Search by property
Jump to navigation
Jump to search
This page provides a simple browsing interface for finding entities described by a property and a named value. Other available search interfaces include the page property search, and the ask query builder.
List of results
- 05000346/LER-1982-043, Forwards LER 82-043/03L-0 + (ML20063P435)
- 05000366/LER-1982-109, Forwards LER 82-109/03L-0 + (ML20063P438)
- ML20063P440 + (ML20063P440)
- 2CAN108202, Responds to NRC Transmitting Amend 24 to License NPF-6 Re Seized Reactor Coolant Pump Shaft Event Reanalysis. Event Description & Results of Cycle 2 Seized Rotor Event Encl + (ML20063P442)
- 05000346/LER-1982-043-03, /03L-0:on 820829,fire Door 428C to Electrical Isolation Room 429A Found Cracked Open.Caused by Component Failure.Latch Mechanism Repaired + (ML20063P443)
- 05000247/LER-1982-035, Forwards LER 82-035/03L-0 + (ML20063P444)
- 05000254/LER-1982-027, Forwards LER 82-027/03L-0 + (ML20063P446)
- 05000366/LER-1982-109-03, /03L-0:on 820908,performance of RCIC Preventative Maint Procedure Disclosed Inoperability of RCIC Trip & Throttle Valve & RCIC Sys.Caused by Closure of Turbine Trip & Throttle Valve.Trip & Throttle Valve Opened + (ML20063P448)
- ML20063P452 + (ML20063P452)
- 05000247/LER-1982-035-03, /03L-0:on 820829,nuclear Power Range Instrumentation Channel N41 Became Inoperative Due to Failure of Power Supply Unit.Cause of Unit Failure Not Stated.Defective High Voltage Power Supply Removed + (ML20063P454)
- ML20063P459 + (ML20063P459)
- 05000373/LER-1982-100, Forwards LER 82-100/03L-0 + (ML20063P461)
- 05000259/LER-1982-070, Forwards LER 82-070/03L-0 + (ML20063P463)
- ML20063P465 + (ML20063P465)
- ML20063P466 + (ML20063P466)
- 05000373/LER-1982-100-03, /03L-0:on 820903,RCIC Equalizing Valves Failed to Close.Caused by Improperly Adjusted Spring Tension.Spring Tension Adjusted + (ML20063P468)
- ML20063P469 + (ML20063P469)
- ML20063P470 + (ML20063P470)
- 05000259/LER-1982-070-03, /03L-0:on 820908,while Calibr Reactor Protection Sys high-water Level Switches on Scram Discharge Tank,Level Switch LS-85-45E Operated at 27 Gallons,Contrary to Tech Specs.Caused by Calibr Drift on Level Switch SL-305-EI-X + (ML20063P471)
- 05000327/LER-1982-108, Forwards LER 82-108/03L-0 + (ML20063P475)
- ML20063P479 + (ML20063P479)
- 05000327/LER-1982-108-03, /03L-0:on 820907,during Mode 1,level Channel LT-63-50 on Refueling Water Storage Tank Declared Inoperable.Caused by Transmitter Out of Tolerance Due to Instrument Drift.Loop Recalibr + (ML20063P486)
- 05000335/LER-1982-041, Forwards LER 82-041/03L-0 + (ML20063P489)
- 05000317/LER-1982-056, Forwards LER 82-056/03L-0 + (ML20063P494)
- 05000335/LER-1982-041-03, /03L-0:on 820907,at 99% Power,Reactor/Turbine Trip Occurred Resulting in Brief Loss of Vital Buses & Iodine Spike.Caused by Motor Auxiliary Contact Initiating False Loss of Load & Inhibit Signals + (ML20063P496)
- 05000254/LER-1982-032, Forwards LER 82-032/03L-0 + (ML20063P498)
- ML20063P500 + (ML20063P500)
- ML20063P501 + (ML20063P501)
- ML20063P503 + (ML20063P503)
- 05000254/LER-1982-032-03, /03L-0:on 820905,HPCI Removed from Svc W/O Actuation of Electromatic Relief Valves.Caused by Need to Perform Scheduled Turbine Overspeed Surveillance Test.Hpci Sys Will Be Tested Operable Upon Return to Power + (ML20063P507)
- 05000325/LER-1982-093, Forwards Updated LER 82-093/03L-1 + (ML20063P509)
- 05000361/LER-1982-107-03, /03L-0:on 820902,condensate Storage Tank T-120 Water Level Fell Below Tech Spec Limit While in Mode 2. Caused by Inadequate Makeup Water Control.Corrective Actions Include Better Planning & Timely Water Transfer + (ML20063P511)
- ML20063P513 + (ML20063P513)
- 05000325/LER-1982-093-03, Review Revealed Inability of Reactor Protection Sys Logic Functional Test PT-01.1.10 to Provide for Electrical Continuity Testing of Input Signal Contacts of Backup Scram Logic Circuitry Solenoids + (ML20063P514)
- 05000361/LER-1982-119-03, /03L-0:on 820919,condensate Storage Tank T-120 Water Level Fell Below Tech Spec Limit While in Mode 2. Caused by Inadequate Makeup Water Control.Corrective Actions Include Better Planning & Timely Water Transfer + (ML20063P515)
- ML20063P516 + (ML20063P516)
- ML20063P517 + (ML20063P517)
- ML20063P518 + (ML20063P518)
- ML20063P519 + (ML20063P519)
- 05000361/LER-1982-121-03, /03L-0:on 820920,condensate Storage Tank T-120 Water Level Fell Below Tech Spec Limit While in Mode 2. Caused by Inadequate Makeup Water Control.Corrective Actions Include Better Planning & Timely Water Transfer + (ML20063P520)
- ML20063P521 + (ML20063P521)
- 05000280/LER-1982-091, Forwards LER 82-091/03L-0 + (ML20063P522)
- 05000254/LER-1982-025, Forwards LER 82-025/03L-0 + (ML20063P524)
- ML20063P526 + (ML20063P526)
- 05000280/LER-1982-091-03, /03L-0:on 820905,water & Sediment Found in Lube Oil of Charging Pump 1-CH-P-1A.Caused by Leak in One Tube of Lube Oil Cooler.Cooler Replaced,Oil Changed & Pump Returned to Svc + (ML20063P527)
- 05000282/LER-1982-016, Forwards LER 82-016/03L-0 + (ML20063P528)
- 05000254/LER-1982-025-03, /03L-0:on 820907,1/2A Standby Gas Treatment Train Heater Found Tripped During Procedure Qop 020-1.Caused by Conservative Switch Setting Due to Inadequate Setpoint Differences.Heater Trip Reset + (ML20063P530)
- 05000313/LER-1982-025, Forwards LER 82-025/03L-0 + (ML20063P533)
- 05000289/LER-1982-013, Forwards LER 82-013/03L-0 + (ML20063P537)
- 05000302/LER-1982-057, Forwards LER 82-057/03L-0 + (ML20063P541)
- 05000313/LER-1982-025-03, /03L-0:on 820828,electrical Jumpers Discovered Across Trip Contacts of Shutdown Bypass High Pressure Trip Bistables for a & D Reactor Protection Sys Channels.Caused by Personnel Error.Jumpers Removed + (ML20063P544)