Search by property
Jump to navigation
Jump to search
This page provides a simple browsing interface for finding entities described by a property and a named value. Other available search interfaces include the page property search, and the ask query builder.
List of results
- 05000281/LER-1982-067-03, /03L-0:on 821109,w/unit at Full Power,Electrical Fire Barrier Penetration Found Improperly Sealed.Cause Unknown.Fire Watch Established & Penetration Temporarily Sealed.Permanent Sealing to Be Completed by 830101 + (ML20070D529)
- 05000395/LER-1982-040, Forwards LER 82-040/03L-0.Detailed Event Analysis Encl + (ML20070D535)
- ML20070D539 + (ML20070D539)
- 05000395/LER-1982-040-03, /03L-0:on 821108,Tech Spec 3.3.2 Had Not Been Complied W/Due to Improper Interpretation.Caused by Personnel Error.Ltr Issued Delineating Correct Interpretation of Tech Spec + (ML20070D542)
- 05000338/LER-1982-075, Forwards LER 82-075/03L-0 + (ML20070D546)
- 05000338/LER-1982-075-03, /03L-0:on 821119,individual Rod Position Indicator for Rods B-10 in Control Bank A,D-4 in Control Bank C & N-9 in Shutdown Bank A,Deviated from Group Demand Position W/No Rod Motion.Caused by Instrument Drift.Channels Recali + (ML20070D550)
- 05000395/LER-1982-039, Forwards LER 82-039/03L-0.Detailed Event Analysis Encl + (ML20070D555)
- NG-91-0222, Comment Supporting Proposed Rule on Secy 90-347 Re Regulatory Impact Survey Rept + (ML20070D556)
- L-82-531, Final Deficiency Rept 82-024 Re Defective Masonry Walls. Initially Reported on 821110.During Insp of as-built Masonry walls,31 Contained Less than Required Amount of Rebar Due to Design Misinterpretation.Walls Will Be Modified + (ML20070D560)
- 05000302/LER-1982-070, Forwards LER 82-070/03L-0.Detailed Event Analysis Encl + (ML20070D562)
- ML20070D566 + (ML20070D566)
- 05000395/LER-1982-039-03, /03L-0:on 821108,steam Generator Steam Flow Transmitter (FT-476) Power Supply Found Defective.Caused by Failure on Transmitter Power Supply (FQY-476).Channel Placed in Tripped Condition.Circuit Board Replaced & Tested + (ML20070D567)
- 05000260/LER-1982-036, Forwards LER 82-036/03L-0 + (ML20070D571)
- 05000302/LER-1982-070-03, /03L-0:on 821107,during Mode 1,nuclear Overpower Channel B Tripped Due to Failure of Reactor Coolant Flow Transmitter RC-14A-FT2.Caused by Shorted Capacitor in Power Supply.Capacitor Replaced & Transmitter Returned to Svc + (ML20070D575)
- 05000260/LER-1982-036-03, /03L-0:on 821113,during Refueling Outage,Reactor Bldg Continuous Air Monitor 2-90-250 Became Inoperable Due to Broken Drive Belt on Sample Pump.Caused by Normal Wear. Std v-belt for Switzer Model 325 Svc Air Pump Replaced + (ML20070D584)
- 05000302/LER-1982-071, Forwards LER 82-071/03L-0 + (ML20070D589)
- ML20070D590 + (ML20070D590)
- 05000296/LER-1982-053, Forwards LER 82-053/03L-0 + (ML20070D595)
- 05000302/LER-1982-071-03, /03L-0:on 821114,during Mode 1,radiation Monitor RM-A5,control Room Iodine Channel Found Inoperable.Caused by Failure of Rotary Selector Switch.Switch Replaced & Monitor Placed in Svc + (ML20070D599)
- ML20070D604 + (ML20070D604)
- 05000296/LER-1982-053-03, /03L-0:on 821111,while Performing Daily Background Source Check of Turbine Bldg Continuous Air Monitor 3-90-251,inlet Hose Found Disconnected.Probably Caused by Failure to Securely Latch Quick Disconnect Fittings + (ML20070D608)
- 05000325/LER-1982-137, Forwards LER 82-137/03L-0 + (ML20070D614)
- ML20070D618 + (ML20070D618)
- ML20070D623 + (ML20070D623)
- 05000325/LER-1982-137-03, /03L-0:on 821111,routine Surveillance Revealed That Indication of Drywell Oxygen Concentration Increased Abruptly from 1.2 to 3.1%.Caused by Failure of Atmosphere Analyzer 1-CAC-AT-1263-2 Due to Zero Shift.Unit Recalibr + (ML20070D624)
- 05000395/LER-1982-041-03, /03L-0:on 821109,during Mode 2,radiation Monitor RM-A1 (Control Room Isolation) Failed Surveillance Test Procedure 360.032.Caused by Instrument Drift.Monitor Calibr & Returned to Svc + (ML20070D646)
- JAFP-82-1261, Responds to NRC Re Violations Noted in IE Health Physics Appraisal Rept 50-333/80-20.Corrective Actions: Offgas Sys Undergoing Testing & Repair.Next Status Rept Will Be Filed by 830201 + (ML20070D655)
- ML20070D668 + (ML20070D668)
- ML20070D673 + (ML20070D673)
- ML20070D674 + (ML20070D674)
- ML20070D694 + (ML20070D694)
- 05000263/LER-1994-004-01, :on 940604 & 20,lightning Strikes Occurred, Resulting in Reactor Scram & Group 2 Containment Isolation, Respectively.Pressure Transmitter PT-7495A & Radiation Monitor RM-17-453B Will Be Modified + (ML20070D697)
- NRC-94-4189, Forwards Responses to NRC RAIs on AP600 from Ltrs of 940429, 0502,11 & 23.Rev to Response Previously Submitted Also Provided + (ML20070D700)
- ML20070D706 + (ML20070D706)
- ML20070D708 + (ML20070D708)
- ML20070D710 + (ML20070D710)
- ML20070D713 + (ML20070D713)
- ML20070D719 + (ML20070D719)
- 05000335/LER-1982-055, Forwards LER 82-055/03L-0 + (ML20070D720)
- ELV-02570, Forwards 1990 Annual Rept-Part 1 + (ML20070D724)
- 05000335/LER-1982-055-03, /03L-0:on 821109,control Element Assembly Motion Inhibit Circuit for Control Element Assembly Out of Sequence Deviation Scanner Failed.Caused by Failure of Relay in Out of Sequence Circuitry.Relay Replaced + (ML20070D725)
- ML20070D728 + (ML20070D728)
- ML20070D733 + (ML20070D733)
- PY-CEI-NRR-1817, Forwards Rev 2 to PDB-F0001, COLR for Perry Nuclear Power Plant,Unit 1 Cycle 5 (Reload 4) & Rev 0 to GE Rept 23A7227, Suppl Reload Licensing Rept for Perry Nuclear Power Plant Unit 1 Reload 4 Cycle 5 + (ML20070D737)
- ML20070D738 + (ML20070D738)
- ML20070D742 + (ML20070D742)
- ML20070D743 + (ML20070D743)
- ML20070D745 + (ML20070D745)
- ML20070D748 + (ML20070D748)
- ML20070D749 + (ML20070D749)