- ML20050A849 + (ML20050A849)
- ML20050A850 + (ML20050A850)
- 05000339/LER-1982-005-03, /03L-0:on 820222,in Mode 1,2J Emergency Diesel Generator Fire Door (S71-16) Between Diesel Room & Turbine Bldg Would Not Latch.Caused by Door Lock Tumbler Rotating on Axis & Not Engaging Latch.Lock Tumbler Tightened + (ML20050A851)
- ML20050A852 + (ML20050A852)
- 05000317/LER-1982-008, Forwards LER 82-008/03L-0 + (ML20050A853)
- ML20050A855 + (ML20050A855)
- ML20050A856 + (ML20050A856)
- 05000317/LER-1982-008-03, /03L-0:on 820303,during Power Operation,While Restoring Component Cooling Lineup to Normal,Component Cooling HX 11 Discovered Isolated for 13-h.Caused by Failure to Log HX Inlet Valves in Locked Valve Deviation Log + (ML20050A857)
- 05000311/LER-1982-014, Forwards LER 82-014/03L-0.Detailed Event Analysis Encl + (ML20050A860)
- 05000338/LER-1982-011, Forwards LER 82-011/03L-0 + (ML20050A863)
- 05000304/LER-1982-003-03, /03L-0:on 820305,while Performing Safeguards Logic Testing Per Procedure PT-10c,relays SIB1 for Trains a & B Malfunctioned,Resulting in Block of Si.Caused by Maladjustment of Relays.Relays Replaced + (ML20050A865)
- 05000325/LER-1982-026, Forwards LER 82-026/03L-0 + (ML20050A866)
- 05000338/LER-1982-011-03, /03L-0:on 820223,at 90% Power & Decreasing,Axial Flux Difference Deviated Greater than -5% from Target for 23 Minutes.Caused by Rapid Power Reduction Necessitated by Leak in Turbine Gland Steam Exhaust Sys + (ML20050A868)
- 05000311/LER-1982-014-03, /03L-0:on 820219,steam Generator 21 Level Channel 2 Read 20% Higher than Channels 3 & 4.Channel 2 Declared Inoperable.Cause Unknown.Transmitter Tested & Found Satisfactory.Sensing Lines Blown Down to Remove Solids + (ML20050A869)
- ML20050A870 + (ML20050A870)
- ML20050A872 + (ML20050A872)
- 05000338/LER-1982-007, Forwards LER 82-007/03L-0 + (ML20050A873)
- 05000324/LER-1982-037, Forwards LER 82-037/03L-0 + (ML20050A877)
- ML20050A879 + (ML20050A879)
- 05000324/LER-1982-037-03, /03L-0:on 820216,during Routine Surveillance, Diesel Generator 4 Control Air Pressure Found Below Tech Spec Psig Limit.Caused by Crud Accumulation in Filter Valve Preventing Proper Seating.Crud Removed + (ML20050A882)
- ML20050A883 + (ML20050A883)
- 05000338/LER-1982-007-03, /03L-0:on 820214,in Mode 1,fire Door S71-7 Declared Inoperable.On 820216,fire Doors A19-1 & A44-1 Declared Inoperable.Caused by Failure of Closures & Latching Mechanisms Due to Excessive Use.Locks Readjusted/Repaired + (ML20050A885)
- ML20050A886 + (ML20050A886)
- 05000324/LER-1982-019, Forwards LER 82-019/03L-0 + (ML20050A887)
- ML20050A889 + (ML20050A889)
- ML20050A890 + (ML20050A890)
- ML20050A891 + (ML20050A891)
- ML20050A892 + (ML20050A892)
- ML20050A893 + (ML20050A893)
- 05000324/LER-1982-019-03, /03L-0:on 820214,during operation,post-accident Drywell Particulate Radiation Detection Instrument 2-CAC- AQH-1262-1 Indicated Downscale.Caused by Moisture in Sampling Chamber.Moisture Removed & Probe Replaced + (ML20050A894)
- 05000316/LER-1982-017, Forwards LER 82-017/03L-0 + (ML20050A895)
- 05000328/LER-1982-019, Forwards LER 82-019/03L-0 + (ML20050A897)
- ML20050A899 + (ML20050A899)
- 05000316/LER-1982-017-03, /03L-0:on 820223,during Rollup of Main Turbine in Preparation for Placing Unit in Svc,Pressurizer Pressure Decreased Below Tech Spec Limit.Caused by Unexpected Decrease in Condenser Vacuum + (ML20050A901)
- ML20050A902 + (ML20050A902)
- ML20050A903 + (ML20050A903)
- 05000327/LER-1982-029, Forwards LER 82-029/03L-0 + (ML20050A904)
- 05000328/LER-1982-019-03, /03L-0:on 820211 During startup,turbine-driven Auxiliary Feedwater Pump Declared Inoperable When Outboard Seal Packing Blew Out.Caused by Normal Deterioration of Packing & Wear of Shaft Sleeve.Packing Replaced + (ML20050A906)
- ML20050A907 + (ML20050A907)
- 05000259/LER-1982-016, Forwards LER 82-016/03L-0 + (ML20050A908)
- 05000327/LER-1982-029-03, /03L-0:on 820215,w/unit in Mode 3,glycol Containment Isolation Valve 1-FCV-61-194 Would Not Reopen When Stroked from Full Open Position.Caused by Conductor G1B1 Not Being Terminated.Conductor Reterminated + (ML20050A910)
- ML20050A911 + (ML20050A911)
- 05000324/LER-1982-034, Forwards LER 82-034/03L-0 + (ML20050A912)
- TXX-3502, Forwards Tables 1 & 2 Re Functional Capability of Class 2 & 3 Austenitic Stainless Steel Pipe Bends & Elbows + (ML20050A914)
- PNO-III-82-032, on 820325,shift Engineer Exposed to 3,600 Mrems During Planned Entry Into Reactor Cavity Beneath Reactor Vessel.Region III Radiation Specialist Will Visit Site & Evaluate Overexposure + (ML20050A915)
- 05000259/LER-1982-016-03, /03L-0:on 820217,during Operation,Reactor Low Water Level Switch 1 (1-LIS-3-203C) Had as-found Calibr of 537.31 Inches.Caused by Instrument Drift.Switch Recalibr & Functionally Tested + (ML20050A916)
- ML20050A917 + (ML20050A917)
- ML20050A918 + (ML20050A918)
- ML20050A920 + (ML20050A920)
- 05000324/LER-1982-034-03, /03L-0:on 820216,while Performing Channel Calibr, PT 4.1.1PC,exhaust Ventilation Radiation High instrument,2- D12-RM-N010A Inadvertently Actuated.On 820217,similar Event Occurred w/2-D12-RM-N010B.Caused by Accidental Jumperi + (ML20050A921)
- ML20050A922 + (ML20050A922)