- 05000387/LER-1982-056-03, /03L-0:on 821120,drywell Vacuum Relief Breaker Valves Were Inoperable Based on Incorrect Position Indication.Caused by Loose Collar on Valve Shaft & Failed Indication Bulb.Setscrew & Bulb Replaced + (ML20070L142)
- 05000328/LER-1982-138, Forwards LER 82-138/03L-0 + (ML20070L147)
- 05000328/LER-1982-138-03, /03L-0:on 821123,lower Containment Airlock Door Failed Air Leak Rate Test.Caused by Backed Off Packing Nut That Allowed Packing to Loosen.Nut Retightened & Door Tested.Design Change Request Submitted + (ML20070L153)
- 0CAN039101, Semiannual Radiological Effluent Release Rept for Jul-Dec 1990 + (ML20070L160)
- ML20070L164 + (ML20070L164)
- ML20070L170 + (ML20070L170)
- 05000361/LER-1982-139, Forwards LER 82-139/03L-0.Detailed Event Analysis Submitted + (ML20070L201)
- ML20070L205 + (ML20070L205)
- 05000361/LER-1982-139-03, /03L-0:on 821113,control Element Assembly 23 Slipped & Dropped in Excess of 5 Inches.Caused by Slow Operation of Grippers.Gripper Actuation Voltages Increased to Max.Startup Procedure S023-3-1.1 Revised + (ML20070L207)
- ML20070L211 + (ML20070L211)
- 05000327/LER-1982-139, Forwards LER 82-139/03L-0 + (ML20070L213)
- W3P82-3056, Forwards Suppl to 810707 Response to IE Bulletin 81-03, Flow Blockage of Cooling Water to Safety Sys Components by Corbicula Sp (Asiatic Clam) & Mytilus Sp (Mussel). Safety- Related Sys Approved & Satisfies Monitoring Requirements + (ML20070L218)
- 05000327/LER-1982-139-03, /03L-0:on 821125 & 28,containment Lower Airlock Door Failed Local Leak Rate Test.Caused by Loose or Damaged Packing in Handwheel Packing Box.Packing Replaced.Problem Under Investigation.Preventive Maint Program Developed + (ML20070L221)
- NRC-91-0029, Monthly Operating Rept for Feb 1991 for Fermi 2 + (ML20070L223)
- 05000259/LER-1982-099, Forwards LER 82-099/01T-0 + (ML20070L226)
- ML20070L232 + (ML20070L232)
- 05000259/LER-1982-099-01, /01T-0:on 821208,during Periodic Leak Detection Program,Weeping Leak Found in Cracked 1/2-inch Core Spray Sys Sample Connection Pipe.Caused by Fatigue Failure Induced by Vibration.Repairs Made + (ML20070L235)
- 05000296/LER-1982-056, Forwards LER 82-056/03L-0 + (ML20070L245)
- ML20070L250 + (ML20070L250)
- FVY-82-132, Provides Addl Info Re NUREG-0313,Revision 1,in Response to NRC .Info Reflects Util Position Re Intergranular Stress Corrosion Cracking as of Apr 1982 & May Be Subj to Change + (ML20070L254)
- ML20070L259 + (ML20070L259)
- 05000361/LER-1982-142-01, /01T-0:on 821128,emergency Chiller E-335 Declared Inoperable,Rendering Creacus Train B Inoperable.Caused by Failure of Resistance Temp Detector in Motor Winding High Temp Trip Circuit.Spare Resistance Temp Detector Installed + (ML20070L262)
- 05000296/LER-1982-056-03, /03L-0:on 821128,particulate Channel on 3-90-256 Drywell CAM Went Downscale Due to Moisture in Sample Chamber.Caused by Accumulation of Condensation in Sample Chamber of NMC Model AM-331F CAM.O-rings Replaced + (ML20070L266)
- 1CAN128209, Requests That 820929 Proposed Tech Spec Change Re Steam Line Break Instrumentation & Control Sys Setpoint Be Withdrawn, Since Concerns Expressed in NRC 821206 Request for Addl Info Cannot Be Adequately Addressed W/O Mods to Sys + (ML20070L274)
- 05000361/LER-1982-001-01, /01T-0:on 821128,emergency Chiller E-335 Declared Inoperable,Rendering Creacus Train B Inoperable.Caused by Failure of Resistance Temp Detector in Motor Winding High Temp Trip Circuit.Spare Resistance Temp Detector Installed + (ML20070L277)
- NLS9100117, Application for Amend to License DPR-46,revising Tech Specs Table 4.2.B Re Functional Test Frequency for RHR Sys Initiation & RHR Sys Pump & Valve Control Logic + (ML20070L291)
- 1CAN128206, Advises That Revisions to BAW-10154P, B&W Small Break LOCA ECCS Evaluation Model & BAW-10092P, Craft 2, Are Endorsed & Applicable to Facility + (ML20070L299)
- ML20070L301 + (ML20070L301)
- ML20070L303 + (ML20070L303)
- 05000354/LER-1991-004, :on 910203,ESF Actuation & Primary Containment Isolation Sys Actuation Occurred While Manipulating Vessel Level Instrument.Caused by Inherent Sensitivity of Reactor Vessel.Incident Will Be Reviewed W/Technicians + (ML20070L307)
- ML20070L310 + (ML20070L310)
- 05000277/LER-1991-005-01, :on 910212,primary Containment Isolation Sys Actuated Due to Blown Fuse During Removal of Blocking Permit Caused by Ground Created While Performing Mod Installation Work.Shift Permit Enforced + (ML20070L322)
- 05000275/LER-1982-012, Forwards LER 82-012/01T-0 + (ML20070L328)
- ML20070L332 + (ML20070L332)
- ML20070L333 + (ML20070L333)
- ML20070L339 + (ML20070L339)
- ML20070L341 + (ML20070L341)
- 05000341/LER-1991-002, :on 910215,emergency Diesel Generators 11 & 13 Inoperable Due to Problems on Woodard Governor Motor Operated Potentiometers.Edg Have Been Tested,Examined & Maint Procedures Will Be in Effect + (ML20070L343)
- 05000275/LER-1982-012-01, /01T-0:on 821206,radiation Survey of Spent Fuel Pool Not Performed in Accordance W/Tech Spec 3.3.3.1.Caused by Personnel Error.Technician Counseled + (ML20070L348)
- 05000366/LER-1982-115, Forwards LER 82-115/03L-0 + (ML20070L352)
- 05000366/LER-1982-115-03, /03L-0:on 821122,core Spray RHR Permissive Pressure Switch B Found Inoperable During Calibr Procedure. Caused by High Setpoint Micro Switch Failure to Actuate. Micro Switch Replaced,Calibr & Returned to Svc on 821217 + (ML20070L367)
- 0CAN128213, Forwards Final Response to NUREG-0612, Control of Heavy Loads at Nuclear Power Plants, Addressing Overhead Handling Sys in Vicinity of Fuel Storage Pools & Containment & Safe Load Paths + (ML20070L392)
- ML20070L402 + (ML20070L402)
- ML20070L409 + (ML20070L409)
- ML20070L413 + (ML20070L413)
- ML20070L415 + (ML20070L415)
- A09341, Responds to NRC 910211 Notice of Violation Noted in Insp Rept 336/90-22 & Forwards Payment of Civil Penalty in Amount of $50,000.Corrective Actions:Fuel Movement Halted When Atmospheric Dump Valve Discovered Open + (ML20070L438)
- ML20070L440 + (ML20070L440)
- ML20070L445 + (ML20070L445)
- ML20070L448 + (ML20070L448)
- ML20070L451 + (ML20070L451)