- ML20071F139 + (ML20071F139)
- 05000369/LER-1983-006, Forwards LER 83-006/03L-0.Detailed Event Analysis Encl + (ML20071F150)
- ML20071F153 + (ML20071F153)
- ML20071F156 + (ML20071F156)
- 05000321/LER-1983-006, Forwards LER 83-006/03L-0 + (ML20071F157)
- 05000331/LER-1983-006, Forwards LER 83-006/03L-0 + (ML20071F166)
- 05000321/LER-1983-006-03, /03L-0:on 830126,during Refueling Outage,Plant Svc Water Turbine Bldg Isolation Valves a & D Failed to Isolate & Pump 1A Failed to Start.Caused by Disconnected Control Wire Lifted for Unknown Reasons + (ML20071F176)
- 05000373/LER-1983-010, Forwards LER 83-010/03L-0 + (ML20071F177)
- ML20071F182 + (ML20071F182)
- 05000369/LER-1983-006-03, /03L-0:on 830131,unit Changed from Mode 5 to 6 W/ Control Room Area Outside Air Pressure Filter Train 2 (VC-B) Inoperable.Subj Train & VC Train a Inoperable on 830125,26 & 29.Caused by Misinterpretation of Tech Specs + (ML20071F183)
- 05000331/LER-1983-006-03, /03L-0:on 830211,during Normal Operation,Power Lost to MSIV D Leakage Control Sys.Caused by Blown Fuse Due to Random Failure of High Alarm Relay B21 K2D.Fuse Replaced. Replacement of Relay Under Consideration + (ML20071F191)
- ML20071F192 + (ML20071F192)
- ML20071F193 + (ML20071F193)
- ML20071F197 + (ML20071F197)
- ML20071F199 + (ML20071F199)
- ML20071F202 + (ML20071F202)
- ML20071F207 + (ML20071F207)
- ML20071F211 + (ML20071F211)
- ML20071F214 + (ML20071F214)
- 05000331/LER-1983-004, Forwards LER 83-004/03L-0 + (ML20071F215)
- 05000254/LER-1983-008, Forwards LER 83-008/03L-0 + (ML20071F218)
- 05000373/LER-1983-010-03, /03L-0:on 830209,during Insp of Main Steam Drain Line Piping,Mechanical Restraint MS20-1012X Found Installed on Line 1MS20BA-1-1/2 Inch in Violation of Plant Design. Caused by Personnel Oversight.Restraint Removed + (ML20071F224)
- ML20071F225 + (ML20071F225)
- 05000296/LER-1983-010, Forwards LER 83-010/03L-0 + (ML20071F227)
- ML20071F230 + (ML20071F230)
- 05000296/LER-1983-010-03, /03L-0:on 830209,main Steam Line Low Pressure Switch Found W/Low Setpoint.Caused by Instrument Drift. Switch 3-PS-1-76 Recalibr + (ML20071F233)
- ML20071F243 + (ML20071F243)
- ML20071F244 + (ML20071F244)
- 05000362/LER-1983-008, Forwards LER 83-008/03L-0 + (ML20071F249)
- 05000327/LER-1983-022, Forwards LER 83-022/03L-0 + (ML20071F255)
- 1CAN038301, Application for Amend to License DPR-51,revising Reactor Bldg Tendon Surveillance Requirement to Reduce Number of Tendons from 21 to 9 for Tenth Year & All Subsequent Tendon Surveillances + (ML20071F261)
- 05000254/LER-1983-008-03, /03L-0:on 830210,during Functional Test Qis 35-2, Fuel Pool Radiation Monitor 1-1705-16A Failed to Trip Upscale.Caused by Instrument Calibr Drift.Monitor Recalibr & Function Test Completed Satisfactorily + (ML20071F264)
- ML20071F265 + (ML20071F265)
- 05000331/LER-1983-004-03, /03L-0:on 830208,during Surveillance Testing,Rcic motor-operated full-flow Test Valve MOV-2515 Would Not Properly Control Flow.Caused by Loose Valve Stem anti- Rotation Collar Due to Worn,Loose Set Screws + (ML20071F267)
- 05000327/LER-1983-022-03, /03L-0:on 830211,two of Four Level Switches Found Out of Tolerance.Caused by Instrument Drift & Inadequate Calibr & Testing Techniques.Switches Recalibr + (ML20071F268)
- ML20071F279 + (ML20071F279)
- ML20071F283 + (ML20071F283)
- ML20071F284 + (ML20071F284)
- ML20071F287 + (ML20071F287)
- 05000362/LER-1983-008-03, /03L-0:on 830123,while in Mode 3,Channel a Level Indicator 3LI-1113-1 for Steam Generator E-089 Declared Inoperable When Indicator Failed Tech Spec Surveillance. Caused by Instrument Drift.Indicator Recalibr + (ML20071F291)
- ML20071F292 + (ML20071F292)
- 05000368/LER-1983-007, Forwards LER 83-007/03L-0 + (ML20071F294)
- 05000366/LER-1979-048, Forwards Updated LER 79-048/03X-1 + (ML20071F297)
- ML20071F298 + (ML20071F298)
- PLA-1507, Forwards Monthly Operating Rept for Jan 1983 + (ML20071F304)
- ML20071F306 + (ML20071F306)
- ML20071F307 + (ML20071F307)
- ML20071F311 + (ML20071F311)
- ML20071F319 + (ML20071F319)
- ML20071F327 + (ML20071F327)
- ML20071F329 + (ML20071F329)