Search by property
Jump to navigation
Jump to search
This page provides a simple browsing interface for finding entities described by a property and a named value. Other available search interfaces include the page property search, and the ask query builder.
List of results
- ML20079H737 + (ML20079H737)
- 05000373/LER-1982-149, Forwards LER 82-149/03L-0 + (ML20079H743)
- ML20079H747 + (ML20079H747)
- ML20079H749 + (ML20079H749)
- 05000373/LER-1982-149-03, /03L-0:on 821112,lake Blowdown Flow Recorder Discovered Giving Incorrect Readings.Caused by Algae Buildup on Instrument Probe.Probe Cleaned & Weekly Functional Test Will Be Performed + (ML20079H751)
- ML20079H753 + (ML20079H753)
- ML20079H755 + (ML20079H755)
- ML20079H759 + (ML20079H759)
- 05000416/LER-1982-120, Forwards LER 82-120/99X-0 + (ML20079H769)
- 05000325/LER-1982-139, Forwards LER 82-139/03L-0 + (ML20079H774)
- ML20079H784 + (ML20079H784)
- 05000311/LER-1983-062-03, /03L-0:on 831128,during Vital Instrument Bus Transfer,Rhr Common Suction Valve 2RH2 Closed,Resulting in Loss of RHR Flow Through Rcs.Caused by Pressure Transmitter PT-405 Spike Due to Voltage Transient + (ML20079H791)
- 05000416/LER-1982-120-99, /99X-0:on 821105,during Shutdown,Fire Door 1A106 Opened to Drain Standby Svc Water Loop B by Allowing Passage of Hose to Channel Water from Flush & Drain of Loop. Door Will Be Restored.Final Rept Expected by 830212 + (ML20079H792)
- BSEP-84-0027, RO 2-SR-83-36:bottom Sediment Sample Gamma Analysis Collected on 831201 Detected Abnormal Co-60 Concentration. Sampling Frequency Increased to Monthly to Closely Monitor Co-60 Activity + (ML20079H794)
- ML20079H799 + (ML20079H799)
- ML20079H802 + (ML20079H802)
- 05000325/LER-1983-060-03, /03L-0:on 831217,remote Shutdown Panel C32-PI-3332 Showed Pressure of 860 Psi While Redundant Control Room Instrumentation Showed Expected Pressure of 990 Psi.Caused by Failed Electrical Capacitor + (ML20079H808)
- ML20079H816 + (ML20079H816)
- ML20079H822 + (ML20079H822)
- 05000366/LER-1982-126, Forwards LER 82-126/03L-0 + (ML20079H823)
- ML20079H825 + (ML20079H825)
- 05000325/LER-1982-139-03, /03L-0:on 821114,HPCI Sys Rendered Inoperable When HPCI Steamline Flow High Channel B Isolation Occurred During Operability Test.Caused by Shorted Positioning Coil in HPCI Speed Control Electrohydraulic Governing Regulator A + (ML20079H828)
- 05000324/LER-1983-092-03, /03L-0:on 831219,accumulator Leak Detection Instruments 2-C12-LS-129-42-11,46-35,50-19 & 18-03 Failed to Respond to Applied Test Input.Caused by Instrument Failure. Instrument Replaced + (ML20079H829)
- ML20079H831 + (ML20079H831)
- ML20079H833 + (ML20079H833)
- 05000266/LER-1982-024, Forwards LER 82-024/03L-0 + (ML20079H834)
- ML20079H835 + (ML20079H835)
- ML20079H839 + (ML20079H839)
- ML20079H841 + (ML20079H841)
- ML20079H844 + (ML20079H844)
- 05000366/LER-1982-126-03, /03L-0:on 821105,post-accident High Drywell Pressure Alarm Failed to Actuate During Quarterly Surveillance Test.Caused by Erroneous Wiring of Drywell & Torus Pressure Recorder.Wiring Error Corrected + (ML20079H849)
- ML20079H850 + (ML20079H850)
- 05000266/LER-1982-024-03, /03L-0:on 821116,during Review of Test Data,Steam Flow Transmitter FT-465 Discovered 0.177% Nonconservative. Caused by Nonconservative Static Zero Shift.Instrument Recalibr + (ML20079H858)
- ML20079H861 + (ML20079H861)
- ML20079H865 + (ML20079H865)
- ML20079H874 + (ML20079H874)
- ML20079H878 + (ML20079H878)
- ML20079H882 + (ML20079H882)
- ML20079H883 + (ML20079H883)
- 05000293/LER-1983-068-01, /01T-0:on 831219,during Refueling Operations, Shield Plugs Separating Dryer Separator Pool from Refuel Cavity Not Removed.Caused by Procedural Inadequacy.Procedure Revised + (ML20079H884)
- ML20079H888 + (ML20079H888)
- 05000346/LER-1982-060-03, /03L-0:on 821111,during Performance of ST 5031.14, Discovered Ventilation Duct Chase 48 Power Supply in Steam & Feedwater Rupture Control Sys Channel 2 Failing at 1-volt/h.Caused by Component Failure.Channel 2 de-energized + (ML20079H894)
- ML20079H895 + (ML20079H895)
- 05000370/LER-1983-086-03, /03L-0:on 831212 & 13,invalid Fire Alarm for Fire Detection Zone 107 Received & Would Not Reset.Caused by Broken Ionization Chamber Mounting Pins.Detector Replaced + (ML20079H900)
- ML20079H901 + (ML20079H901)
- ML20079H904 + (ML20079H904)
- SNRC-1004, Submits Technical Guidance & Methodology for Conducting Rebuilt Emergency Diesel Generator Overload Testing,Per Rev 1 to Reg Guide 1.108.Preoperational Test Program Must Demonstrate full-load-carrying Capability + (ML20079H905)
- ML20079H907 + (ML20079H907)
- ML20079H908 + (ML20079H908)
- ML20079H922 + (ML20079H922)
- ML20079H925 + (ML20079H925)