Search by property
Jump to navigation
Jump to search
This page provides a simple browsing interface for finding entities described by a property and a named value. Other available search interfaces include the page property search, and the ask query builder.
List of results
- ML20077F332 + (ML20077F332)
- BVY-94-121, Monthly Operating Rept for Nov 1994 for VT Yankee Nuclear Power Station + (ML20077F346)
- 05000244/LER-1983-021-03, /03L-0:on 830618,pressurizer Water Level Dropped Below 12%.Caused by RCS Cooldown After Reactor Trips.Level Restored by Increasing Charging Flow + (ML20077F350)
- ML20077F351 + (ML20077F351)
- ML20077F359 + (ML20077F359)
- BECO-LTR-94-120, Forwards 1995 Environ Monitoring,Thermal Discharge Fish Surveillance & Dissolved N Saturation Reduction Programs & Plans + (ML20077F366)
- ML20077F367 + (ML20077F367)
- ML20077F372 + (ML20077F372)
- 05000271/LER-1983-016-03, /03L-0:on 830620,MSIV 86A Closed in 5.5 S.Caused by Broken Spring in Hydraulic Dashpot Closure Time Adjustment Mechanism.Broken Spring Replaced,Hydraulic Dash Pot Reassembled & Valve Retimed + (ML20077F378)
- 05000285/LER-1994-009, :on 941108,inappropriate Use of Auxiliary Bldg Crane Over Irradiated Fuel.Caused by Combination of Inadequate pre-job Briefing.Conveying Mgt Expectations Re Conduct of pre-job Briefings + (ML20077F379)
- 05000244/LER-1983-024-03, /03L-0:on 830621,Foxboro Model N-E11DM Steam Generator Steam Flow Transmitter FT-464 Found Out of Tolerance.Caused by Pressure Static Shift.Transmitter Adjusted + (ML20077F381)
- ML20077F386 + (ML20077F386)
- 05000389/LER-1983-032-03, /03L-0:on 830623,channel a wide-range Nuclear Instrumentation Failed.Caused by Failure of Log Count Rate Circuit Board LCR-1 Mfg by Electro Mechanic.Board Replaced + (ML20077F391)
- RBG-15-533, Responds to Re Status of Licensing Review Group-II Issue Solutions.Status Provided in Util ,Including Status Table for Clinton,Perry & River Bend Per Discussions W/Nrc at 830609 Meeting + (ML20077F398)
- 05000334/LER-1994-009-01, :on 941103,operation Prohibited by TS Inadequate RCS Relief Path.Nominal Port Diameter Was Used for Calculations Rather than Effective Vent Diameter Based on Specific Trim Installed + (ML20077F399)
- ML20077F407 + (ML20077F407)
- ML20077F411 + (ML20077F411)
- ML20077F412 + (ML20077F412)
- ML20077F414 + (ML20077F414)
- ML20077F415 + (ML20077F415)
- ML20077F416 + (ML20077F416)
- ML20077F425 + (ML20077F425)
- ML20077F426 + (ML20077F426)
- ML20077F429 + (ML20077F429)
- ML20077F431 + (ML20077F431)
- 05000298/LER-1983-012-03, /03L-0:on 830621,during Control Rod Shuffle,Fuel Bundle Removed & Reloaded Into Core in Same Position W/O All Control Rods Inserted.Caused by Personnel Error.Crews Briefed + (ML20077F436)
- 05000298/LER-1983-011-01, /01T-0:on 830710,welds CSA-BJ-5 & 6 Found Leaking During Grinding of Weld Crowns.Caused by Intergranular Stress Corrosion Cracking.Welds to Be Repaired by Weld Overlay Methods.Piping Will Be Replaced + (ML20077F446)
- LIC-94-0250, Forwards Evaluation of Irradiated Capsule W-275 + (ML20077F452)
- 05000220/LER-1983-015-03, /03L-0:on 830624,while Performing Surveillance Test N1-ISP-RVT on Main Steam Electromatic Relief Valve Tailpipe Temp Sensors,Inputs Indicated Excessive Drift.Cause Unknown.Corrective Action Being Evaluated + (ML20077F453)
- 05000325/LER-1983-027-03, /03L-0:on 830630,1/8-inch Cut Found in Fire Hose Station SW-2 Fire Hose.Cause Undetermined.Hose Replaced + (ML20077F454)
- ML20077F459 + (ML20077F459)
- 05000389/LER-1983-028-03, /03L-0:on 830624,position Indicator Channels Declared Inoperable When Control Element Assemblies 44 & 22 Appeared to Slip.Caused by Erroneous Indications Due to Mismatched Impedance.Computer Leads Lifted + (ML20077F468)
- ML20077F470 + (ML20077F470)
- 05000261/LER-1983-013-03, /03L-0:on 830625,RCS Leak Rate Determined to Be 1.07 Gpm.Caused by Packing of Pressurizer Block Valve RC-536.Valve Will Be Repacked During Next Cold Shutdown + (ML20077F472)
- 05000302/LER-1983-024-03, /03L-0:on 830624,procedures Governing Lab Determination of Sodium Hydroxide Concentration Erroneously Equated 1.0 Mg Per Liter w/1.0 Ppm Causing Concentration Error.Caused by Procedure Inadequacy + (ML20077F474)
- ST-HL-AE-3800, Monthly Operating Repts for May 1991 for South Texas Project Electric Generating Station + (ML20077F478)
- ML20077F479 + (ML20077F479)
- ML20077F481 + (ML20077F481)
- ML20077F485 + (ML20077F485)
- HL-1684, Monthly Operating Repts for May 1991 for Hatch Nuclear Plant Units 1 & 2 + (ML20077F488)
- 05000277/LER-1990-004, :on 900321,determined That Under DBA Conditions Some ECCS & RCIC Sys Room Coolers Would Not Receive Min Acceptable Emergency Svc Water Flow.Caused by Buildup of Corrosion Products.Piping Inspected + (ML20077F492)
- 05000277/LER-1991-013-01, :on 910530,determined That Two Penetration Fire Seals Not Qualifiable Per 10CFR50,App R Due to Voids & Uncured Polyurethane Sealant Matl.Caused by Improper Seal Installation.Firewatches Initiated + (ML20077F494)
- ML20077F497 + (ML20077F497)
- ML20077F502 + (ML20077F502)
- ML20077F503 + (ML20077F503)
- 05000395/LER-1983-070-03, /03L-0:on 830629,pressurizer Relief Tank Level Indicator Removed from Svc Due to High Indication.Caused by Zero Shift on Transmitter.Transmitter Calibr + (ML20077F504)
- 05000311/LER-1983-031-03, /03L-0:on 830623,spurious Safeguards Equipment Control Sys Actuation Deenergized Various Loads on Vital Bus 2A.Caused by Internal Circuitry Noise.Corrective Action to Be Taken When Investigation Completed + (ML20077F506)
- 05000416/LER-1983-081-03, /03L-0:on 830627,control Room Fresh Air Unit a Declared Inoperable When Results of Lab Analysis of Carbon Sample Not Received within 31 Days.Caused by Delay of Shipment Sample Pending Vendor Approval + (ML20077F510)
- 05000277/LER-1991-014, :on 910521,isolation of HPCI Sys Occurred Unexpectedly During Surveillance Test.Caused by Leaking Isolation Valve,Resulting in Pressurization of Switch.Valve Replaced & Test Performed Satisfactorily + (ML20077F512)
- 05000277/LER-1991-015, :on 910515,reactor Bldg & Refueling Floor Ventilation Sys Tripped & Standby Gas Treatment Sys Initiated When Incorrect Fuse Pulled.Caused by Personnel Error.Fuses Will Be Labeled + (ML20077F513)
- 05000353/LER-1991-008-02, :on 910401,emergency Diesel Generator Declared Inoperable During Surveillance Test.Caused by Personnel Error.Procedures Revised to Provide Caution & Direction for Fuse Installation & Verification + (ML20077F517)