Search by property
Jump to navigation
Jump to search
This page provides a simple browsing interface for finding entities described by a property and a named value. Other available search interfaces include the page property search, and the ask query builder.
List of results
- AECM-83-0093, Monthly Operating Rept for Jan 1983 + (ML20079L346)
- ML20079L347 + (ML20079L347)
- 05000397/LER-1983-001-03, /03L-0:on 831225,while Loading First Fuel Bundle, Rod Block Protective Interlock Lost.Caused by Misinterpretation of Tech Spec Intent.Calibr & Survillance Procedures Changed + (ML20079L348)
- 05000361/LER-1983-154-03, /03L-0:on 831211,during Mode 5 Outage,Channel a Pressurizer Level Transmitter 2LT-0110-1 Found Inoperable During Performance of 18-month Calibr.Caused by Empty Ref Leg.Leg Filled + (ML20079L350)
- 05000259/LER-1983-073-01, /01T-0:on 831231,reactor Coolant Sample Indicated Chloride Concentration of 525 Ppb & Conductivity & Offgas Radiation Level Increased While Ph Decreased.Caused by Resin Intrusion Into Reactor Vessel.Trap Replaced + (ML20079L353)
- ML20079L355 + (ML20079L355)
- ML20079L361 + (ML20079L361)
- 05000366/LER-1980-049-03, While Performing Standby Liquid Control Pump Operability & Relief Valve Test,Sblc Pump B Discharge Relief Valve Failed to Operate at Required Pressure.Caused by Setpoint Drift + (ML20079L362)
- 05000395/LER-1983-076-03, Pressurizer PORV PCV-444B-RC Would Not Fully Stroke When Operated from Main Control Board.Caused by Low Operating Pressure.Regulator for PCV-44B-RC Replaced + (ML20079L363)
- 05000373/LER-1991-011-05, :on 911002,TS Surveillance Missed During Primary Containment Due to Missed Prerequisite C.6 in Procedure LOP-VQ-11.Procedure LOP-VQ-11 Will Be Revised & Operating Dept Will Be Trained on Event + (ML20079L369)
- JPN-91-060, Forwards Response to Generic Ltr 91-06, Resolution of Generic Issue A-30, Adequacy of Safety-Related DC Power Supplies. Advises That Design,Maint,Surveillance & Test Procedures for Dc Power Supplies Reasonable Alternatives + (ML20079L370)
- ML20079L372 + (ML20079L372)
- ML20079L379 + (ML20079L379)
- ML20079L381 + (ML20079L381)
- JPN-91-061, Responds to Generic Ltr 89-04 Re Guidance on Developing Acceptable Inservice Testing (IST) Program.Requests That NRC Review Open Relief Requests by 920101 to Enable Util to Implement Rev 4 to IST During Next Refueling Outage + (ML20079L382)
- AECM-84-0011, RO 83-114/0:on 831215,control Room Temp Exceeded Tech Spec Limit of 77 Degrees F for Period of More than 8 H.Max Recorded Temp Was 80 Degrees F.Availability or Operability of Equipment within Area Not Affected + (ML20079L384)
- ML20079L385 + (ML20079L385)
- 05000338/LER-1983-006, Forwards LER 83-006/03L-0 + (ML20079L386)
- ML20079L388 + (ML20079L388)
- ST-HL-AE-4001, Forwards Emergency Response Data Sys Implementation Plan, Per 10CFR50,App E,Section VI.4.a.Implementing Procedures Will Be Modified to Require That Sys Be Activated within 1 H of Declaration of Alert + (ML20079L389)
- 05000361/LER-1991-015-01, :on 911001,containment Purge Isolation Sys Train a Actuation Occurred While Performing Radiography. Cause Not Stated.Health Physics Procedures Modified & Training Will Be Conducted + (ML20079L390)
- ML20079L394 + (ML20079L394)
- RBG-14-374, Submits Addl Info in Response to NRC Re Util 811209 Final Response to IE Bulletin 81-03, Flow Blockage of Cooling Water to Safety Sys Components by Corbicula Sp (Asiatic Clam) & Mytilus Sp (Mussel) + (ML20079L395)
- ML20079L396 + (ML20079L396)
- 05000338/LER-1983-006-03, /03L-0:on 830125,triaxial Peak Accelegraphs on RHR HX & Safety Injection Pipe Found Inoperable from Corrosion Damage on Internal Parts.Caused by Moisture Entering Accelegraphs.Units Replaced + (ML20079L397)
- 05000389/LER-1983-077-03, /03L-0:on 831221,diesel Generator 2B Failed to Start within 10 & Fuel Oil Day Tank Failed to Automatically Fill Above 30% Level.Cause for Slow Start Not Determined.Tank Holding Relay Module Replaced + (ML20079L404)
- ML20079L405 + (ML20079L405)
- ML20079L406 + (ML20079L406)
- ML20079L407 + (ML20079L407)
- ML20079L408 + (ML20079L408)
- ML20079L411 + (ML20079L411)
- 05000251/LER-1983-022-03, /03L-0:on 831219,routine Sample of Boric Acid Storage Tank Boron Concentration Revealed Three Tanks Exceeding Tech Spec Limits.Caused by Lack of Communication Between Chemistry & Operations Personnel + (ML20079L416)
- ML20079L417 + (ML20079L417)
- ML20079L418 + (ML20079L418)
- ML20079L419 + (ML20079L419)
- ML20079L420 + (ML20079L420)
- RBG-14-367, Interim Deficiency Rept DR-92 Re Supplier & Subsupplier ASME III Documentation for Category I Stainless Steel Thermowells.Initially Reported on 830114.Investigation Not Completed.Next Rept Expected by 830418 + (ML20079L421)
- ML20079L424 + (ML20079L424)
- ML20079L426 + (ML20079L426)
- BVY-91-109, Responds to NRC Re Violations/Deviations Noted in Safety Insp Rept 50-271/91-23 on 910903-06.Corrective actions:corrected,computer-generator Manifests,Listing Fe-55 Sent to Lab & New Task Matrix Formed + (ML20079L427)
- ML20079L428 + (ML20079L428)
- ML20079L429 + (ML20079L429)
- ML20079L431 + (ML20079L431)
- 3F1091-18, Responds to Generic Ltr 91-11, Resolution of Generic Issue 48, Limiting Condition for Operation (LCO) for Class 1E Vital Instrument Buses & 49, Interlocks & LCOs for Class 1E Tie Breakers + (ML20079L432)
- ML20079L434 + (ML20079L434)
- ML20079L435 + (ML20079L435)
- ML20079L436 + (ML20079L436)
- ML20079L437 + (ML20079L437)
- ML20079L439 + (ML20079L439)
- ML20079L440 + (ML20079L440)
- 05000387/LER-1983-007, Forwards LER 83-007/03L-0 + (ML20079L443)