Search by property
Jump to navigation
Jump to search
This page provides a simple browsing interface for finding entities described by a property and a named value. Other available search interfaces include the page property search, and the ask query builder.
List of results
- 05000302/LER-1982-073-04, /04T-0:on 821126,isolation Setpoint on Liquid Waste Effluent Monitor (RM-L7) Not Sufficiently Conservative to Preclude Release in Excess of 10CFR20.Caused by Inadequate Process.Procedure Revised + (ML20070D415)
- ML20070D416 + (ML20070D416)
- ML20070D417 + (ML20070D417)
- ML20070D418 + (ML20070D418)
- ML20070D420 + (ML20070D420)
- ML20070D423 + (ML20070D423)
- ML20070D431 + (ML20070D431)
- 05000302/LER-1982-072, Forwards LER 82-072/03L-0 + (ML20070D436)
- 05000277/LER-1982-038-03, /03L-0:on 821106 & 08,isolation Valves SV2671C, SV2671D & SV2671A in Sample Lines to Oxygen Analyzers Failed to Fully Close.Caused by Accumulation of Dirt on Seat & Valve Disk.Valves Disassembled,Cleaned & Rebuilt + (ML20070D440)
- ML20070D443 + (ML20070D443)
- ML20070D446 + (ML20070D446)
- 05000302/LER-1982-072-03, /03L-0:on 821125,determined Reactor Coolant Water Leaking to Nuclear Svcs Closed Cycle Cooling Sys Through Letdown Cooler B.Caused by Thermal Shock Due to Long Isolation During Rapid Restoration to Svc.Cooler Replaced + (ML20070D449)
- 05000259/LER-1982-092, Forwards LER 82-092/03L-0 + (ML20070D457)
- 05000281/LER-1982-067, Forwards LER 82-067/03L-0 + (ML20070D462)
- 05000259/LER-1982-092-03, /03L-0:on 821116,reactor Pressure Switches PS-68-93 & PS-68-64 Found Operating Below Tech Spec Requirements.Caused by Calibr Drift.Switches Recalibr & Returned to Svc + (ML20070D467)
- 05000296/LER-1982-054, Forwards LER 82-054/03L-0 + (ML20070D471)
- L-82-529, Final Deficiency Rept 82-021 Re Incorrect Reactor Protective Sys Low Flow Input Signals.Initially Reported on 821013.Wiring Diagram & Polarity of Input Signal Cables Corrected.Deficiency Not Reportable Per 10CFR50.55(e) + (ML20070D476)
- 05000334/LER-1982-052, Forwards LER 82-052/03L-0 + (ML20070D478)
- SNRC-1791, Advises That a Mattessich (Senior Reactor Operator License SOP-4425-1) Permanently Assigned to Nine Mile Point Unit 2 & No Longer Needs to Maintain License at Shoreham + (ML20070D481)
- 05000296/LER-1982-054-03, /03L-0:on 821110 low-pressure Main Steamline Pressure Switch 3-PS-1-76 Had Setpoint Less than Tech Spec Requirements.Caused by Setpoint Drift.Switch Recalibr & Returned to Svc + (ML20070D484)
- SNRC-1794, Shoreham Nuclear Power Station Annual Operating Rept,1990 + (ML20070D485)
- SNRC-1790, Forwards Proposed Changes to Defueled TS Re Seismic Monitoring Instrumentation,Radiation Monitoring Instrumentation & Administrative Terminology,To Resolve Comments at 900802 Meeting W/Nrc + (ML20070D487)
- 05000395/LER-1982-038, Forwards LER 82-038/03L-0.Detailed Event Analysis Encl + (ML20070D489)
- ML20070D490 + (ML20070D490)
- ML20070D492 + (ML20070D492)
- 05000334/LER-1982-052-03, /03L-0:on 821105,leaking Fire Hydrant Reported in Southeast Yard.Cause Not Stated.Leak Isolated & Temporary Fire Hose Installed in Fuel Bldg to Insure Adequate Fire Protection + (ML20070D495)
- ML20070D500 + (ML20070D500)
- ML20070D501 + (ML20070D501)
- B13730, Responds to 910110 Telcon Request for Addl Info Re Spent Fuel Storage,Per Amend 39 to License NPF-49 Restricting Limited Storage of Spent Fuel in Spent Fuel Pool + (ML20070D508)
- 05000395/LER-1982-038-03, /03L-0:on 821114,main Control Board Indication for Steam Generator a Steam Flow (FT-474) Failed to Indicate Sys Flow.Caused by Indicator Needle Sticking to Lower Stop. Channel Calibr Performed + (ML20070D509)
- ML20070D514 + (ML20070D514)
- 05000247/LER-1982-045, Corrected LER 82-045/01T-0:on 821108,insp Revealed That Upper End Plug from Fuel Rod within Assembly Separated from Fuel Tube.Cause Not Stated.Assembly Replaced + (ML20070D516)
- ML20070D517 + (ML20070D517)
- ML20070D528 + (ML20070D528)
- 05000281/LER-1982-067-03, /03L-0:on 821109,w/unit at Full Power,Electrical Fire Barrier Penetration Found Improperly Sealed.Cause Unknown.Fire Watch Established & Penetration Temporarily Sealed.Permanent Sealing to Be Completed by 830101 + (ML20070D529)
- 05000395/LER-1982-040, Forwards LER 82-040/03L-0.Detailed Event Analysis Encl + (ML20070D535)
- ML20070D539 + (ML20070D539)
- 05000395/LER-1982-040-03, /03L-0:on 821108,Tech Spec 3.3.2 Had Not Been Complied W/Due to Improper Interpretation.Caused by Personnel Error.Ltr Issued Delineating Correct Interpretation of Tech Spec + (ML20070D542)
- 05000338/LER-1982-075, Forwards LER 82-075/03L-0 + (ML20070D546)
- 05000338/LER-1982-075-03, /03L-0:on 821119,individual Rod Position Indicator for Rods B-10 in Control Bank A,D-4 in Control Bank C & N-9 in Shutdown Bank A,Deviated from Group Demand Position W/No Rod Motion.Caused by Instrument Drift.Channels Recali + (ML20070D550)
- 05000395/LER-1982-039, Forwards LER 82-039/03L-0.Detailed Event Analysis Encl + (ML20070D555)
- NG-91-0222, Comment Supporting Proposed Rule on Secy 90-347 Re Regulatory Impact Survey Rept + (ML20070D556)
- L-82-531, Final Deficiency Rept 82-024 Re Defective Masonry Walls. Initially Reported on 821110.During Insp of as-built Masonry walls,31 Contained Less than Required Amount of Rebar Due to Design Misinterpretation.Walls Will Be Modified + (ML20070D560)
- 05000302/LER-1982-070, Forwards LER 82-070/03L-0.Detailed Event Analysis Encl + (ML20070D562)
- ML20070D566 + (ML20070D566)
- 05000395/LER-1982-039-03, /03L-0:on 821108,steam Generator Steam Flow Transmitter (FT-476) Power Supply Found Defective.Caused by Failure on Transmitter Power Supply (FQY-476).Channel Placed in Tripped Condition.Circuit Board Replaced & Tested + (ML20070D567)
- 05000260/LER-1982-036, Forwards LER 82-036/03L-0 + (ML20070D571)
- 05000302/LER-1982-070-03, /03L-0:on 821107,during Mode 1,nuclear Overpower Channel B Tripped Due to Failure of Reactor Coolant Flow Transmitter RC-14A-FT2.Caused by Shorted Capacitor in Power Supply.Capacitor Replaced & Transmitter Returned to Svc + (ML20070D575)
- 05000260/LER-1982-036-03, /03L-0:on 821113,during Refueling Outage,Reactor Bldg Continuous Air Monitor 2-90-250 Became Inoperable Due to Broken Drive Belt on Sample Pump.Caused by Normal Wear. Std v-belt for Switzer Model 325 Svc Air Pump Replaced + (ML20070D584)
- 05000302/LER-1982-071, Forwards LER 82-071/03L-0 + (ML20070D589)
- ML20070D590 + (ML20070D590)