re Containment Spray Surveillance Tests Concerning Lineup of Valve A,Water Drained to Containment. Caused by Personnel Error + (ML20081A905)
- 05000369/LER-1983-082-03, /03L-0:on 830911,pressurizer Heater Group 1B Declared Inoperable When Operation Did Not Aid in RCS Pressure Control.Caused by Blown 500 Amp Line Fuse in Vacuum Contractor Cabinet.Fuse Replaced + (ML20081A907)
- ML20081A908 + (ML20081A908)
- TXX-4067, Forwards Test Results Re Fire Rating of Watertight Doors, Verifying Acceptability of Std Industrial Watertight Doors Utilized at Facility as 3 H Fire Barriers + (ML20081A909)
- ML20081A911 + (ML20081A911)
- 05000361/LER-1984-006, :on 840103,spurious Toxic Gas Isolation Sys Actuations Occurred.Caused by Toxic Gas Isolation Sys Setpoint Set at Threshold Level of Detection.Tech Specs Revised to Raise Setpoint Requirements + (ML20081A915)
- RBG-16-210, Revises Schedule for Providing Responses to Draft SER Issues & Clarifications to Fsar.Responses Previously Committed for 831015 Will Be Provided Between 831101 & 1231 + (ML20081A923)
- TXX-4066, Requests Withdrawal of 831004 Engineering Basis for Structural Integrity of Raceway Supports Associated w/1 H Rated Cable Protective Envelope Sys Upon Exposure to Fire. Supports Capable of Withstanding 1 H Fire + (ML20081A930)
- ML20081A932 + (ML20081A932)
- ML20081A933 + (ML20081A933)
- ML20081A945 + (ML20081A945)
- 05000315/LER-1983-077, Forwards Updated LER 83-077/03X-1 & LERs 83-096/03L-0 & 83-097/03L-0 + (ML20081A947)
- 05000389/LER-1984-002-01, :on 840130,hydrogen Analyzer 2B & Control Room Air Conditioner HVA-3A Unavailable for Mode Changes as Required by Tech Specs.Caused by Improper Review & Recordkeeping.Personnel Reinstructed + (ML20081A948)
- ML20081A958 + (ML20081A958)
- ML20081A963 + (ML20081A963)
- 05000370/LER-1983-048-03, /03L-0:on 830914,15 & 16,average Lower Containment Temp Exceeded Tech Spec Requirements.Caused by Const & Design Deficiencies.Sys Air Handling Units Realigned to to Cooler Source & Cooling Flow Increased + (ML20081A965)
- ML20081A966 + (ML20081A966)
- ML20081A967 + (ML20081A967)
- ML20081A969 + (ML20081A969)
- ML20081A974 + (ML20081A974)
- ML20081A979 + (ML20081A979)
- ML20081A981 + (ML20081A981)
- ML20081A983 + (ML20081A983)