- 05000364/LER-1982-017-03, /03L-0:on 820427,during Full Length Control Rod Operability test,FNP-2-STP-5.0 Group 1 & Control Banks a, Group 1 & B,Group 1 Control Rods Declared Inoperable.Caused by Faulty Slave Cycler Counter Card.Card Replaced + (ML20053D582)
- ML20053D583 + (ML20053D583)
- ML20053D584 + (ML20053D584)
- 05000364/LER-1982-019-03, /03L-0:on 820430,pressurizer Pressure Fell Below Tech Spec Limit.Caused by Transient in Pressurizer Pressure Transmitter PT-444 Opening Spray Valve.Pressure Restored + (ML20053D586)
- ML20053D587 + (ML20053D587)
- 05000321/LER-1982-036, Forwards LER 82-036/03L-0 + (ML20053D588)
- ML20053D590 + (ML20053D590)
- ML20053D592 + (ML20053D592)
- ML20053D594 + (ML20053D594)
- 05000321/LER-1982-036-03, /03L-0:on 820429,1B21-R615 Reactor Level Recorder Found Inoperative.Caused by Open Resistor R18 in Recorder Amplifier.Component Replaced & Recorder Recalibr + (ML20053D595)
- ML20053D596 + (ML20053D596)
- ML20053D597 + (ML20053D597)
- ML20053D598 + (ML20053D598)
- ML20053D599 + (ML20053D599)
- ML20053D600 + (ML20053D600)
- 05000366/LER-1982-048, Forwards LER 82-048/03L-0 + (ML20053D601)
- ML20053D603 + (ML20053D603)
- 05000259/LER-1982-028-03, /03L-0:on 820428,phase C Relay of 4-kv Shutdown Board D Tripped Above Max Allowable Value.Caused by Instrument drift.Gould-Brown Boveri Ite 27/59H Relay Recalibr.Tests Will Be Completed by 820801 + (ML20053D604)
- ML20053D605 + (ML20053D605)
- 05000366/LER-1982-048-03, /03L-0:on 820506,core Spray Sys & LPCI Sys Discovered Inoperable.Caused by Personnel Error.Lpci & Core Spray Loops Aligned to Torus W/Torus Inoperable Due to Inoperable Level Instrumentation + (ML20053D606)
- ML20053D607 + (ML20053D607)
- ML20053D611 + (ML20053D611)
- ML20053D613 + (ML20053D613)
- 05000348/LER-1982-021-03, /03L-0:on 820428,2A Recombiner Oxygen Outlet Analyzer Declared Inoperable When B2 Oxygen Fuel Cell Failed.Cause Not Stated.Fuel Cell Replaced + (ML20053D615)
- ML20053D617 + (ML20053D617)
- ML20053D621 + (ML20053D621)
- ML20053D622 + (ML20053D622)
- 05000298/LER-1982-009-03, /03L-0:on 820428,suppression Chamber Level Instrument PC-LI-13 Failed full-scale.Caused by Personnel Error.Ref Water Leg Drained While Collecting Torus Water Sample.Level Transmitter Replaced.Sampling Valve Tagged + (ML20053D623)
- 05000368/LER-1982-016, Forwards LER 82-016/03L-0 + (ML20053D624)
- ML20053D626 + (ML20053D626)
- ML20053D627 + (ML20053D627)
- 05000368/LER-1982-016-03, /03L-0:on 820505,electrolyte Levels of Battery Cells in 2D-12 Found Above Max Tech Spec Levels.Caused by Over Charging Battery to Raise Cell Voltages.Electrolyte Removed from Cells + (ML20053D628)
- ML20053D629 + (ML20053D629)
- ML20053D630 + (ML20053D630)
- ML20053D631 + (ML20053D631)
- ML20053D632 + (ML20053D632)
- 05000321/LER-1982-040, Forwards LER 82-040/03L-0 + (ML20053D634)
- ML20053D636 + (ML20053D636)
- ML20053D637 + (ML20053D637)
- ML20053D638 + (ML20053D638)
- ML20053D639 + (ML20053D639)
- 05000321/LER-1982-040-03, /03L-0:on 820430,during Testing,Rhr Svc Water Pump IE11-C001A Failed to Meet Rated Flow Requirements of Tech Specs.Caused by Failed Mechanical Seal.Mechanical Seal Replaced + (ML20053D640)
- ML20053D641 + (ML20053D641)
- 05000327/LER-1982-054, Forwards LER 82-054/03L-0 + (ML20053D643)
- ML20053D645 + (ML20053D645)
- 05000324/LER-1982-059, Forwards LER 82-059/03L-0 + (ML20053D646)
- ML20053D648 + (ML20053D648)
- 05000327/LER-1982-054-03, /03L-0:on 820502,at 100% Power,Steam Generator Blowdown Containment Isolation Valve 1-FCV-1-25 Would Not Reopen After Blowdown Was Isolated.Caused by Ruptured Valve Operator Diaphragm.Diaphragm Replaced + (ML20053D649)
- 05000324/LER-1982-059-03, /03L-0:on 820426,during Refueling While Realigning Core Spray Subsystem Pump Suction to Core Spray Tank Vs Suppression Pool,Tank Water Inventory Fell Below Tech Spec Requirement.Caused by Personnel Error.Inventory Restored + (ML20053D652)
- 05000339/LER-1982-018, Forwards LER 82-018/03L-0 + (ML20053D653)