- ML20055A098 + (ML20055A098)
- 05000250/LER-1982-008, Forwards LER 82-008/03L-0 + (ML20055A099)
- ML20055A101 + (ML20055A101)
- ML20055A102 + (ML20055A102)
- 05000280/LER-1982-026-03, /03L-0:on 820618,electrical Penetration Found Improperly Sealed.Caused by Personnel Failure to Restore Penetration to Original State Following Cable Installation. Penetration Sealed + (ML20055A104)
- ML20055A105 + (ML20055A105)
- ML20055A106 + (ML20055A106)
- 05000250/LER-1982-008-03, /03L-0:on 820609,3A High Head Safety Injection Pump Failed to Start from Manual Operation of Normal Control Switch.Cause Not Determined.Breaker Control Panel Fuses Replaced & Breaker Racked Out & Backed in + (ML20055A108)
- ML20055A109 + (ML20055A109)
- ML20055A110 + (ML20055A110)
- ML20055A112 + (ML20055A112)
- 05000327/LER-1982-078, Forwards LER 82-078/03L-0 + (ML20055A113)
- ML20055A115 + (ML20055A115)
- IR 05000518/1982007 + (ML20055A116)
- ML20055A117 + (ML20055A117)
- 05000259/LER-1982-039-03, /03L-0:on 820609,fuse 16A-F19 Blew Due to Failure of Coil for Relay 16A-K66B,resulting in Inboard Primary Containment Isolation.Caused by Short in Coil for Relay 16A-K66B.Fuse & Relay Coil Replaced + (ML20055A118)
- ML20055A119 + (ML20055A119)
- ML20055A120 + (ML20055A120)
- ML20055A121 + (ML20055A121)
- ML20055A122 + (ML20055A122)
- ML20055A123 + (ML20055A123)
- ML20055A124 + (ML20055A124)
- 05000327/LER-1982-078-03, /03L-0:on 820613,oxygen Concentration in Waste Gas Decay Tank J Was Higher than Tech Spec Limit W/Hydrogen Concentration Greater than 4%.Caused by Air Leakage in Monitor Sample Lines.Oxygen Concentration Reduced + (ML20055A125)
- ML20055A126 + (ML20055A126)
- 05000327/LER-1982-074, Forwards LER 82-074/03L-0 + (ML20055A128)
- 05000335/LER-1982-022-03, /03L-0:on 820609,subcooled Margin Monitor Failed to Operate.Caused by 1A2 Tc Input Transmitter Failure.Lead from Transmitter Lifted & Subcooled Monitor Returned to Svc on 820610 + (ML20055A130)
- ML20055A131 + (ML20055A131)
- ML20055A132 + (ML20055A132)
- ML20055A133 + (ML20055A133)
- 05000366/LER-1982-034, Forwards LER 82-034/03L-0 + (ML20055A134)
- IR 05000275/1982020 + (ML20055A136)
- 05000325/LER-1982-063-03, /03L-0:on 820609,erratic post-accident Monitoring Control Room Recorder/Indicator,Indications & Recordings Received.Caused by Shifting of Instrument Timing Sequence + (ML20055A137)
- ML20055A138 + (ML20055A138)
- ML20055A139 + (ML20055A139)
- ML20055A140 + (ML20055A140)
- ML20055A141 + (ML20055A141)
- 05000327/LER-1982-074-03, /03L-0:on 820605,train B Automatic Control Valve 1-LCV-3-171 & Train a Valve 1-PCV-3-122 Declared Inoperable. Inoperability Caused by Failed Controller & Failed Hydraulic Pump Motor Due to Deadheaded Pump + (ML20055A143)
- ML20055A144 + (ML20055A144)
- IR 05000338/1982008 + (ML20055A145)
- 05000366/LER-1982-034-03, /03L-0:on 820622,control Room Received Low Pressure Alarm on Hydraulic Control Unit 26-19.Caused by Setpoint Drift.Pressure Switch Recalibr & Returned to Svc + (ML20055A146)
- ML20055A147 + (ML20055A147)
- IR 05000280/1982002 + (ML20055A149)
- ML20055A150 + (ML20055A150)
- BSEP-82-1455, Advises That High Pressure Annunciators Will Not Be Installed on Instrument Air Headers to Safety Relief Valves Per 810320 Commitment,In Response to IE Bulletin 80-25.New Solenoids Should Be Available During 1983-84 Refueling + (ML20055A152)
- ML20055A153 + (ML20055A153)
- IR 05000454/1982008 + (ML20055A154)
- ML20055A155 + (ML20055A155)
- ML20055A157 + (ML20055A157)
- ML20055A158 + (ML20055A158)
- IR 05000528/1982019 + (ML20055A159)
- ML20055A160 + (ML20055A160)