List of results
- ML20063L861 + (ML20063L861)
- 05000333/LER-1982-034-03, /03X-1:on 820713,instrument Flow Components Drift Resulted in Nonconservative Calculation of Core Thermal Power.Rated Thermal Power Limit Exceeded on Approx 75 Days of Cycle 5 Operation.Caused by Instrument Drift + (ML20063L869)
- 05000259/LER-1982-055, Forwards LER 82-055/03L-0 + (ML20063L871)
- 05000369/LER-1993-011, :on 931115,determined That DG 1B Fuel Storage Tank Level Gauge Out of Tolerence Due to Malfuntion of Subj Gauge.Iae Technician Calibrated Level Gauge to Bring Gauge Back Into Tolerence + (ML20063L874)
- ML20063L886 + (ML20063L886)
- 05000259/LER-1982-055-03, /03L-0:on 820807,environ Data Station Delta Air Temp for 620-737 MSL (TDR-90-103) & 620-887 MSL (TDR-90-140) Observed to Read Downscale.Caused by Hewlett Packard Model 3450 Digital Voltmeter Failing on Ohms Range + (ML20063L900)
- ML20063L903 + (ML20063L903)
- ML20063L905 + (ML20063L905)
- 05000244/LER-1982-018, Forwards LER 82-018/03L-0 + (ML20063L913)
- 05000315/LER-1982-064-03, /03L-0:on 820803,fire Doors 460 & 462 of 4-kV Switchgear Room Found Open W/Doors Blocked by Air Hose. Caused by Personnel Error.Hose Removed.Training Conducted & Need to Comply W/Posted Requirements Emphasized + (ML20063L916)
- LIC-94-0047, Comment on Draft NUREG-1482, Guidelines for IST Programs at Npps. Licensee Should Not Have to State in IST Program Methods of Ensuring Code Compliance,If Licensee Complying W/ Code + (ML20063L922)
- 05000244/LER-1982-018-03, /03L-0:on 820730,computer Alarm Received, Indicating RPI for Control Rod Bank a Group 2 Position HO2 Deviated from Control Rod Bank a by 12 Steps.Caused by Instrument Drift.Rpi Adjusted to Correct Drift + (ML20063L924)
- RC-94-0057, Comment Supporting NUREG-1488, Revised Livermore Seismic Hazard Estimates for 69 NPP Sites East of Rocky Mountains + (ML20063L925)
- 05000315/LER-1982-065-03, /03L-0:on 820804,containment Area Monitor R-2 Trip Alarm Setpoint Set Above Tech Spec Limits to Free Fuel Assembly Caught on Containment Upender Cable.Caused by Conscious Decision to Violate Tech Specs + (ML20063L927)
- 05000482/LER-1994-002, :on 940124,WCGS Entered TS 3.1.3.1 Action Statement (c)(4) Due to Electrical Problem W/Crdm M-12. Caused by Loose Cable Connector for CRDM M-12.Maint Performed on Connector + (ML20063L930)
- 05000336/LER-1982-034, Forwards LER 82-034/03L-0 + (ML20063L931)
- ML20063L935 + (ML20063L935)
- 05000315/LER-1982-066-03, /03L-0:on 820805,surface Cracks Discovered in Two Portions of Divider Barrier Seal.Cause Could Not Be Determined.Affected Portions of Seal Replaced W/Uniroyal H300.Matl Replaced in Areas Similar to Cracked Areas + (ML20063L936)
- 05000315/LER-1982-067-03, /03L-0:on 820816,fire Door 373 Would Not Latch. Caused by Loose & Missing Screws.Screws Replaced/Tightened & Staked.Insp Procedure Changed to Require Staking of All Screws in Doors & Associated Hardware + (ML20063L938)
- 05000336/LER-1982-034-03, /03L-0:on 820801,while Performing Plant Heatup, Change from Mode 5 to Mode 4 Was Made W/O Performing Required Surveillance of Containment Personnel Airlock. Caused by Operator Error + (ML20063L941)
- 05000315/LER-1982-068-03, /03L-0:on 820817,4-kV Switchgear Room Cardox Sys Isolated W/No Names on Entry Board & No Personnel in Room. Caused by Personnel Error.Technician Had Erased Name But Failed to Return Carbon Dioxide Switch to Normal + (ML20063L946)
- ML20063L955 + (ML20063L955)
- JAFP-94-0116, Forwards Ja FitzPatrick Nuclear Power Plant Effluent & Waste Disposal Semiannual Rept Jul-Dec 1993 & Rev 0 to DVP-01.02, Radiological Effluent Controls & Odcm + (ML20063L957)
- ML20063L960 + (ML20063L960)
- ML20063L962 + (ML20063L962)
- 05000362/LER-1993-005, :on 931130,containment Isolation Valve 3HV6371 Failed to Open.Caused by Inverted Upstream Skirt.Valve Correctly Assembled,Tested & Determined Operable During Refueling Outage + (ML20063L970)
- ML20063L983 + (ML20063L983)
- ML20063L997 + (ML20063L997)
- ML20063M000 + (ML20063M000)
- ML20063M002 + (ML20063M002)
- ML20063M003 + (ML20063M003)
- ML20063M004 + (ML20063M004)
- ML20063M005 + (ML20063M005)
- ML20063M008 + (ML20063M008)
- ML20063M010 + (ML20063M010)
- ML20063M015 + (ML20063M015)
- ML20063M017 + (ML20063M017)
- LIC-94-0042, Forwards Fort Calhoun Station Performance Indicators Jan 1994 + (ML20063M019)
- ML20063M023 + (ML20063M023)
- LIC-94-0050, Special Rept:On 940120,discovered That Seal Around Penetration 56E-F-331 Degraded Due to Time Required to Repair Penetration Seal.Penetration Returned to Functional Status & Fpip 3776 Closed + (ML20063M030)
- ML20063M032 + (ML20063M032)
- ML20063M033 + (ML20063M033)
- ML20063M037 + (ML20063M037)
- ML20063M040 + (ML20063M040)
- ML20063M043 + (ML20063M043)
- ML20063M047 + (ML20063M047)
- ML20063M055 + (ML20063M055)
- ML20063M064 + (ML20063M064)
- ML20063M070 + (ML20063M070)
- ML20063M078 + (ML20063M078)
- ML20063M085 + (ML20063M085)