Search by property
Jump to navigation
Jump to search
This page provides a simple browsing interface for finding entities described by a property and a named value. Other available search interfaces include the page property search, and the ask query builder.
List of results
- 05000366/LER-1983-025, Forwards LER 83-025/03L-0 + (ML20076D554)
- ML20076D560 + (ML20076D560)
- 05000366/LER-1983-025-03, /03L-0:on 830414,during Turbine Bldg Area Temp Functional Test & Calibr,Monitor 2U61-R002 Found Out of Calibr.Caused by Setpoint Drift of Five Temp Switches & Inoperability of One Switch.Monitor Replaced + (ML20076D562)
- ML20076D565 + (ML20076D565)
- B10788, Discusses Re Proposed Revs to Tech Specs for Cycle 6 Reload.Current Tech Spec Limits Provide Acceptable Margin of Safety + (ML20076D576)
- 05000317/LER-1983-019, Forwards LER 83-019/01T-0 + (ML20076D581)
- ML20076D585 + (ML20076D585)
- 05000317/LER-1983-019-01, /01T-0:on 830426,PORV ERV-404 Opened While Raising RCS Pressure.Caused by Failure of Control Room Operator to Monitor RCS Pressure Carefully.Short Circuit Caused Loss of Control Power to ERV-402 During Troubleshooting + (ML20076D586)
- ML20076D593 + (ML20076D593)
- ML20076D595 + (ML20076D595)
- ML20076D598 + (ML20076D598)
- ML20076D603 + (ML20076D603)
- 05000293/LER-1983-016, Forwards LER 83-016/03L-0 + (ML20076D607)
- ML20076D612 + (ML20076D612)
- 05000334/LER-1983-011, Forwards LER 83-011/03L-0 + (ML20076D615)
- ML20076D616 + (ML20076D616)
- 05000293/LER-1983-016-03, /03L-0:on 830402,overload Annunciation Received When MOV-220-2 Switched Open During Scram Recovery.Probably Caused by Spurious Annunciator from Overload Mechanism in Cutler-Hammer Motor Control Ctr.Valve Returned to Svc + (ML20076D620)
- ML20076D621 + (ML20076D621)
- ML20076D623 + (ML20076D623)
- ML20076D626 + (ML20076D626)
- 05000318/LER-1983-022, Forwards LER 83-022/03L-0 + (ML20076D628)
- AECM-83-0328, Responds to NRC Re Violations Noted in IE Insp Rept 50-416/83-14.Corrective Actions:Technician Responsible for Violation Suspended for 7 Days.Procedure Adherence Emphasized + (ML20076D632)
- ML20076D633 + (ML20076D633)
- ML20076D634 + (ML20076D634)
- ML20076D635 + (ML20076D635)
- 05000244/LER-1983-013-01, /01T-0:results of multi-frequency Eddy Current Exam of Steam Generator a Inlet & Outlet Revealed No Tubes W/Indications Above Plugging limit.Twenty-three Tubes W/ Intergranular Attack Indications Found in Generator B + (ML20076D636)
- 05000334/LER-1983-011-03, /03L-0:on 830409,motor Thermal Overload Relay for Containment Sump to 1A Low Head Safety Injection Pump Suction Valve (MOV-SI-860A) Tripped,Disabling Motor.Cause Unknown.Event Will Be Reevaluated + (ML20076D637)
- ML20076D641 + (ML20076D641)
- 05000327/LER-1983-056, Forwards LER 83-056/01T-0 + (ML20076D645)
- 05000293/LER-1983-018, Forwards LER 83-018/03L-0 + (ML20076D648)
- ML20076D649 + (ML20076D649)
- ML20076D651 + (ML20076D651)
- 05000387/LER-1983-056, Forwards LER 83-056/03L-0 + (ML20076D658)
- ML20076D666 + (ML20076D666)
- ML20076D667 + (ML20076D667)
- 05000327/LER-1983-056-01, /01T-0:on 830503,inner Door to Upper Containment Airlock Discovered Inoperable.Caused by Sheared Stud on Latching Mechanism & Failed Cam Follower Bearing Allowing Outer Door to Open While Inner Door Not Closed + (ML20076D670)
- ML20076D671 + (ML20076D671)
- L-83-456, Forwards Response to Unresolved Item Re Intermixing of Cables in Redundant Safeguard Cable Trays Per IE Insp Repts 50-250/83-14 & 50-251/83-14.Addl Info Re Structural Evaluation of as-built Cable Tray Sys Program Also Encl + (ML20076D672)
- ML20076D678 + (ML20076D678)
- 05000293/LER-1983-018-03, /03L-0:on 830408,during Insp,Standby Gas Treatment Sys B Heater Contact & Wiring Found Burnt,Rendering Sys Inoperable.Caused by High Resistance Due to Loose Wires at Contactor Terminal.Contactor & Wires Replaced + (ML20076D681)
- ML20076D691 + (ML20076D691)
- ML20076D696 + (ML20076D696)
- ML20076D698 + (ML20076D698)
- ML20076D702 + (ML20076D702)
- ML20076D703 + (ML20076D703)
- ML20076D705 + (ML20076D705)
- 05000348/LER-1983-018-03, /03L-0:on 830413,RCS Temp Average Fell Below Tech Spec Limit.Caused by Excessive Leakby on 1A Main Feedwater Regulating Bypass Valve.Stroke on 1A Main Feedwater Regulating Bypass Valve Adjusted & Verified + (ML20076D708)
- ML20076D709 + (ML20076D709)
- ML20076D711 + (ML20076D711)
- ML20076D712 + (ML20076D712)
- ML20076D713 + (ML20076D713)