- 05000369/LER-1983-040-03, /03L-0:on 830604,06 & 28,Fire Detection Zones Efa 76,150 & 103 Declared Inoperable Due to Invalid Alarms. Caused by Spurious Alarms & High Dust Concentration.Smoke & Fire Ionization Detectors Replaced + (ML20072N495)
- ML20072N502 + (ML20072N502)
- ML20072N503 + (ML20072N503)
- 05000416/LER-1983-058, Forwards LER 83-058/01T-0 + (ML20072N506)
- ML20072N507 + (ML20072N507)
- 05000321/LER-1983-030-03, /03L-0:on 830221,while Performing RCIC Pump Operability Procedure,Rcic Pump Discovered to Pump at Max Output of 360 Gpm.Caused by Failure of Turbine Speed Control Circuit Signal Converter.Converter Replaced + (ML20072N514)
- ML20072N519 + (ML20072N519)
- ML20072N522 + (ML20072N522)
- 05000395/LER-1983-018-03, /03L-0:on 830306,while in Mode 1,nuclear Sampling Sys Valves 9398 A,B & C Failed to Close During Initial Performance of Accelerated Test Program.Caused by Crud Buildup on Valve Seats.Crud Dislodged & Switch Repaired + (ML20072N524)
- 05000416/LER-1983-058-01, /01T-0:on 830311,fire Watches Not Conducted in Two Areas of Fire Detection Zone 2-19 as Required by Tech Specs. Caused by Personnel Oversight.Room Numbers Added to Fire Watch Checksheets.Updated Rept Will Be Submitted by 830 + (ML20072N530)
- ML20072N533 + (ML20072N533)
- 05000369/LER-1983-010, Forwards LER 83-010/03L-0 + (ML20072N534)
- ML20072N537 + (ML20072N537)
- ML20072N540 + (ML20072N540)
- ML20072N543 + (ML20072N543)
- ML20072N546 + (ML20072N546)
- ML20072N549 + (ML20072N549)
- 05000259/LER-1983-013, Forwards LER 83-013/01T-0 + (ML20072N550)
- ML20072N558 + (ML20072N558)
- 05000369/LER-1983-010-03, /03L-0:on 830216,while in Mode 6,control Room Outside Air Intake Radiation Monitors 1EMF-43A &43B Declared Inoperable.Caused by Personnel Error.Monitors Returned to Svc & Inlet Valves Opened After Testing + (ML20072N563)
- AECM-83-0386, Final/Interim Deficiency Rept PRD-82/14 for Units 1/2, Respectively Re Sheared Bolts on Rear Crankcase Cover of Delaval Diesel Generators.Unit 1 Bolts Not Defective.Unit 2 Rept Due on 850130.Also Reportable Per Part 21 + (ML20072N571)
- ML20072N573 + (ML20072N573)
- ML20072N575 + (ML20072N575)
- 05000369/LER-1983-009, Forwards LER 83-009/03L-0.Detailed Event Analysis Encl + (ML20072N582)
- ML20072N585 + (ML20072N585)
- RBG-15-389, Interim Deficiency Rept DR-105 Re Electrical Separation of Reactor Protection Sys Wiring from NSSS Shutoff Wiring within Power Generation Control Complex.Initially Reported on 830329.Info from GE Awaited.Next Rept Due by 830913 + (ML20072N588)
- ML20072N589 + (ML20072N589)
- ML20072N590 + (ML20072N590)
- 05000313/LER-1983-014-03, /03L-0:on 830609,auxiliary Feedwater Pump P-75 Rendered Inoperable.Caused by Supply Piping Seal Break Due to Piping Misalignment.Piping Replaced & Realigned to Reduce Stress + (ML20072N591)
- 05000366/LER-1983-026-03, /03L-0:on 830610,diesel Generator 2C Failed to auto-start After Manual Trip.Caused by Shutdown Solenoid Stuck in Shutdown Position.Solenoid Cleaned + (ML20072N594)
- ML20072N596 + (ML20072N596)
- ML20072N597 + (ML20072N597)
- 05000259/LER-1983-013-01, /01T-0:on 830307,standby Gas Treatment Train C Removed from Svc for Maint.Testing Revealed Train Failed to Meet Tech Spec Flowrate Requirements.Caused by Stuck Back Draft Damper.Damper Adjusted + (ML20072N598)
- RA-20-0067, Emergency Plan PLP-007, Revision 94 + (ML20072N601)
- ML20072N605 + (ML20072N605)
- ML20072N608 + (ML20072N608)
- 05000369/LER-1983-009-03, /03L-0:on 821112,during Troubleshooting & Checkout Activities Following Diesel Generator Mod Work,Diesel Generator 1B Experienced Failures.Caused by Wires on Wrong Terminal,Burned Diodes & Spurious Low Crankcase Signals + (ML20072N611)
- 05000318/LER-1983-017, Forwards LER 83-017/03L-0 + (ML20072N613)
- ML20072N614 + (ML20072N614)
- 0CAN038322, Requests Exemption from Implementation Schedule for 10CFR50, App R,Sections III.G.2.a,b & C Or,Alternatively,From 10CFR50.48(c) for All Fire Protection Barriers/Penetrations & All Suppression/Detection Sys.Justification Encl + (ML20072N618)
- ML20072N621 + (ML20072N621)
- 05000296/LER-1983-014, Forwards LER 83-014/03L-0 + (ML20072N623)
- ML20072N626 + (ML20072N626)
- 05000318/LER-1983-017-03, /03L-0:on 830218,power Lost to Saltwater Outlet Valves for 21 Svc Water & 21 Component Cooling Water Hx. Caused by Installation of Wrong Value Fuses.Correct Fuses Installed + (ML20072N629)
- ML20072N631 + (ML20072N631)
- ML20072N634 + (ML20072N634)